Project Description

Tender for Comprehensive Maintenance Of Externalelectric Supply (Ht And Lt) Including All Ht Equipmet At Pier 2 And Pier 5 Under Ge(Sb) Karwar

BOQ

Name of Work:- COMPREHENSIVE MAINTENANCE OF EXTERNALELECTRIC SUPPLY (HT AND LT) INCLUDING ALL HT EQUIPMET AT PIER 2 AND PIER 5 UNDER GE(SB) KARWAR
Sl. No. Item Description
1Taking down HT switch gear (Vacuum circuit breaker ) of capacity 11 KV 250/350 MVA , up to 2500 Amps comprising of following repairs, servicing, carrying out preventive maintenance and refixing the same after repairs/ servicing: - Make- Schnider
2(a) Tripping off the breaker, lowering the breaker with raising/lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing/inspection/overhauling
3(b) Servicing/Inspecting/checking of automatic safety shutter operation for serviceability and replacement of spares if required.
4(b) Servicing/Inspecting/checking of circuit spout and circuit spout connections for RYB phases and replacement of spares if required.
5(c) Dismantling and checking of cross bar assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc.
6(d) Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism.
7(e) Servicing/Inspecting/checking of secondary sockets/busbar earthing plugs/earthing sockets and replacement of spares if required.
8(f) Checking, setting and adjustment of lowering and raising operation of the breaker trolley.
9(g) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly.
10(h) The inspection of HT switch gear shall involve:-(i) Inspection of truck & hoist assembly.(ii) Inspection of assembly & components of solenoid assembly.(iii) Inspection of assembly & components of dependent mechanism.(iv) Inspection of assembly & components of spring box mechanism.(v) Inspection of motor mechanism spring charge assembly (vi) Inspection of assembly of trip unit & related components, Make: Schnider VCB Indoor type
11Notes: (i) The contractor shall carryout the comprehensive maintenance of the HT VCB panels catered under subject work through the Original Equipment Manufacturer of that HT VCB panels or from their accredited / authorised agencies only. The spares shall be of the make as per existing or as per the OEM.(ii)Monthly schedule for proper maintenance of HT VCB panels and necessary documentation including all spare parts required to be replaced during the period shall be as per particular specification and as per maintenance manual provided by OEM.(iii)The parts shall be genuine and from Original Equipment Manufacturer (OEM) and approved by GE & all minor spare parts and parts recommended by the OEM required for repair / replacement for maintenance of HT VCB panels to be replaced during maintenance at no extra payment as per particular specification(iv) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, compound, to put in to the VCBs and panels in serviceable condition, testing and commissioning all as specified and as directed by the Engineer-in-Charge.v) Major spares like Breaker bushings, vacuum interrupter, busbar spout, busbar spout connections, circuit spout/circuit spout connections/buffer fixed contacts, moving contacts, solenoid spares, dependent/spring mechanism/ motor mechanism, trip unit etc will be measured and paid separately under relevant items of Schedule 'A'. However the rate quoted shall be deemed to include for any other minor spares require replacement.
12Supply only the following spares suitable for 11 KV 250/350 MVA , up to 630 Amps HT switch gear VCBs and 11 KV HT panel repair work under relevant Schedule - Make- Schneider
13(a) Torsion spring suitable for 11KV VCB
14(b) Motor cut off switch suitable for 11KV VCB
15(c) Charging motor suitable for 11KV VCB
16(d) LED Indication Lamps
17(e) Shunt trip coil 110 V DC/220 V DC
18(f) Shunt trip coil 110 V DC/220 V DC with assembly
19(g) Breaker control switch
20(h) Busbar Spout
21(j) Circuit spout
22(k) Control circuit fuses 2 A to 63 A
23(l) HRC fuse (PT HT side)
24(m) PT plug contact
25(o) VCB buffers
26(p) 110 Volt DC closing coil assembly
27(q) Push to trip knob red assembly
28(r) Push to trip knob green assembly
29(s) Ratchet wheel
30(t) Nylon release lever
31(u) VCB charging powl
32(v) Shutters for racking shaft
33(w) Bus bar support insulator for VCB panel
34(x) Vacuum interrupter
35(y) Monoblock for busbar spout/circuit spout
36(z) Spring drum suitable for 11KV VCB
37(aa) Spring suitable for 11KV VCB
38(ab) Roller chain suitable for 11KV VCB
39Material and labour for Strip Opening the busbar of the 10 Nos HT 11 KV VCB panels section for decarbonising of busbar and connected items/removing the old teared/ unsv insulation from the bus bar, checking the IR value before fixing the HT sleeve and refixing the heat shrinkable insulating tape and sleeve suitable for 11 kv busbar not less than 3mm thick having dielectric strength not less than 15kv/mm and HT insulation tape for CT/ PT connection complete and checking the IR value before testing and commissioning the bus bar all as specified . Note :- Test sheet of IR value shall be submitted by the contractor, no cost extra shall be paid by the department and all testing requirement shall be arrange by the contractor including transportation and T&P.
40Supply and fix in replacement & testing and commissioning of CTs epoxy cast wound primary with minimum primary current 50 to 630 A, single/ double ratio, double core (Protection core-5P10 & Metering core- Class 1.0), 25 KA for 1 sec of 15 VA minimum Burden including necessary fixing arrangement to match with the existing system complete all as directed Make - as per OEM HT panel manufacturers..
41Supply & Fixing in replacement & testing and commissioning of potential transformer PT ratio 11000/110 Volts accuracy class 0.5, 50VA , indoor type , epoxy resin cast, strut type single stage suitable for power measurement, connecting to HT/VCB to match with the existing system complete all as directed Make - as per OEM HT panel manufacturers.
42Supply & laying 1.5 sqmm flexible PVC stranded copper conductor cable, unsheathed, 1100 V grade for control wiring.
43Supply & laying 2.5 sqmm flexible PVC stranded copper conductor cable, unsheathed, 1100 V grade for control wiring.
44S& Fixing in replacement multifunction meter, Digital type (Displaying A, V, PF, Hz, KVA, KW, KVAR, KWh, KVARh etc.) Class 1/0.5 with RS485 port for communication in Modbus protocol.
45S& Fixing in replacement of space heater with thermostat and new connected separate control with wiring
46Disconnect and taking out the IDMT/ Numerical/ Microprocessor based relay of (Micom-P127 3 Phase + EF, Master tripping Relay & Transformer protection relay) over current IDMT with instant trip, Separate curve selection for phase and EF from Latching of fault current up to last 5 faults with time stamping. Inbuilt Trip circuit supervision function (TCS).Inbuilt Breaker Failure function (50BF).Programmable Annunciation contacts. Site selectable CT secondary i.e. 1A/5ASelf Supervision of relay. Metering function. Fully communicable with IEC standard open protocol IEC60870-5-103.Aux.V-24-240AC/DC11 KV HT panel, cleaning the contacts, calibrating the relay by conducting secondary injection tests, checking of current transformer, rectification of defects in control wiring for proper tripping of circuit breakers through CTs and relay and tripping coils, adjustment/setting to plug and time multiplier settings of the relay to achieve the discrimination in tripping, tune/synchronies upstream breaker relay settings, re-installation of relay, & commissioning etc complete all as specified and as directed.Make- Schneider Please Enable Macros to View BoQ information
47Disconnect and taking out the IDMT/ Numerical/ Microprocessor based relay of (Micom-P127 3 Phase + EF, Master tripping Relay & Transformer protection relay) over current IDMT with instant trip, Separate curve selection for phase and EF from Latching of fault current up to last 5 faults with time stamping. Inbuilt Trip circuit supervision function (TCS).Inbuilt Breaker Failure function (50BF).Programmable Annunciation contacts. Site selectable CT secondary i.e. 1A/5ASelf Supervision of relay. Metering function. Fully communicable with IEC standard open protocol IEC60870-5-103.Aux.V-24-240AC/DC11 KV HT panel, cleaning the contacts, calibrating the relay by conducting secondary injection tests, checking of current transformer, rectification of defects in control wiring for proper tripping of circuit breakers through CTs and relay and tripping coils, adjustment/setting to plug and time multiplier settings of the relay to achieve the discrimination in tripping, tune/synchronies upstream breaker relay settings, re-installation of relay, & commissioning etc complete all as specified and as directed.Make- Schneider Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58518445
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 1.24 Crore
LAST DATE 12-12-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Comprehensive Maintenance Of Externalelectric Supply (Ht And Lt) Including All Ht Equipmet At Pier 2 And Pier 5 Under Ge(Sb) Karwar
Basic Detail
Tender No 86167
Bidding Type Tender
Location
City Uttara Kannada
State Karnataka
Key Dates
Publish Date 13 Nov 2026
Submission Date 12 Dec 2026
Open Date 14 Dec 2026
Finance
Tender Value 1.24 Crore
Tender Fee 1000
EMD 1.99 Lakhs
Exemption Available
Document List
4f6f424c-9152-4480-847f-c56197ff81ef.html
86167Tender.pdf
BOQ_895766.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 13, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 12, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 20 days
Dec 14, 2026

Bid Opening Date

Technical bids will be opened and evaluated.