Tender For Rewiring & Renovation Of Electrical Installations For Divisional Office Building In Mini Godown At Fsd Varanasi Under Do Varanasi.
Tender Value
24.51 Lakhs
Estimated cost
Bid Submission
25 Nov 2026
4 days left
EMD
49040
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Varanasi → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Rewiring & Renovation Of Electrical Installations For Divisional Office Building In Mini Godown At Fsd Varanasi Under Do Varanasi.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying , installation , testing and commissioning of cubical type panel with size (1.4x1.3x0.4 Mtr) suitable for operation at 415 (+/-) 6% Volts,50Hz,3 Phase 4 Wire system made out from CRCA sheet steel 2.0 mm and covers shall be cold rolled sheet thickness not less than 1.6mm fabricated factory finished followed-42 by powder coated painting & provided with gaskit to make dust , damp and vermin proof degree of IP 67 , hinged type openable door , loaking arrangement , detachable gland plate , connection , interconnections with suitable size (400 Amp capacity) 4 strip high conductivety elctrical aluminium (ALU) busbar codifies in red,yellow,blue and black colour and PVC insulated copper conductor cable 1100Volt grade for internal wiring including providing and fixing digital type Ampere meter, Voltmeter, Indication LED lamp, Selector switch,Labeling comprise white letters on black background, cable alleys, cable gland plates in two half, etc. necessary metering protections & indications and mounted complete as required including foundation works as required with following switch gears etc:-(Confoming to relevent BIS/IS standard or equivalent) 1) MCCB 200 Amps 4 Pole 36KA with thermomagnetic release (incomer) with 1.1) 1 no. 0-500V 96 sqmm digital multifunction meter with selector switch for indicating V, A, pf, F, KW, KVA, KWH, KVAH etc. 1.2) 3 No. phase indicating lamps to show the incoming power with 2A TP MCB for protection.1.3) 2 Nos. indicating lights for incomer on/ trip position. 1.4) 1 No. Phase Reversal relay with matching cast resin CTs and alarm. 1.5) 1 no. 3 phase voltage monitoring relay cum phase sequence meter2) 2 Nos MCCB 100 Amps 4 Pole 30KA with thermomagnetic release3) 1 no MCCB 63 Amps 4 Pole 25KA with thermomagnetic release4) 4 nos. MCB DP 40 Amps 5) 4 strip AL Busbar 400Amp (1.3 Amp per Sq.mm, TPN)- 02 Sections |
| 2 | Supply of PVC insulated PVC sheathed cable of 1.1KV grade armoured Underground aluminum conductor cable as reqd confirming to IS –7098 part I with up to date amendments) of the following size |
| 3 | 3.5x50 sqmm |
| 4 | 3.5x35 sqmm |
| 5 | 4x25 sqmm |
| 6 | 4x16 sqmm |
| 7 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/HDPE pipe as required.Upto 35 sqmm. |
| 9 | Supply and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 kv grade as required. |
| 10 | 4x35 sqmm (32mm) |
| 11 | 4x25 sqmm (28 mm) |
| 12 | 4x16 sqmm (25 mm) |
| 13 | 4x10 sqmm (25 mm) |
| 14 | Supply, installation, testing and commisioning of weather proof MS loop in loop out busbar box havin 4P MCCB 63Amp and of size not less than 450x375x200 mm with 4 Nos. suitable capacity ALU (upto 150 Amp) Bus Bar (R,Y,B & N) duly finished and painting, detachable gland plate & Arrangement for interconnection etc as required. (Confoming to relevent BIS/IS standard or equivalent) |
| 15 | Supplying and laying of following size HDPE pipe(PN 6, PE 63) ISI marked along with all accessories like socket, bend, couplers etc. as per latest standard IS Code, Part II complete with fitting and cutting, jointing etc. Direct in ground (75cm below ground level) including excavation and refeling the trench but excludings and cushioning and protective covering etc.complete as required. 40 mm dia (OD=40 mm & ID=35 mm nominal) |
| 16 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 17 | 3x2.5 sqmm |
| 18 | 3x4 sqmm |
| 19 | 3x6 sqmm |
| 20 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. |
| 21 | LED Panel light 2x2 ft., (System lumen efficacy >135 lm/Watt) Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends ,CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as System lumen efficacy >135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shapesize and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management:heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). 40 watt |
| 22 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . |
| 23 | 4 way (4+12) double door. |
| 24 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 25 | 12 way , Double door |
| 26 | 16 way , Double door |
| 27 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 28 | 12 Module (200mmX150mm) |
| 29 | 8 Module (125mmX125mm) |
| 30 | 6 Module (200mmX75mm) |
| 31 | 2 Module (75mmX75mm) |
| 32 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 33 | 5/6 A switch |
| 34 | 15/16 A switch |
| 35 | 3 pin 5/6 A socket outlet |
| 36 | 6 pin 15/16 A socket outlet |
| 37 | Supply of 1200 mm sweep ceiling fan suitable for 230 V ±10%, 50 Hz single-phase AC supply, complete with energy-efficient motor (minimum 75 W or as per BEE norms), aerodynamically balanced aluminium blades, double ball bearing assembly for smooth and silent operation, minimum air delivery of 210 CMM, and rated speed of about 300–320 RPM. The fan shall be provided with powder-coated finish, rust-resistant body, thermal overload protection, and shall conform to relevant IS standards (IS: 374). The item includes supply of down-rod, shackle assembly, canopy, terminal block, and all standard accessories, complete in all respects as approved by the Engineer-in-Charge. |
| 38 | Supply of Wall Fan 400mm Sweep complete with suitable for 230 V ±10%, 50 Hz single-phase AC supply, complete with energy-efficient motor (minimum 75 W or as per BEE norms), The fan shall be provided with powder-coated finish, rust-resistant body, thermal overload protection, and shall conform to relevant IS standards (IS: 374) including accessories complete in all respects as directions by the Engineer-in-Charge. |
| 39 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 40 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 41 | Installation, Testing and Commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS/HFFR PVC insulated, copper conductor, single core cable etc. as required. |
| 42 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 43 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required. (Confoming to relevent BIS/IS standard or equivalent) |
| 44 | Supplying and fixing following rating, 240/415 volts, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 45 | Single pole 6A-32A |
| 46 | Double Pole 40A |
| 47 | Double Pole 63A |
| 48 | Triple Pole & Neutral 100A |
| 49 | Supplying and fixing of following sizes of steel conduitalong with accessories in recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 50 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 51 | 25 mm |
| 52 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required (Confoming to relevent BIS/IS standard or equivalent) |
| 53 | 50 mm dia. G.I. pipe (medium class) |
| 54 | Dismantling Cement Concrete manually/ by mechanical means including disposal of material whithin 50 metres lead as per the directions of Engineer In-charge. |
| 55 | Nominal concrete 1:3:6 or rich mix 1:4:8 or leaner (including equivalent design mix) |
| 56 | Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required. |
| 57 | Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. (upto 450 mm sweep) |
| 58 | Supply, Installation, Testing and Commissioning of wall mounted mounted electric operated heavy duty FlyKiller Machine having 2 UV tubes of 20 watt each as required. Shape & size shall be as approved by Engineer-in-Charge as per requirement (Confoming to relevent BIS/IS standard or equivalent) |
| 59 | Supplying, Installation, Testing and Commissioning of Inverter Type Air Cooled Cassette type Air conditioners completewith Indoor unit(IDU), Out door unit (ODU), R-32/R410A/R-407 Green Refrigerant, wireless Remote, inbuilt drain pump, suitable for 400/230V, 50 Hz ,1 /3 phase AC supply, including surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5.5 Mtr (IDU to ODU), copper power and control cable upto 5.5 Mtr (IDU to ODU) including drain pipe, the system shall be capable of performing cooling, dehumidification, Air circulation, filteration & ventilation of following capacity with Scroll/rotary compressor with min 5year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB) as specified.The system shall be able to deliver 100% of the rated capacity as per relevant ISCode. The lab testing reports as per IS: 1391 shall be submitted from NationalAccreditation Board for Testing and Calibration Laboratories (NABL) accredited asper International Electrotechnical Commission (IEC) 17025 standards/CentralPower Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and asper IS: 1391 as required. Inverter Type |
| 60 | 3.0 TR with 5 Star BEE Rating |
| 61 | Supply, Installation,Testing & commissioning of LED pylon signage(both side LED lightening) of 17.5 sqfts both sides fabricated out of 1\\"x1\\" MS pipe box, 3mm thick computerised router cut ACP Sheet and 3mm thick acrylic sheet pasted from back of the cut out letters, logo and complete content with LED and waterproof & dustproof power supplies for backlit purpose. Powder coated Aluminum sheet shall be fixed from the required side of the entire board to make box section, Light Source: LED modules , Lumens: 120–150 lumens per watt for standard module, Life: min. 60,000 burning hours, Power consumption - ~ 1.5 Watt per module(approx), input:230V, output: 12V DC, 1ft = ~ 3 Module, Working Temperature: -10 ℃ to 55 ℃, making it visible even in low light conditions, Waterproof LED modules, energy-efficient IP68 rated with colour temperature with IP68 grade power supply, Backlight with transparent acrylic backs etc. Frame will be held on min. 2 nos. MS angle of required length of min. 1\\"X1\\" from the ground including required suitable foundation( including required earthwork exacavation , laying PCC(1:3:6), Cement concrete(1:1.5:3) , shuttering, plastering of 6mm including filling of exacavated sand) to support pylon board with \\" Food Corporation of India, DO Varanasi,FCI Logo, address etc. written in Hindi and English language on both sides of board .Design as per the latest FCI norms to be provided by FCI and as per the direction of Engineer-in-charge . |
| 62 | Supply, Installation, Testing and Commissioning of electric operated automatic ABS Hand Dryer size 240mm x240mm x230mm suitable for 230V, 50 Hz supply with relevant safety standards and IS specifications as per the directions of Engineer In-charge |
| 63 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. As required. |
| 64 | Dismantling of over head lines comprising of copper/ABCCable/ aluminium overhead conductor, G.I. wire, cross arms, insulators etc. as required. |
| 65 | Credit item |
| 66 | Iron Scrap (dismantled iron poles, conduits, panal etc.)(L.S.) |
| 67 | Aluminium Scrap (i.e., ABC Cable etc.) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysNov 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender