Tender For Provn Of Under Ground Storage Sheds With Connected Infrastructure At Sumdo And Khab
Tender Value
69.28 Crore
Estimated cost
Bid Submission
21 Dec 2026
33 days left
EMD
15 Lakhs
Bank guarantee accepted
Document Fee
3000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kinnaur → Himachal Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Under Ground Storage Sheds With Connected Infrastructure At Sumdo And Khab
BOQ
| Sl. No. | Item Description |
| 1 | SCHEDULE 'A' PART-I A (BUILDING WORK : CSP STRUCTURE ) |
| 2 | Design & developed all drawings and Construction of RCC collection chamber with size 1.5m x1.5m x 2m at Sumdo Location as per scope of work specified in Schedule 'A' Notes , including excavation in hard dense soil, returning filling & removal of surplus soil , PCC 1:4:8 type D-2 (using 40 mm graded stone aggregates) in foundation base, RCC in M-30 (Design Mix) with TMT reinforcement, necessary form work for raft footing, RCC walls, sub base, floor, plinth protection, Steel roof trust in angle, tee etc with PPGI roof sheet , including external, internal & steel surface painting etc And for structure references and other specifications should be taken from the scope of work (Schedule 'A' Notes) & DBR, complete all as per final approved drawings, specified and directed. |
| 3 | Complete Structural Design & Development, Engineering, Preparation of Complete Engineering and Construction Drawings, Vetting of Structural Design and Drawings by IIT, Supply of All Fabricated CSP Components, Construction, Erection and Installation of a Hybrid Underground, Soil-Embedded Storage Shed (Ammunition Bunker) at Upper Sumdo Location, comprising a curved-roof structural system made of Deep Corrugated Steel Plates (CSP) with a minimum plate thickness of 6.00 mm, supported on Reinforced Cement Concrete (RCC) foundations and walls, including all associated RCC structural works. The bunker shall have a minimum clear internal floor dimension of 13.30 metres (Length) × 9.30 metres (Width) × 4.20 metres (Height, from finished floor level to the crown of the curved arch roof), designed for a total storage capacity of 30 MT (3 × 10 MT) and All structural references, technical parameters, design criteria, construction requirements, material specifications and other applicable provisions shall be strictly adopted and complied with as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. The work shall be executed in its entirety in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the competent authority/Engineer-in-Charge |
| 4 | Complete Structural Design & Development, Engineering, Preparation of Complete Engineering and Construction Drawings, Vetting of Structural Design and Drawings by IIT, Supply of All Fabricated CSP Components, Construction, Erection and Installation of a Hybrid Underground, Soil-Embedded Storage Shed (Ammunition Bunker) at Lower Sumdo Location, comprising a curved-roof structural system made of Deep Corrugated Steel Plates (CSP) with a minimum plate thickness of 6.00 mm, supported on Reinforced Cement Concrete (RCC) foundations and walls, including all associated RCC structural works. The bunker shall have a minimum clear internal floor dimension of 19.30 metres (Length) × 9.30 metres (Width) × 4.20 metres (Height, from finished floor level to the crown of the curved arch roof), designed for a total storage capacity of 60 MT (3 × 20 MT) and All structural references, technical parameters, design criteria, construction requirements, material specifications and other applicable provisions shall be strictly adopted and complied with as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. The work shall be executed in its entirety in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the competent authority/Engineer-in-Charge |
| 5 | Complete Structural Design & Development, Engineering, Preparation of Complete Engineering and Construction Drawings, Vetting of Structural Design and Drawings by IIT, Supply of All Fabricated CSP Components, Construction, Erection and Installation of a Hybrid Underground, Soil-Embedded Storage Shed (Ammunition Bunker) at 04 gun Posn Sumdo Location, comprising a curved-roof structural system made of Deep Corrugated Steel Plates (CSP) with a minimum plate thickness of 6.00 mm, supported on Reinforced Cement Concrete (RCC) foundations and walls, including all associated RCC structural works. The bunker shall have a minimum clear internal floor dimension of 19.30 metres (Length) × 9.30 metres (Width) × 4.20 metres (Height, from finished floor level to the crown of the curved arch roof), designed for a total storage capacity of 60 MT (3 × 20 MT) and All structural references, technical parameters, design criteria, construction requirements, material specifications and other applicable provisions shall be strictly adopted and complied with as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. The work shall be executed in its entirety in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the competent authority/Engineer-in-Charge |
| 6 | Complete Structural Design & Development, Engineering, Preparation of Complete Engineering and Construction Drawings, Vetting of Structural Design and Drawings by IIT, Supply of All Fabricated CSP Components, Construction, Erection and Installation of a Hybrid Underground, Soil-Embedded Storage Shed (Ammunition Bunker) at Upper Khab Location, comprising a curved-roof structural system made of Deep Corrugated Steel Plates (CSP) with a minimum plate thickness of 6.00 mm, supported on Reinforced Cement Concrete (RCC) foundations and walls, including all associated RCC structural works. The bunker shall have a minimum clear internal floor dimension of 13.30 metres (Length) × 9.30 metres (Width) × 4.20 metres (Height, from finished floor level to the crown of the curved arch roof), designed for a total storage capacity of 30 MT (3 × 10 MT) and All structural references, technical parameters, design criteria, construction requirements, material specifications and other applicable provisions shall be strictly adopted and complied with as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. The work shall be executed in its entirety in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the competent authority/Engineer-in-Charge |
| 7 | Complete Structural Design & Development, Engineering, Preparation of Complete Engineering and Construction Drawings, Vetting of Structural Design and Drawings by IIT, Supply of All Fabricated CSP Components, Construction, Erection and Installation of a Hybrid Underground, Soil-Embedded Storage Shed (Ammunition Bunker) at Lower Khab Location, comprising a curved-roof structural system made of Deep Corrugated Steel Plates (CSP) with a minimum plate thickness of 6.00 mm, supported on Reinforced Cement Concrete (RCC) foundations and walls, including all associated RCC structural works. The bunker shall have a minimum clear internal floor dimension of 19.30 metres (Length) × 9.30 metres (Width) × 4.20 metres (Height, from finished floor level to the crown of the curved arch roof), designed for a total storage capacity of 60 MT (3 × 20 MT) and All structural references, technical parameters, design criteria, construction requirements, material specifications and other applicable provisions shall be strictly adopted and complied with as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. The work shall be executed in its entirety in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the competent authority/Engineer-in-Charge |
| 8 | NOTES: APPLICABLE TO SERIAL ITEM Nos. 02 TO 07: The rates quoted against Serial Item Nos. 02 to 07 shall be deemed to be inclusive of all materials, labour, plant, machinery, equipment, transportation, fabrication, installation, testing, commissioning and all incidental and ancillary works necessary for the complete execution of the respective items. The detailed scope, technical requirements and specifications shall be as stipulated in the Scope of Work (Notes to Schedule 'A'), Design Basis Report (DBR) and the attached Indicative Layout Plan. and The entire work shall be executed strictly in accordance with the final IIT-vetted and approved structural design, final approved drawings, technical specifications and instructions issued by the Competent Authority/Engineer-in-Charge. No extra payment or separate claim shall be admissible for any component, material or activity forming part of the stipulated scope of these items.The scope of work shall include, but not be limited to, the following:(i) Foundations: Providing and constructing in-situ RCC foundations using design-mix concrete, including the required sub-base, reinforcement, formwork and associated works, complete as per the approved structural design and DBR. |
| 9 | (ii) Earthwork: Excavation in hard and dense soil, returning, filling, compaction and disposal of surplus excavated soil for the construction of the soil-embedded underground storage shed (Ammunition Bunker) with CSP curved-roof structure. The excavation shall commence from the lowest ground level as finalized by the GE at site and shall be carried out to the lines, levels, dimensions and profiles stipulated in the final approved drawings.(iii) Superstructure: Construction of the RCC superstructure, including front head wall, rear closure/retaining wall, side RCC walls, necessary structural supports and arrangements for fixing and anchoring the CSP curved-roof structure. RCC partition walls shall also be provided for segregation of the storage compartments. The finished floor level (FFL) shall be maintained at a minimum height of 450 mm above the adjoining road level, or as specified in the final approved drawings.(iv) CSP Curved-Roof Structure: Providing, supplying, fabricating and installing Deep Corrugated Steel Plates (CSP) of minimum 6.00 mm thickness for the curved-roof structure, including all associated structural steel components such as crown members, trusses, purlins, cleats, connection plates, base plates, anchor bolts, fasteners, welding and other accessories, complete as per the final approved structural design and DBR. |
| 10 | (v) Waterproofing: Providing complete waterproofing treatment to all RCC structures and the CSP curved-roof structure, including suitable protective coatings, membranes, joint treatments and associated accessories, as specified in the approved design and technical specifications. The waterproofing system shall carry a minimum warranty/guarantee period of 10 years.(vi) Internal Electrification: Providing complete flame-resistant internal electrical installations, including suitable wiring, cables, conduits, fittings, fixtures, switches, distribution boards, protective devices and all necessary electrical accessories, complete as per the approved electrical design and applicable standards.(vii) Heavy-Duty Door: Providing and installing heavy-duty, blast-resistant mild steel doors, including frames, hinges, locking arrangements, fixtures, fittings and all associated accessories, as per the final approved design and specifications. |
| 11 | (viii) Painting and Protective Coating: Providing fire-resistant/protective painting and coating systems to the specified surfaces of the RCC and structural steel/CSP components, including surface preparation, primer and finishing coats, complete as per the approved specifications.(ix) RCC Flooring: Providing and constructing RCC flooring, including the required sub-base, reinforcement, concrete, finishing and associated works, complete as specified in the DBR and final approved drawings.(x) HVAC System: Design, supply, installation, testing and commissioning of a complete HVAC system, including all required infrastructure, equipment, machinery, accessories, ducting, fittings, controls, electrical connections and DG set with associated accessories, as required for the intended storage facility and in accordance with the approved design. |
| 12 | (xi) Access Ramp: Providing and constructing the required access ramp, including earthwork, sub-base, RCC works, reinforcement, finishing and associated drainage arrangements, complete as specified in the DBR and final approved drawings.(xii) Protective Shell: Providing and constructing the specified protective shell layers over the CSP curved-roof structure, including all required materials, placement, compaction and associated protective works, in accordance with the approved structural design, DBR and final approved drawings.(xiii) Earth Covering, Embankment and Drainage: Providing the specified granular/soil filling and embankment above the CSP curved-roof arch crown, with a minimum cover height of 1.80 metres and a maximum height of 5.00 metres, as established by the final approved structural design. The scope shall also include earth filling and proper compaction in all excavated areas, peripheral gaps and voids surrounding the CSP curved-roof storage structure, together with suitable surface and subsurface drainage arrangements to prevent water accumulation and ensure effective disposal of collected water, complete as per the final approved drawings and specifications. |
| 13 | Design & developed all drawings and Construction of Switch Room with toilet facility as per scope of work specified in Schedule 'A' Notes, with plinth area 19.00 Sqm , minimum total height 3.20 M above plinth level, minimum plinth height 45 cm including excavation in hard dense soil, returning filling & removal of surplus soil , PCC 1:4:8 type D-2 (using 40 mm graded stone aggregates) in foundation base, RCC in M-30 (Design Mix) , TMT reinforcement, necessary form work for footing, columan, plinth beam, lintel, roof beam & roof slab, sub base, floor, plinth protection, PCC block masonry walls, including internal electrification, external/ internal/ steel surface painting, ATT, roof treatment etc And for structure references and other specifications should be taken from the scope of work (Schedule 'A' Notes) & DBR, complete all as per final approved drawings, specified and directedNote : (i) Sumdo Location = 02 (ii) Khab Location = 01 |
| 14 | SCHEDULE 'A' PART-I B (BUILDING WORK CONVENTIONAL) |
| 15 | Construction of Sentry post (RCC Framed Structure) with permanent specifications etc complete all as shown on drawings, specified and directed.Note : Sumdo Location = 03 Khab Location = 01 |
| 16 | Construction of 01 x 225000 Ltr capacity under ground circular RCC static water tank complete all as shown on drawings and specified and directed.Note : Sumdo Location = 04 Khab Location = 02 |
| 17 | Total amount of SCHEDULE 'A' PART - II(INTERNAL WATER SUPPLY) (For details see Sch 'A' in PDF folder) |
| 18 | Total amount of SCHEDULE 'A' PART - III A(LIGHTENING PROTECTION) (For details see Sch 'A' in PDF folder) |
| 19 | Total amount of SCHEDULE 'A' PART - III B(LIGHTENING PROTECTION) |
| 20 | M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mm x 600 mm x 6 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to be packed thickness of 15 cm all round the plate using 32 X 6 mm thick galvanised iron earth strip as earth lead moulded and rivetted to earth plate at one end all as shown in electrical plate No. 3 of SSR -I 2009, and connected to main equipment at switch/control board at another end as specified and including necessary excavation, earthwotk, PCC work as provision of PCC 1:2:4 type B1 (using 20 mm graded stone agg) as in pits chamber and Cast iron earth pit cover with watering pipe 20mm dia galvanised iron pipe medium grade, funnel with wire mesh and lugs, and 40mm dia galvanised iron pipe medium grade for protection of earth strip, including testing etc complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
| 21 | M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mm x 600 mm x 6 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to be packed thickness of 15 cm all round the plate using 32 X 6 mm thick galvanised iron earth strip as earth lead moulded and rivetted to earth plate at one end all as shown in electrical plate No. 3 of SSR -I 2009, and connected to main equipment at switch/control board at another end as specified and including necessary excavation, earthwotk, PCC work as provision of PCC 1:2:4 type B1 (using 20 mm graded stone agg) as in pits chamber and Cast iron earth pit cover with watering pipe 20mm dia galvanised iron pipe medium grade, funnel with wire mesh and lugs, and 40mm dia galvanised iron pipe medium grade for protection of earth strip, including testing etc complete all as specified and directed by Engr-in-Charge. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 16, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 33 daysDec 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 40 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender