Tender For Re-Electrification Work Of Government Girls Inter College Gomti Nagar Lucknow
Tender Value
14.96 Lakhs
Estimated cost
Bid Submission
30 Nov 2026
17 days left
EMD
1.50 Lakhs
Bank guarantee accepted
Document Fee
766
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Lucknow → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Re-Electrification Work Of Government Girls Inter College Gomti Nagar Lucknow
BOQ
| Sl. No. | Item Description |
| 1 | Wiring for light point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 2 | Wiring for Twin Control light point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 3 | Wiring for Fan point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 4 | Wiring for Call bell Point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 5 | Wiring for Exhaust fan with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 6 | Wiring for Plug Point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. |
| 7 | Wiring for circuit/ Submain wiring alongwith earth wire with the following sizes of KRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit as required. |
| 8 | 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 9 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 10 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 11 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 12 | 2 X16 sq. mm + 1 X 6 sq. mm earth wire |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 15 | S/F of 12 way SPN DB with additional metallic Double door without MCB Cat-A |
| 16 | S/F of 4 way TPN DB with additional metallic Double door without MCB Cat-A |
| 17 | Supply and fixing of call bell of approved make on polished MDFEG/ Teak ply board Complete all respect. |
| 18 | Installation of exhaust/fresh air fan in the existing opening including making good the damage connection testing commissioning etc as required. |
| 19 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. |
| 20 | S/F of 6 to 32 Amp SP MCB |
| 21 | S/L & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB ''C'' curve including connections, etc. as required. For A.C |
| 22 | Providing and laying G.I Strip 32mm x 6mm from earth electrode directly in ground as required. |
| 23 | S/F of Brass Compression gland & Aluminum Lugs |
| 24 | 50sqmm 3-1/2 core |
| 25 | 35sqmm 3-1/2 core |
| 26 | S/F of 16 SWG MS drum with Luvers duly painted including marking hole in the wall for fresh air/exhaust fan and finishing properly complete in all respect. |
| 27 | Supplying and fixing of following rating, DP MCB (10KA) C series MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 28 | 40 Amp DP MCB |
| 29 | 32 Amp DP MCB |
| 30 | Supplying and fixing following rating, Four pole (Three phase and neutral) 415 V, residual current circuit breaker (RCCB) having a sensitivity current 30 A in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 31 | 25 Amp 4P RCCB |
| 32 | 40 Amp 4P RCCB |
| 33 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation. B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS: 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 °C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required.1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 34 | S/F LED Bulb 9 Watt |
| 35 | Supply of Exhaust Fan/Fresh air fan 300mm Sweep 900/1400 RPM |
| 36 | Supply and Laying of Aluminum conductor PVC insulated armored served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top On surface the cable run shall be fixed on M.S clamps etc of suitable sixe or as directed by Engineer in charge complete in all respect including exaction and refilling. The armoring of the cable shall be properly connected with the earth conductor by clamps etc. |
| 37 | 50sqmm 3-1/2 core |
| 38 | 35sqmm 3-1/2 core |
| 39 | Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS: 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI ≥80, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 Im/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. |
| 40 | (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder Coated CRCA Sheet Body (Thickness > 0.50 mm) 18-22Watt |
| 41 | Supply, Installation, Testing and Commissioning of LT Panel vermin proof floor mounting, M.S channel base with bottom and Fabricated out of 2.0/11.6mm thick CRCA sheet steel, painted with powder coated paint of shade as per the direction of Engineering-Charge after proper sheet treatment process of sheet steel. The Bus Bar of panel shall be of Electrical grade High Conductive Aluminum alloy of appropriate cross section as per rating. The main bus bar shall run throughout the panel of rating as main incomer rating. The Bus Bar shall be supported by non hygroscopic SMC/DMC Bus Bar supports which shall be mounted don proper interval to ensure the bear the jerks of short Circuit of 50KA for panels having ACB as Incomer & 36KA for panels having MCCB Incomers Panel shall be constructed in fully Segregated Compartment Design for Each Feeder as per 3b construction Format. The Panel shall be complete in all respect as per IS: 8623 Part-2&3. There shall be Separate Metering Compartment for incomer metering and outgoing metering. Incoming 100Amp MCCB-1 No, Outgoing 4 32Amp MCCB 4 No. |
| 42 | LED Street light fixture, powder coated pressure die cast aluminium body (System lumen efficacy ≥135 lm/Watt).Supplying, Installation, Testing & Commissioning of Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 °C to 50 °C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%, THD < 10% as per IEC 61000-3-2, P. F.20.95, IP-66, IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. |
| 43 | System lumen efficacy ≥135 Im/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 44 | GST @ 18% Extra Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 13, 2026
11:30 IST
Tender Published
Tender notice published.
TodayNov 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysNov 30, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender