Tender For Repair / Replacement And Maintenance Of 66/11 Kv Sub Station Alongwith Other Connected Works Under Age E/M-Ii Of Ge 865 Ews
Tender Overview
Project Description
Tender For Repair / Replacement And Maintenance Of 66/11 Kv Sub Station Alongwith Other Connected Works Under Age E/M-Ii Of Ge 865 Ews
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 15-Nov-2026 | Revised NIT amount | Other | 30-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Disconnecting of HT supply from 11 KV VCB of any make/type/capacity for repair works, servicing and taking out trolley with complete decarburizing the contact points, cleaning with CRC solution and inner body cleaning with vaccum cleaner etc. and repair/replacement of defective parts found during servicing. Reassembling and testing of relays for tripping time setting, over current setting, earth fault setting etc. including checking of vaccum intrupter, tripping mechanism and ratchet wheel & spring charging mechanism etc. after servicing, complete all as specified and/or as directed by Engr-in-Charge. |
| 2 | Disconnecting of HT supply from 66 KV VCB/SF-6 breaker of any make/type/capacity for repair works, servicing and taking out trolley with complete decarburizing the contact points, cleaning with CRC solution inner body cleaning with vaccum cleaner etc. and repair/replacement of defective parts found during servicing. Reassembling and testing of relays for tripping time setting, over current setting, earth fault setting etc. including checking of its control panel and power TR protection system such as defferential relay, master trip relay, power TR oil/windinding temp, bucolz relay and mechanical system etc. after servicing testing, complete all as specified and/or as directed by Engr-in-Charge. |
| 3 | Note for Srl item No 1.00 to 2.00 :(i) Spare parts will be measured and paid for separately under respective item and if copper wire and ferule required for wiring include in this items.(ii) For testing and calibration of relays will be measured and paid separately under respective items. |
| 4 | Taking out IDMT relays from panel. Opening it for repair work, servicing complete with decarburizing the contact points, cleaning with CRC solution and inner body clean with vaccum cleaner etc. and repair/replacement of all defective parts if any found during servicing. Reassembling and testing of relays for tripping time setting, over current setting, earth fault setting etc. (ii) For testing and calibration of relays will be measured and paid separately under respective items. Note :- All parts are deemed to be included in this item rate required for relay in service condition. |
| 5 | Supply only of following parts of HT VCB for item No 1.00 & 2.00 above :- |
| 6 | Spring charging motor 24-30/240 Volt DC/AC for 66 KV VCB/SF-6 breaker of existing make, type, size & capacity complete. Make : As per existing sample all as specified and directed at site. |
| 7 | Spring charging motor 30/240 Volt DC/AC for 11KV VCB of existing make, type, size & capacity complete suitable for existing VCBs. Make : As per existing sample all as specified and directed at site. |
| 8 | Open/Close auxiliary contacts switch suitable for upto 1600 Amp HT VCB. Make/Type- As per existing sample. |
| 9 | Open/Close auxiliary contacts switch suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 10 | Plug-Socket connectors of electrical accessories suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 11 | Door locking handle suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 12 | Trolly alignment lever suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 13 | Under voltage release suitable for 1600 Amps HT VCB. Make/Type- As per existing sample. |
| 14 | Under voltage release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 15 | Over voltage release suitable for 1600 Amps HT VCB. Make/Type- As per existing sample. |
| 16 | Over voltage release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 17 | Under/over frequency release suitable for 1600 Amps HT VCB. Make/Type- As per existing sample. |
| 18 | Under/over frequency release suitable for upto 1250 Amps HT VCB. Make/Type- As per existing sample. |
| 19 | Shunt trip closing coil assembly 66 KV SF6 Breaker 24-30/220 volts, DC/AC. Make/Type- As per existing sample. |
| 20 | Shunt trip tripping coil assembly 66 KV SF6 Breaker 24-30/220 volts, DC/AC. Make/Type- As per existing sample. |
| 21 | Shunt trip closing coil assembly 24-30/220 volts, DC/AC for HT VCB. Make/Type- As per existing sample. |
| 22 | Shunt trip tripping coil assembly 24-30/220 volts, DC/AC for HT VCB. Make/Type- As per existing sample. |
| 23 | Series trip coil 24-30/220 volts, DC/AC for HT VCB. Make/Type- As per existing sample. |
| 24 | Spring charging Motor Cut of switch. Make/Type- As per existing sample. |
| 25 | Ratchet wheel assembly (small, large & middle gear assy). Make/Type- As per existing sample. |
| 26 | Manual spring charging gear assembly complete. Make/Type- As per existing sample. |
| 27 | Breaker IN/OUT handle. Make/Type- As per existing sample. |
| 28 | Local remote switch. Make/Type- As per existing sample. |
| 29 | Test/service position indicator. Make/Type- As per existing sample. |
| 30 | Breaker control switch. Make/Type- As per existing sample. |
| 31 | Mechanism charged/discharge indicator switch. Make/Type- As per existing sample. |
| 32 | Toggle ON/OFF switch for Heater & illumination circuit. Make/Type- As per existing sample. |
| 33 | Mechanical ON/OFF indication. |
| 34 | Door switch. Make/Type- As per existing sample. |
| 35 | Auto/Manual selection switch. Make/Type- As per existing sample. |
| 36 | Push button. Make/Type- As per existing sample. |
| 37 | ON/OFF Emergency trip push button. Make/Type- As per existing sample. |
| 38 | Indicator lamp LED type complete with holder to read RYB with necessary wiring complete. |
| 39 | Operation counter. Make/Type- As per existing sample. |
| 40 | Selector switch for voltmeter- 4 position (RY-YB-BR-OFF), 3 ways . |
| 41 | TNC control switch with pistol grip. |
| 42 | Spring charging handle. |
| 43 | VCB operating handle. |
| 44 | Terminal connectors. |
| 45 | Annunciator, 4 Window with existing dimension on panel for OC/EF/WTI/OTI/ Bucholz trip, with inbuilt PB of mute, ACK, Reset, Accept. |
| 46 | Master relay operating voltage 24V/110V DC or as per sample complete all as directed. |
| 47 | Spacer Heater. Make/Type- As per existing sample. |
| 48 | Thermostate 30-90 Deg. |
| 49 | Hooters. Make/Type- As per existing sample. |
| 50 | Terminal Block for CT wire. |
| 51 | Terminal Block for Remote feedback/within panel/board wire |
| 52 | NO/NC Contacts. Make/Type- As per existing sample. |
| 53 | Bridge rectifier. Make/Type- As per existing sample. |
| 54 | Auxiliary switch 7NO + 7NC. Make/Type- As per existing sample. |
| 55 | \\"ZZ\\" micro switch. Make/Type- As per existing sample. |
| 56 | Butterfly switch for motor cut off. Make/Type- As per existing sample. |
| 57 | Motor cut off switch (Cherry). Make/Type- As per existing sample. |
| 58 | Timer for spring charging motor. Make/Type- As per existing sample. |
| 59 | Drive link assembly with adjuster. Make/Type- As per existing sample. |
| 60 | Big cam with main shaft with bearing & cover. Make/Type- As per existing sample. |
| 61 | Trip /Close shaft assembly with springs & closing strips. Make/Type- As per existing sample. |
| 62 | 11KV, VCB fixed contact suitable for 1600Amp capacity. Make/Type- As per existing sample. |
| 63 | 11KV, VCB moving contact suitable for upto 1600Amp capacity. Make/Type- As per existing sample. |
| 64 | 11KV, VCB fixed contact suitable for 1250Amp capacity. Make/Type- As per existing sample. |
| 65 | 11KV, VCB moving contact suitable for 1250Amp capacity. Make/Type- As per existing sample. |
| 66 | Spout insulator incl hardware suitable for 11KV VCB of various capacity. Make/Type- As per existing sample. |
| 67 | Spur gear of sizes as per sample suitable for upward or downward trolly movement mechanism with lock and bushing as required for 11KV VCB/bus coupler complete. Make/Type- As per existing sample, all as specified and directed by Engr-in-charge. |
| 68 | Trip shackle lever. Make/Type- As per existing sample. |
| 69 | Ratchet Pin suitable for HT VCB. Make/Type- As per existing sample. |
| 70 | Insulated dust proof cover frame. Make/Type- As per existing sample. |
| 71 | Push Rod. Make/Type- As per existing sample. |
| 72 | Fuses holder suitable for cylindrical/DIN fuse. |
| 73 | HRC fuse (link type) having capacity 2 to 6 Amp, 415 V, 80 KA. |
| 74 | HRC fuse (link type) having capacity 10 to 32 Amp, 415 V, 80 KA. |
| 75 | 11 KV, VCB, PT fuse 3.15 Amp complete as per sample. |
| 76 | Stud type terminals of 30V/110V DC suitable for 11KV VCB. |
| 77 | Antipumping Contactor 4NO+4NC, 24V/110V DC, 6 Amp. Make/Type- As per existing sample. |
| 78 | Auxiliary contactor for contact multiplication 4NO+4NC, 24V/110V, DC, 6 Amp. Make/Type- As per existing sample. |
| 79 | Testing and calibration of HT VCB 11 KV complete with primary and secondary test as required including checking of wiring of all electrical measuring instrument and resetting of relay and proper alignment mechanical system for smooth functioning and tripping at any type of fault developed in feeders, complete all as specified and/or as directed by Engr-in-Charge. Note :- Contractor will submit primary and secondary test record at the time of caliberation of HT VCB, SF-6 based panel, TR control panel by current injecting kit duly signed to Engineer-in-Charge. The rate quoted by tenderer shall be deemed to include the cost of this provision incl T&P required for injecting regulated high current, HT megger and other sundry items as required in compliance with relevent IS/IEC codes, complete all as specified and/or as directed by Engr-in-Charge. |
| 80 | S&F in replacement of vaccum interrupter bottle for vaccum circuit breaker of 1600 Amps in HT panel 11000 volts grade, complete all as specified and/or as directed by Engr-in-Charge. Make/Type- As per existing sample. |
| 81 | All as per Srl item No 6.00 above but upto 1250 Amps capacity. |
| 82 | S&F in replacement of indicators flush mounted, high intensity, clustered LED type, insulated from 30/220 V, DC/AC supply with appropriate coloured code (Red, Green, Blue, Amber, White), complete all as specified and/or as directed by Engr-in-Charge. |
| 83 | S&F in replacement of MCB single pole 6 to 32 Amps of 10 KA in existing panel with incoming and outgoing connection, complete all as specified and/or as directed by Engr-in-Charge.Make : Legrand/L&T/Siemens or equivalent as approved by GE. |
| 84 | S&F in replacement of Bus Support insulators, non hygroscopic, track-resistant, high strength epoxy insulators, complete all as specified and/or as directed by Engr-in-Charge. |
| 85 | S&F in replacement of lugs, tinned copper, pre-insulated fork and pin type as applicable, complete all as specified and/or as directed by Engr-in-Charge. |
| 86 | Supply, installation, testing and commissioning in replacement of 11KV Current Transformer with Indoor & Resin cast type single pole (Three core type) CTR-600-300/5+5A, STR - 26.3KA/3Sec, insulation level 28KV/75KVP, duty cycle: 0.03 Sec,-CO-3 Min,-CO fixing on existing 11 KV panel including necessary connections, any modification required, addition/alteration required for fixing CT in existing 11 KV panel, complete all as specified and/or as directed by Engr-in-Charge.Make / type - as per existing sample, complete all as specified and/or as directed by Engr-in-Charge. |
| 87 | S&F in replacement of UNSV defective protective relays with Digital protective Relay - 3 OC + 1 Earth fault 3 phase over current and earth fault (2 NO + 2 NC output contact) with high set, CT rating 5A, field selectable 20-110V, including addition/alteration including testing, calibration of relays and replaced control wring as required at site. Make/ type : as per existing sample. |
| 88 | M&L for wiring from battery charger to all 11 KV VCB with 2.5 sqmm, 1100 volt grade multi strand flexible copper conductors and shall be properly bunched, tied, ferruled for proper indication and crimped with adequate size/types of lugs after wiring testing, complete all as specified and/or as directed by Engr-in-Charge. |
| 89 | S&F PVC insulated and PVC sheathed cable galvanised steel stip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 2.5 Sqmm 12 core 1100 volt grade incl taking out old cable of any size and type, complete all as specified and/or as directed by Engr-in-Charge. |
| 90 | All as per Srl item No 15.00 above but 2.5 Sqmm 6 core 1100 volts grade. |
| 91 | All as per Srl item No 15.00 above but 2.5 Sqmm 4 core 1100 volts grade. |
| 92 | All as per Srl item No 15.00 above but 2.5 Sqmm 2 core 1100 volts grade. |
| 93 | Disconnection of Transformer 66/11 KV of capacity 6.3 MVA from HV and LV side carefully after taking proper safety measures and loading the same with proper T&P into vehicles with proper T&P and vehicles, complete all as specified and/or as directed by Engr-in-Charge. |
| 94 | Transportation of Transformer 66/11 KV from MES 66 KV Yard to civil workshop for repair with suitable Truck/Trailer, complete all as specified and/or as directed by Engr-in-Charge. |
| 95 | Loading of Transformer 66/11 KV from civil workshop after repair with suitable T&P, complete all as specified and/or as directed by Engr-in-Charge. |
| 96 | Transportation of Transformer 66/11 KV civil workshop to MES 66 KV Yard Leh after repair with suitable Truck/Trailer, complete all as specified and/or as directed by Engr-in-Charge. |
| 97 | M&L for opening the top cover of transformer and carrying out the following work/repairs by speacialist Technician/ Engineer at factory work shop :- (a) Removing of transformer oil from transformer into seperate container & filling the new transformer oil. (b) Taking out the core/coil of transformer (c) Cleaning the transformer inside properly by used transformer oil as per manufacturer's guidelines and painting with one coat of zink painting as per manufacturer's norms. (d) Ovening in vapour phase drying oven at factory workshop for 72 hrs. (e) Re-tanking and assembly of core coil (f) Replacement of bushing, spindle, oil level indicator, winding temp gauge, oil temp gauge, drain valve of transformer. (g) Refixing of the transformer top cover with, gasket, nuts, bolts and washers. (h) Repair of radiator & replacement of defective plate of core as per existing size. Note : Cost of material and testing will be measured and paid seperately in respective items here in after. |
| 98 | M&L for re-winding of HV leg copper coil wire with new tripple paper cover (TPC) as per specification of copper conductor for transformer 66/11 KV of capacity 6.3 MVA & matching with existing gauge and same number of turns including best quality insulation, varnishing by vaccum impregnation and baking of coil assembly to achieve designed voltage ratio as per manufacturer's instruction, complete all as specified and/or as directed by Engr-in-Charge. |
| 99 | M&L for re-winding of LV leg copper coil wire with new tripple paper cover (TPC) as per specification of copper conductor for transformer 66/11 KV of capacity 6.3 MVA & matching with existing gauge and same number of turns including best quality insulation, varnishing by vaccum impregnation and baking of coil assembly to achieve designed voltage ratio as per manufacturer's instruction, complete all as specified and/or as directed by Engr-in-Charge. |
| 100 | M&L for replacement of 66 KV class of insulating material for HV and LV side of 66 KV Transformer, complete all as specified and/or as directed by Engr-in-Charge. |
| 101 | De-tanking and Re-tanking of Transformer 66/11 KV transformer of capacity 6.3 MVA, complete all as specified and/or as directed by Engr-in-Charge. |
| 102 | M&L for OLTC servicing of 66 KV/11 KV Transformer with replacement of minor parts such as gaskets nut bolt etc., complete all as specified and/or as directed by Engr-in-Charge. |
| 103 | M&L for replacement of Gaskets complete for Top cover, HV and LV bushings and Radiators vents etc., complete all as specified and/or as directed by Engr-in-Charge. |
| 104 | M&L for replacement of Breather complete with Silica Gel suitable for 66/11 KV transformer, complete all as specified and/or as directed by Engr-in-Charge. |
| 105 | Ovening of winding 66/11 KV transformer of capacity 6.3 MVA, complete all as specified and/or as directed by Engr-in-Charge. |
| 106 | Testing of capacitance and Tan Delta test, Narrow Band Dielectric frequency response winding test, Capacitance and Tan Delta & Narrow Band Dielectric frequency response Bushing (1--505 Hz) and Polarization Index (PI) of Transformer 6.3 MVA, complete all as specified and/or as directed by Engr-in-Charge. |
| 107 | Testing of Transformer Turns Ratio test, Exitaion current test, Magnetic balance test, HV/LV winding resistance test, of Transformer 6.3 MVA capacity, complete all as specified and/or as directed by Engr-in-Charge. |
| 108 | M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 400 sqmm 3 core with working voltage 11000 volts, complete all as specified and/or as directed by Engr-in-Charge. |
| 109 | S&F in replacement of jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint kit complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 400 Sqmm, complete all as specified and/or as directed by Engr-in-Charge. |
| 110 | S&F in replacement of jointing kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint kit complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 400 Sqmm, complete all as specified and/or as directed by Engr-in-Charge. |
| 111 | S&F in replacement of lighting arrester expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 66000 V and required accessories type as per existing including taking down old unserviceable lighting arrester, complete all as specified and/or as directed by Engr-in-Charge. |
| 112 | S&F in replacement of 30V 200 AH Battery bank consisting of 2V 200 AH Batteries 15 Nos with terminal connections and mounting race including accessories, complete all as specified and/or as directed by Engr-in-Charge. |
| 113 | S&F in replacement of 30-V, 20A Flot cum booster charger Auto / manual selection with full wave rectification for 220V, 1 phase, 50Hz AC input along with inbuilt DC distribution box, complete all as specified and/or as directed by Engr-in-Charge. |
| 114 | Supply and filling SF6 Gas with 11 Kg cylinder, complete all as specified and/or as directed by Engr-in-Charge. |
| 115 | Supply and filling transformer oil (Naphthenic) as per IS 12463 (1998), dielectric strength should be upto 60 KV, breaking voltage, complete all as specified and/or as directed by Engr-in-Charge.Make : Savita/Power Oil/Trans Oil. |
| 116 | Dehydration of HV / EHV grade transformer oil minimum three cycles to achieve dielectric strength not less than 50 KV for 1 minute with 2.5mm Gap as per IS-335 -1983 for EHV grade including topping up with new transformer oil all as directed. Note :- (i) Centrifuging Machine with all T&P and testing machine of oil, required for dehydration shall be arranged by contractor. (ii) Oil required for topping up the transformer will be measured & paid seperately. |
| 117 | S&F in replacement of HV (66KV side) bushing with brass metal connecting rod, nut, bolt and washer suitable for transformer 6.3MVA, 66/11KV as per IS, replacement of worn out stud, complete all as specified and/or as directed by Engr-in-Charge. |
| 118 | S&F in replacement of HV (11KV Side) Bushing of transformer with Brass metal connecting rod, nut bolt and washer, suitable for 6.3MVA, 66/11KV capacity of transformer as per IS, complete all as specified and/or as directed by Engr-in-Charge. |
| 119 | Reconnection of 66/11 KV transformer of capacity 6.3 MVA complete with all LV and HV connection including all control cables to the transformer i.e. WTI, OTI, Buchholz relay and OLTC, complete all as specified and/or as directed by Engr-in-Charge. |
| 120 | Servicing of 66 KV isolator switch after taking proper safety measures and shut down, decabonizing of all contacts with anti corrosive solution and applying petrolium jelly to all contacts and greasing to all moving mechanical parts, tightening of all connection clamps and proper adjustment of isolator, complete all as specified and/or as directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 8 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender