Tender For Special Repair/Replacement Of 11 Kv Transformers And Ht Ocbs Against Ber At installation Angre And installation Trata Under Hq Mna And Special Repair/Upgradation Of 750 Kva Transformer To 1000 Kva Capacity Against Ber At installation Vajra
Tender Overview
Project Description
Tender for Special Repair/Replacement Of 11 Kv Transformers And Ht Ocbs Against Ber At installation Angre And installation Trata Under Hq Mna And Special Repair/Upgradation Of 750 Kva Transformer To 1000 Kva Capacity Against Ber At installation Vajrabahu (A-14 Building), Naval Dockyard, Mumbai.
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: COMMANDER WORKS ENGINEER (NAVAL WORKS) MUMBAI Name of Work : SPECIAL REPAIR/REPLACEMENT OF 11 KV TRANSFORMERS AND HT OCBs AGAINST BER AT INS ANGRE AND INS TRATA UNDER HQ MNA AND SPECIAL REPAIR/UPGRADATION OF 750 KVA TRANSFORMER TO 1000 KVA CAPACITY AGAINST BER AT INS VAJRABAHU (A-14 BUILDING), NAVAL DOCKYARD, MUMBAI. Contract No: 8571/CWE (NW) MUMBAI/E8 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Item Code / Make Quantity Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT In Words |
| 2 | M&L for dismantling the existing transformer of any capacity from the existing location by disconnecting electrical connections carefully and depositing it in the MES store yard, including cutting of walls, removal of shutters and making good the affected portions compelte all as specified and directed. Note: The quoted rates shall be deemed to include the cost of cutting the wall, removing the shutter for taking out the transformer, providing all necessary tools and plants (T&P), and making good the affected portions to match the existing condition. |
| 3 | Supply, installation, testing and commissioning of indoor type, three-phase, 50 Hz, 500 KVA capacity, 11 KV/415 V, core-type, copper-wound, oil-immersed, naturally cooled (ONAN) step-down transformer with external cooling tubes, HV winding delta-connected and LV winding star-connected with Dyn11 vector group and neutral brought out separately on LV side. The transformer shall be provided with HV off-circuit, hand-operated tap changer having tapping positions of +5%, +2.5%, 0%, -2.5% and -5%. The transformer shall conform to IS 2026 and IS 1180 (Part 1):2014 including latest amendment No 4 dt March 2021 to IS code 1180, with Energy Efficiency Level-3 losses, as applicable.The transformer shall be complete with the following accessories:(a) Three numbers 11 KV porcelain bushings on HV side with copper rods, connectors, nuts, bolts and washers, including three numbers suitable ACSR conductors for connection from GOAB switch to transformer.(b) LV cable box with three numbers porcelain bushings, copper rods, connectors and one cable gland suitable for 3.5-core, 300 sq.mm, 1100 V grade XLPE armoured cable, including termination accessories.(c) Oil conservator with oil level gauge and filter-type drain valve. |
| 4 | (d) Dehydrating breather with initial filling of silica gel.(e) Explosion vent/pressure relief device, thermometer pocket, oil drain valve, lifting lugs, oil filling arrangement, air release valve and four numbers detachable solid cast-steel rollers.(f) One number 100 mm diameter dial-type thermometer with 0–120°C range, maximum temperature indicator and resetting arrangement.(g) Two numbers earthing terminals on transformer tank suitable for connecting 50 mm × 6 mm GI earth strips.(h) Rating plate and terminal marking plate.(j) Additional neutral bushing in LV cable box for independent neutral earthing.The transformer shall be supplied complete with insulating oil, all necessary fittings, accessories and hardware, installed, tested and commissioned at site, complete in all respects, as specified and directed by the Engineer-in-Charge. |
| 5 | Notes for Item No. 1.01:(i) A suitable platform for mounting the transformer shall be provided as per the OEM's recommendations, and the cost thereof shall be deemed to be included in the quoted rates.(ii) The General Arrangement (GA) drawing of the transformer shall be submitted by the contractor and got approved from GE before commencement of manufacturing.(iii) Pre-dispatch factory inspection of the transformer shall be carried out by the representative of Accepting officer at the OEM's premises before dispatch.(iv)The cost of providing trained manpower, materials, testing equipment, relay setting arrangements and all other necessary resources required for the inspection and testing shall be deemed to be included in the quoted rates. |
| 6 | M&L for carefully disconnecting the electrical connections and dismantling the BER HT OCB, including incoming and outgoing connections, from its existing location and depositing the same at MES store yard, complete as specified and directed by the Engineer-in-Charge.Note: The quoted rates shall be deemed to include the cost of cutting the wall, removing the shutter for taking out the OCB, providing all necessary tools and plants (T&P), and making good the affected portions to match the existing condition, complete in all respects. |
| 7 | Supply, installation, testing and commissioning of indoor type, metal-clad, floor-mounted, draw-out type Vacuum Circuit Breaker (VCB) panel, ICOG (Incoming-cum-Outgoing) single-panel arrangement, rated 6.6/11 KV, 400 A, 3-phase, 3-wire, 50 Hz, with fault level of 250 MVA at 11 KV and short-time withstand/breaking capacity of 25 KA for 1 second. The panel shall be totally enclosed, single-busbar type, horizontal/vertical isolation type, front-operated and extensible, complete with CTs, PTs, three vacuum interrupters, epoxy support insulators, self-aligning finger-type isolating contacts, integral racking mechanism, mechanical and electrical interlocks, automatic safety shutters, padlocking arrangement and isolation plugs. The VCB shall have manually and electrically motor-charged independent closing/tripping springs, trip-free operating mechanism, closing and tripping push buttons, mechanical ON/OFF indication and necessary interlocks for insertion and withdrawal. Separate earth protection shall be provided for circuit breaker, busbar and cable compartments. The panel shall conform to IEC 62271-100 and IEC 62271-200, complete with all standard fittings, accessories, protection and control arrangements required for incoming and outgoing operations, as specified and directed by the Engineer-in-Charge.Location: INS Trata. |
| 8 | Notes:(i) The General Arrangement (GA) drawing of the HT panel shall be submitted by the contractor and got approved from GE before commencement of manufacturing.(ii) Factory inspection of VCB panels shall be carried out by the representative of Accepting Officer at the OEM's premises before dispatch.(iii)The cost of providing trained manpower, materials, testing equipment, relay setting, calibration and all other necessary arrangements required for inspection and testing shall be deemed to be included in the quoted rates. |
| 9 | Supplying, laying, testing and commissioning in repairs XLPE insulated, screened, PVC bedded, galvanised steel strip/wire armoured heavy duty electric power cable, 1100 volts grade, with stranded aluminium conductor of size 185 sq.mm, 3 core, laid in trenches/along wall/floor including all necessary materials, saddles, clamps and fixing arrangements, complete all as specified and as directed by Engineer-in-Charge. |
| 10 | Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed. |
| 11 | Supply , fixing, testing in repairs of JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 25 mm dia with 250 micron ( averaSchneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill comound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof incl all as specified .Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole. |
| 12 | Supply, installation, testing and commissioning of indoor type, three-phase, 50 Hz, 1000 KVA capacity, 11 KV/415 V, core-type, copper-wound, oil-immersed, naturally cooled (ONAN) step-down transformer with external cooling tubes, HV winding delta-connected and LV winding star-connected with Dyn11 vector group and neutral brought out separately on LV side. The transformer shall be provided with HV off-circuit, hand-operated tap changer having tapping positions of +5%, +2.5%, 0%, -2.5% and -5%. The transformer shall conform to IS 2026 and IS 1180 (Part 1):2014, including latest amendment No 4 dt 2021 to IS code, with Energy Efficiency Level-3 losses, as applicable. The transformer shall be suitable for continuous operation at an ambient temperature of 40°C, with temperature rise and other performance parameters conforming to applicable standards.The transformer shall be complete with the following accessories:(a) Three numbers of 11 KV porcelain bushings on HV side with copper rods, connectors, nuts, bolts and washers, including three numbers of suitable ACSR conductors for connection from GOAB switch to transformer.(b) One LV cable box comprising three numbers of porcelain bushings with copper rods, connectors, nuts, bolts and washers, and one cable gland suitable for 3.5-core, 300 sq.mm, 1100 V grade XLPE-insulated, heavy-duty armoured cable, including termination accessories. |
| 13 | (c) Oil conservator with oil level gauge and filter-type drain valve.(d) Dehydrating breather with initial filling of silica gel.(e) Explosion vent/pressure relief device, thermometer pocket, oil drain-cum-filter valve, lifting lugs, oil filling arrangement with cap/plug, connection plate, air release valve and four numbers of detachable solid cast-steel rollers.(f) One number 100 mm diameter, dial-type, vapour-pressure thermometer having a range of 0–120°C, with metal protective guard, maximum temperature indicator and resetting arrangement.(g) Two numbers of earthing terminals on transformer tank suitable for connecting 50 mm × 6 mm GI earth strips for body earthing.(h) Rating plate and terminal marking plate.(i) One additional neutral bushing in the LV cable box for independent neutral earthing.The transformer shall be supplied complete with insulating oil, all necessary fittings, accessories and hardware, installed, tested and commissioned at site, complete in all respects, as specified and directed by the Engineer-in-Charge.Note : Back-fill compund shall not be mixed with any soil while pouring in the bore hole. |
| 14 | Notes:(i) A suitable platform for mounting the transformer shall be provided as per OEM recommendations, and the cost thereof shall be deemed to be included in the quoted rates.(ii) The cost of disconnecting and dismantling the existing transformer from the powerhouse, including necessary arrangements such as cutting/alteration of the shutter door and wall for removal, shifting and depositing the dismantled transformer at MES store yard, and making good the disturbed portions to match the existing condition, shall be deemed to be included in the quoted rates.(iii) The General Arrangement (GA) drawing of the transformer shall be submitted by the contractor and got approved from GE before commencement of manufacturing.(iv) Pre-dispatch factory inspection of the transformer shall be carried out by the representative of Accepting officer at the OEM's premises before dispatch.(v) The cost of providing trained manpower, materials, testing equipment, relay setting arrangements and all other necessary resources required for inspection and testing shall be deemed to be included in the quoted rates. |
| 15 | Supply, installation, testing and commissioning of 415 V, 3-phase, 4-wire, indoor type, cubicle-mounted LT panel board, dust and vermin-proof, fabricated from 2 mm thick CRCA sheet steel, with front-opening hinged doors, copper busbars rated for 2000 A, powder-coated finish, suitable internal wiring with stranded copper conductors of adequate size, CTs, foundation/supporting channels, cable termination arrangements, cable glands, hinged covers with gaskets and all necessary accessories, complete as specified and directed by the Engineer-in-Charge.The panel shall be suitable for accommodating the following switchgear, protection devices and metering instruments: |
| 16 | A. Incoming:(a) 1600 A, 4-pole, 415 V, 50 kA, manually operated draw-out type ACB with thermal-magnetic release – 01 No.B. Outgoing:(a) 630 A, 4-pole, 25 kA, thermal-magnetic MCCB – 01 No.(b) 400 A, 4-pole, 16 kA, thermal-magnetic MCCB – 02 Nos.(c) 320 A, 4-pole, 16 kA, thermal-magnetic MCCB – 06 Nos.(d) 250 A, 4-pole, 16 kA, thermal-magnetic MCCB – 09 Nos.(e) 125 A, 4-pole, 16 kA, thermal-magnetic MCCB – 03 Nos.(f) 350 A, 440 V, manually operated off-load changeover switch – 01 No.C. Metering and Indication:(a) Digital voltmeter – 01 No., (b) Digital ammeter with suitable CTs – 01 No., (c) LED-type phase indication lamps (R, Y & B) – 01 Set.The complete LT panel shall be supplied with all necessary internal connections, busbar supports, insulators, control wiring, terminals, protective devices, interconnections and hardware required for satisfactory operation, complete in all respects, as specified and directed by the Engineer-in-Charge. Total in Figures 0.0 23 INR Zero Only Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender