Tender for Tender for Tender For Chitaipur Zone Sewerage Scheme Of Nagar Nigam Varanasi, Distt-Varanasi
Tender Value
606.79 Crore
Estimated cost
Bid Submission
11 Dec 2026
19 days left
EMD
6.06 Crore
Bank guarantee accepted
Document Fee
23600
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Varanasi → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Tender For Chitaipur Zone Sewerage Scheme Of Nagar Nigam Varanasi, Distt-Varanasi
BOQ
| Sl. No. | Item Description |
| 1 | Civil Work |
| 2 | Sewer Network |
| 3 | Execavation |
| 4 | Excavation for following depth below G.L. for laying of sewers in ordinary soil earth, sand, loam and clay including cutting of jointing pits, trimming dressing leveling refilling of trenches in 20cm layers watering and ramming the same including removal of surplus earth or other dismantled materials up to distance 50m from the centre of trenches. |
| 5 | 0.00 - 1.50 m BGL |
| 6 | 1.51 - 3.00 m BGL |
| 7 | 3.01 - 4.50 m BGL |
| 8 | 4.51 - 6.00 m BGL |
| 9 | 6.01 - 7.50 m BGL |
| 10 | 7.51 - 9.00 m BGL |
| 11 | TIMBERING |
| 12 | Providing and fix open timbering (covering 1/3rd) of surface area by planks in trenches for the following depth below G.L. Consisting of 40 mm approved country wood planks for poling boards 125mm x 75mm Indian Sal wood walers and 100 mm dia. Sal ballies for shuttering at 1.5m c/c including removal after laying. Both sides will be taken as one side for the purpose of payment and measurements i.e. area equals to length x depth of trenches and dismantled timbering materials will be the property of the contractor. |
| 13 | 0.00 - 3.00 m BGL |
| 14 | Providing and fix close timbering in the trenches for the following depth below G.L. consisting of 40 mm approved country wood planks for poling broads 125 mm x 75 mm Indian Sal wood walers and 100 mm dia. Sal bellies for truing the shuttering at 1.5 M c/c/ including removal after laying of sewers. Both side of trenches will be taken as one side for the purpose of payment and measurement i.e. area equals to length x depth of trenches. Dismantled timbering materials will be the property of the contractor. |
| 15 | 0.00 - 3.00 m BGL |
| 16 | 3.01 - 6.00 m BGL |
| 17 | 6.01 - 9.00 m BGL |
| 18 | Same as item No. 14 but for close timbering left in trench (unused timbering) |
| 19 | 0.00 - 3.00 m BGL |
| 20 | 3.01 - 6.00 m BGL |
| 21 | 6.01 - 9.00 m BGL |
| 22 | Laying of Sewer Network |
| 23 | Supply of following sizes of RCC NP3/NP4 S&S rubber rings joints pipe & rubber ring from factory to site of work including transportations loading, unloading, stacking all taxes excise duty transit insurance etc. complete. |
| 24 | 200 mm dia pipe |
| 25 | 250 mm dia pipe |
| 26 | 300 mm dia pipe |
| 27 | 350 mm dia pipe |
| 28 | 400 mm dia pipe |
| 29 | 450 mm dia pipe |
| 30 | 500 mm dia pipe |
| 31 | 600 mm dia pipe |
| 32 | 700 mm dia pipe |
| 33 | 800 mm dia pipe |
| 34 | 200 mm dia pipe |
| 35 | 250 mm dia pipe |
| 36 | 300 mm dia pipe |
| 37 | 350 mm dia pipe |
| 38 | 400 mm dia pipe |
| 39 | 450 mm dia pipe |
| 40 | 500 mm dia pipe |
| 41 | 600 mm dia pipe |
| 42 | 700 mm dia pipe |
| 43 | 800 mm dia pipe |
| 44 | 900 mm dia pipe |
| 45 | 1000 mm dia pipe |
| 46 | 1100 mm dia pipe |
| 47 | 1200 mm dia pipe |
| 48 | 1400 mm dia pipe |
| 49 | Carting of following sizes of RCC NP3/NP4 S&S rubber rings joints pipe & rubber ring from store to site of work, lowering gasket the same into trenches and laying true to the alignment and gradient including excavation of earth below invert level of pipes cost of all jointing materials, testing etc. complete. |
| 50 | 200 mm dia pipe |
| 51 | 0.00 - 1.50 m BGL |
| 52 | 1.51 - 3.00 m BGL |
| 53 | 3.01 - 4.50 m BGL |
| 54 | 4.51 - 6.00 m BGL |
| 55 | 6.01 - 7.50 m BGL |
| 56 | 7.51 - 9.00 m BGL |
| 57 | 250 mm dia pipe |
| 58 | 0.00 - 1.50 m BGL |
| 59 | 1.51 - 3.00 m BGL |
| 60 | 3.01 - 4.50 m BGL |
| 61 | 4.51 - 6.00 m BGL |
| 62 | 6.01 - 7.50 m BGL |
| 63 | 7.51 - 9.00 m BGL |
| 64 | 300 mm dia pipe |
| 65 | 0.00 - 1.50 m BGL |
| 66 | 1.51 - 3.00 m BGL |
| 67 | 3.01 - 4.50 m BGL |
| 68 | 4.51 - 6.00 m BGL |
| 69 | 6.01 - 7.50 m BGL |
| 70 | 7.51 - 9.00 m BGL |
| 71 | 350 mm dia pipe |
| 72 | 0.00 - 1.50 m BGL |
| 73 | 1.51 - 3.00 m BGL |
| 74 | 3.01 - 4.50 m BGL |
| 75 | 4.51 - 6.00 m BGL |
| 76 | 6.01 - 7.50 m BGL |
| 77 | 7.51 - 9.00 m BGL |
| 78 | 400 mm dia pipe |
| 79 | 0.00 - 1.50 m BGL |
| 80 | 1.51 - 3.00 m BGL |
| 81 | 3.01 - 4.50 m BGL |
| 82 | 4.51 - 6.00 m BGL |
| 83 | 6.01 - 7.50 m BGL |
| 84 | 7.51 - 9.00 m BGL |
| 85 | 450 mm dia pipe |
| 86 | 0.00 - 1.50 m BGL |
| 87 | 1.51 - 3.00 m BGL |
| 88 | 3.01 - 4.50 m BGL |
| 89 | 4.51 - 6.00 m BGL |
| 90 | 6.01 - 7.50 m BGL |
| 91 | 7.51 - 9.00 m BGL |
| 92 | 500 mm dia pipe |
| 93 | 0.00 - 1.50 m BGL |
| 94 | 1.51 - 3.00 m BGL |
| 95 | 3.01 - 4.50 m BGL |
| 96 | 4.51 - 6.00 m BGL |
| 97 | 6.01 - 7.50 m BGL |
| 98 | 7.51 - 9.00 m BGL |
| 99 | 600 mm dia pipe |
| 100 | 0.00 - 1.50 m BGL |
| 101 | 1.51 - 3.00 m BGL |
| 102 | 3.01 - 4.50 m BGL |
| 103 | 4.51 - 6.00 m BGL |
| 104 | 6.01 - 7.50 m BGL |
| 105 | 7.51 - 9.00 m BGL |
| 106 | 700 mm dia pipe |
| 107 | 0.00 - 1.50 m BGL |
| 108 | 1.51 - 3.00 m BGL |
| 109 | 3.01 - 4.50 m BGL |
| 110 | 4.51 - 6.00 m BGL |
| 111 | 6.01 - 7.50 m BGL |
| 112 | 7.51 - 9.00 m BGL |
| 113 | 800 mm dia pipe |
| 114 | 0.00 - 1.50 m BGL |
| 115 | 1.51 - 3.00 m BGL |
| 116 | 3.01 - 4.50 m BGL |
| 117 | 4.51 - 6.00 m BGL |
| 118 | 6.01 - 7.50 m BGL |
| 119 | 7.51 - 9.00 m BGL |
| 120 | 900 mm dia pipe |
| 121 | 0.00 - 1.50 m BGL |
| 122 | 1.51 - 3.00 m BGL |
| 123 | 3.01 - 4.50 m BGL |
| 124 | 4.51 - 6.00 m BGL |
| 125 | 6.01 - 7.50 m BGL |
| 126 | 7.51 - 9.00 m BGL |
| 127 | 1000 mm dia pipe |
| 128 | 0.00 - 1.50 m BGL |
| 129 | 1.51 - 3.00 m BGL |
| 130 | 3.01 - 4.50 m BGL |
| 131 | 4.51 - 6.00 m BGL |
| 132 | 6.01 - 7.50 m BGL |
| 133 | 7.51 - 9.00 m BGL |
| 134 | 1100 mm dia pipe |
| 135 | 0.00 - 1.50 m BGL |
| 136 | 1.51 - 3.00 m BGL |
| 137 | 3.01 - 4.50 m BGL |
| 138 | 4.51 - 6.00 m BGL |
| 139 | 6.01 - 7.50 m BGL |
| 140 | 7.51 - 9.00 m BGL |
| 141 | 1200 mm dia pipe |
| 142 | 0.00 - 1.50 m BGL |
| 143 | 1.51 - 3.00 m BGL |
| 144 | 3.01 - 4.50 m BGL |
| 145 | 4.51 - 6.00 m BGL |
| 146 | 6.01 - 7.50 m BGL |
| 147 | 7.51 - 9.00 m BGL |
| 148 | 1400 mm dia pipe |
| 149 | 0.00 - 1.50 m BGL |
| 150 | 1.51 - 3.00 m BGL |
| 151 | 3.01 - 4.50 m BGL |
| 152 | 4.51 - 6.00 m BGL |
| 153 | 6.01 - 7.50 m BGL |
| 154 | 7.51 - 9.00 m BGL |
| 155 | Bedding |
| 156 | Cement concrete work in bedding below G.L. at specified depth with cement, coarse sand and 20 mm gauge approved stone ballast (1:2:4) including supply of all materials, labour, T&P etc. required for the proper completion of work. |
| 157 | 0.00 - 1.50 m BGL |
| 158 | 1.51 - 3.00 m BGL |
| 159 | 3.01 - 4.50 m BGL |
| 160 | 4.51 - 6.00 m BGL |
| 161 | 6.01 - 7.50 m BGL |
| 162 | 7.51 - 9.00 m BGL |
| 163 | Lean Cement concrete work in bedding below G.L. at specified depth with cement, coarse sand and 20 mm gauge approved stone ballast (1:4:8) including supply of all materials, labour, T&P etc. required for the proper completion of work. |
| 164 | 0.00 - 1.50 m BGL |
| 165 | 1.51 - 3.00 m BGL |
| 166 | 3.01 - 4.50 m BGL |
| 167 | 4.51 - 6.00 m BGL |
| 168 | 6.01 - 7.50 m BGL |
| 169 | 7.51 - 9.00 m BGL |
| 170 | Well graded crushed rock/ gravel max size 25mm including supply of all materials, labour, T&P etc. into the trenches for bedding of DWC/RCC Pipes including watering compaction, labour T&P etc. for completion of work. |
| 171 | 0.00 - 1.50 m BGL |
| 172 | 1.51 - 3.00 m BGL |
| 173 | 3.01 - 4.50 m BGL |
| 174 | 4.51 - 6.00 m BGL |
| 175 | 6.01 - 7.50 m BGL |
| 176 | 7.51 - 9.00 m BGL |
| 177 | Mild steel or iron work in plain work such as R.C.C. or R.B. work (when not included in over all rates), wrought to required shape, as necessary including bending for proper completion of work including supply of steel and wastage. |
| 178 | Construction of circular type brick masonry manhole (with Extra Heavy Duty type manhole cover) with top slab made of cement concrete 1:1.5:3 with graded granite stone aggregate (12 mm nominal size), foundation concrete 1:4:8 graded stone aggregate other than granite 40mm nominal size, wall made of brick masonry using 1st class bricks having crushing strength between 100 to 149 kg/cm² in cement mortar 1:4 inside plastering 12 mm thick 1:3 finished smooth with neat cement, pinning, outside plaster 1:4 and making channels with cement concrete 1:2:4 graded granite stone aggregate (12 mm nominal size) complete as per specifications. |
| 179 | 900mm internal dia., 1.65m deep |
| 180 | 1200mm internal dia., 2.30m deep |
| 181 | 1500mm internal dia., 4.95m deep |
| 182 | 1500mm internal dia., 9.0 m deep |
| 183 | 1800mm internal dia., 12.0 m deep |
| 184 | Same as item no 180 for Regulation of Shafts plus/minus from the above mentioned depth |
| 185 | 900mm internal dia., 1.65m deep |
| 186 | 1200mm internal dia., 2.30m deep |
| 187 | 1500mm internal dia., 4.95m deep |
| 188 | 1500mm internal dia., 9.0 m deep |
| 189 | 1800mm internal dia., 12.0 m deep |
| 190 | same as above item No 180 but form RCC pre-Cast manhole as per CPHEEO Guidelines |
| 191 | 1200mm internal dia., 2.30m deep |
| 192 | 1500mm internal dia., 4.95m deep |
| 193 | 1500mm internal dia., 9.0 m deep |
| 194 | 1800mm internal dia., 12.0 m deep |
| 195 | Same as item no 192 for Regulation of Shafts plus/minus from the above mentioned depth |
| 196 | 1200mm internal dia., 2.30m deep |
| 197 | 1500mm internal dia., 4.95m deep |
| 198 | 1500mm internal dia., 9.0 m deep |
| 199 | 1800mm internal dia., 12.0 m deep |
| 200 | Dismantling/Cutting of the following type of road for laying sewers, manholes, sewer connection chambers etc. including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 201 | Bituminous road |
| 202 | Concrete road |
| 203 | Interlocking tile road |
| 204 | B.O.E road |
| 205 | Stone Patia road |
| 206 | Permanent re-instatement of the following ty pe of road surface after laying of sewer line including supply of all materials, labour, T&P etc. required for completion of work. it also includes necessary excavation required for preparation of trench for reinstatement of road, disposal of surplus unserviceable material, watering, ramming, cleaning surface for proper completion of the work as per directions of Engineer ‐in ‐charge. |
| 207 | Bituminous road (PWD) |
| 208 | Bituminous road (Nagar Nigam) |
| 209 | C.C. Road in M25 grade |
| 210 | Interlocking Road |
| 211 | BOE Road |
| 212 | Stone Patia road |
| 213 | Supply of MS pipe (As per IS:3589 made from steel confirming to IS:2062), with anti corrosive treatment with P.U. coating and Installation of product pipe with Casing pipe by Trenchless method including preparing and setting up the plants and equipement, preparing new pipe work material, installation new pipe-work and commissioning system or making the system ready for commissioning by Trenchless operation including, all related civil and mechanical works like excavation, shoring/strutting, etc. drilling, stringing, reaming, and pulling back the new pip-work on the designed bore path alignment, proper disposal of drilling fluid, and back fill of site after completion all inclusive as per IndSTT:101:2018: Code of prectice of Trenchless Technique Suiting Indian Conditions. |
| 214 | 250 mm dia pipe, 10mm Pipe Wall Thickness |
| 215 | 300 mm dia pipe, 10mm Pipe Wall Thickness |
| 216 | 350 mm dia pipe, 10mm Pipe Wall Thickness |
| 217 | 400 mm dia pipe, 10mm Pipe Wall Thickness |
| 218 | 450 mm dia pipe, 10mm Pipe Wall Thickness |
| 219 | 500 mm dia pipe, 10mm Pipe Wall Thickness |
| 220 | 600 mm dia pipe, 10mm Pipe Wall Thickness |
| 221 | 700 mm dia pipe, 12mm Pipe Wall Thickness |
| 222 | 800 mm dia pipe, 12mm Pipe Wall Thickness |
| 223 | 900 mm dia pipe, 12mm Pipe Wall Thickness |
| 224 | 1000 mm dia pipe, 12mm Pipe Wall Thickness |
| 225 | 1100 mm dia pipe, 12mm Pipe Wall Thickness |
| 226 | 1200 mm dia pipe, 12mm Pipe Wall Thickness |
| 227 | 1400 mm dia pipe, 12mm Pipe Wall Thickness |
| 228 | Providing and erecting temporary barricading at site as per drawing/ direction of Engineer-in-Charge which includes hiring of Eucalyptus Ballies and arrangement for traffic diversion such as traffic signals during construction at site as directed by the Engineer-in-Charge. The barricading provided shall be retained in position at site continuously i/c shifting of barricading from one location to another location as many times as required during the execution of the entire work till its completion. Rate include its maintenance for damages, painting, all incidentals, labour materials, equipments and works required to execute the job. The barricading shall not be removed without prior approval of Engineer-in-Charge. (Note :- One time payment shall be made for providing barricading from start of work till completion of work i/c shifting. The barricading provided shall remain to be the property of the contractor on completion of the work). The rate is for unit length of pipe laying. |
| 229 | Disposal of Surplus Earth, dismantled material and garbage etc by mechanical transport including loading, unloading and stacking (lead upto 12 km away from the site as per instruction of Engineer-in-charge) |
| 230 | Diversion of Existing Sewer line during laying of New Sewer includding Supply of 7.1 mm thick MS pipe size 200 mm dia and as per requirement of site condition including cost of ms pipe ms bend flange nut volt rubber packing also including hiring of DG set welding machine and gas cutter all labour material etc complete10% of Total Length and re- use of pipe |
| 231 | Dewatering work during laying of pipe line and construction of manhole |
| 232 | Provision for Sand filling in trench for cuision of pipe |
| 233 | Provision for shifting and reinstatement of electric and telephone poles during excavation and laying of sewer lines. |
| 234 | Provision for shifting of electric and telephone cable, gas pipeline, existing water supply mains falling in the alignment of conveying main during excavation and the restoring utilities / services to its original condition. etc. during excavation and laying of sewer lines. |
| 235 | Sewer House Connection |
| 236 | Construction of House Connecting chambers for two connections of size 0.6 x 0.6 x 0.75m including supply of materials, labour T&P etc (also including excavation, & refiling of tranches, disposal of surplus earth and garbage up distance of 12 Km from the site etc. complete). |
| 237 | Making Domestic Sewer connection using 110mm HDPE pipe PN-6, PE-100 including supply of pipe, specials, Bedding as per CPHEE manual, labours, material, T&P etc. in true to alignment & gradient (also including dismantling & restatement of drain, excavation, making interconnection from toilet, kitchen and bathroom of House & refiling of tranches disposal of surplus earth and garbage up distance of 12 Km from the site etc. complete). |
| 238 | Laying of Sewer line from House Connecting chambers to M.H using 160mm HDPE pipe PN-6, PE-100 including supply of pipe, specials, Bedding as per CPHEE manual, labours, material T&P etc. in true to alignment & gradient (also including excavation & refiling of tranches disposal of surplus earth and garbage up distance of 12 Km from the site etc. complete). |
| 239 | Sewer Inter Connection Chamber to intercept the waste water from toilet, kitchen, and bathroom 0.30x0.30x0.45m including supply of materials, labour T&P etc (also including excavation, & refiling of tranches, disposal of surplus earth and garbage up to distance of 12 Km from the site etc. complete). |
| 240 | Rising Main |
| 241 | Execavation |
| 242 | Excavation for following depth below G.L. for laying of sewers in ordinary soil earth, sand, loam and clay including cutting of jointing pits, trimming dressing leveling refilling of trenches in 20cm layers watering and ramming the same including removal of surplus earth or other dismantled materials up to distance 50m from the centre of trenches. |
| 243 | 0.00 - 1.50 m BGL |
| 244 | Providing, Supplying, laying, jointing & field testing at site as per specifications of centrifugally cast (spun) following dia Pressure Pipes with epoxy internal coaating and externally painting for sewerage confirming to IS 8329:2000 (amended upto date) with push on type EPDM 'ISI marked' rubber gasket (including cost of rubber gasket) joining as per IS 5382 specifications. Pipes shall be out side Zinc coated with finishing layer of Bitumen and have factory internal cement mortar lining. The rates include all the cost of material, cost of specials, all local and central taxes, labour required, transportation, loading, unloading, conveyance to site and stacking including lowering, laying & jointing with DI pipes and specials, etc. complete and giving satisfactory hydraulic field testing, commissioning as per specifications etc., complete as directed by Engineer. The pipe shall be ISI marked. |
| 245 | 800mm Dia DI K-9 |
| 246 | 1000mm dia DI K-9 |
| 247 | 1100mm dia DI K-9 |
| 248 | Providing, Erecting, Testing, Commissioning, of C.I. double ball orifice type 100 mm dia Air Valve inclusive of all taxes, transportation, insurance, Confirming to IS. With Construction of 350x350x500 mm size air valve chamber as per type design including supply & fixing of 50 mm dia medium duty perforated C.I. cover. |
| 249 | Dismantling/Cutting of the following type of road for sewer house connection including shorting out and stacking serviceable materials and disposal of unserviceable materials upto distance of 50 m. |
| 250 | Bituminous road |
| 251 | Permanent re-instatement of the following ty pe of road surface after laying of sewer line including supply of all materials, labour, T&P etc. required for completion of work. it also includes necessary excavation required for preparation of trench for reinstatement of road, disposal of surplus unserviceable material, watering, ramming, cleaning surface for proper completion of the work as per directions of Engineer ‐in ‐charge. |
| 252 | Bituminous road (Nagar Nigam) |
| 253 | Disposal of Surplus Earth |
| 254 | Provision for Sand filling in trench for cuision of pipe |
| 255 | MAIN PUMPING STATION (MPS) |
| 256 | Design, Construction, Supply of all materials, Erection and Commissioning of MPS (73.0 MLD) with all the civil, LT/HT panel Room, DG set foundation, Pump House, Boundry wall, Internal Road, Gate etc. all complete including all neccessary work as neccesity. |
| 257 | LIFT STATION |
| 258 | Design, Construction, Supply of all materials, Erection and Commissioning of Lift Station-1 (38.0 MLD) with all the civil, LT/HT panel Room, DG set foundation, Pump House, Boundry wall, Internal Road, Gate etc. all complete including all neccessary work as neccesity. |
| 259 | Design, Construction, Supply of all materials, Erection and Commissioning of Lift Station-2 (59.0 MLD) with all the civil, LT/HT panel Room, DG set foundation, Pump House, Boundry wall, Internal Road, Gate etc. all complete including all neccessary work as neccesity. |
| 260 | E&M Works |
| 261 | MAIN PUMPING STATION AND THEIR APPURTENANT WORK |
| 262 | VFD starter of suitable capaity as per pump set requiremet |
| 263 | SUBMERSIBLE PUMP SET: |
| 264 | Submersible sewage non-clog pumps withJacket cooled Integreated Motor of IP 68Protection for 400±10% V AC, 3phase 50 Hz. suitable to pump raw sewage with specific gravity of 1.05 and also capable to handle solids up to 135mm size with all suitable piping and specials having following material of construction.Casing- 2%NiCIImpeller- ASTM CF8MShaft & Shaft sleeve- ASTM SS 410 including Automatic Coupling system,Guide rail system comprises of Pedestal, bracket, upper guide rail holder etc. |
| 265 | 283 LPS, 21 m Head, 980 RPM |
| 266 | CAPACITOR Panel:(APFC) |
| 267 | Provision for supply of shunt type power factor improvement capacitor Panel of suitable to boost the power factor up to 0.95. |
| 268 | MAIN PIPING & VALVES: |
| 269 | Provision for main piping and valves for 450 mm dia, and 1200 mm dia common header line |
| 270 | Motor operated Sluice Valve with actuator |
| 271 | CIDF 1200 mm ø |
| 272 | CIDF 450 mm ø or as per site requirement |
| 273 | Reflex Valve |
| 274 | CIDF 450 mm ø or as per site requirement |
| 275 | CIDF 1200mm ø |
| 276 | Piping or as per site requirement |
| 277 | DIDF Pipe dia 1200 mm |
| 278 | DIDF Pipe dia 450 mm X 3M |
| 279 | CIDF Tee 1200x450x1200 mm,DI blind flange dia 1200 mm,CIDF 90 degree bend dia 1200 mm,CIDF 90 degree bend dia 450 mm,CIDF 90 degree duckfoot bend dia 450 mm,CIDF Reducer/Enlarger 1200 mmx450 mm ,DIDF Reducer/Enlarger 300 mmx 450 mm |
| 280 | Dismentaling joints 450 mm |
| 281 | Dismentaling joints 1200 mm |
| 282 | Nut and bolts with washer(SS) M20x120,M24x120,M27x140 |
| 283 | Necessary Piping pump set foundation rubber packing, insertion and other material |
| 284 | Electromagnetic Flow Meter: |
| 285 | (i) Providing, Installation, Testing and commissioning of 1200 mm dia Chronne Marshall make ELECTRO MAGNETIC FLOW METER cum totalizer having following charecteristics/MOC: Liner: Polyurethane or Hard Rubber / Electrode MOC: SS316L /Housing : Die Cast Aluminium or CS / Power Supply: 90-230 V AC / Output: 4-20mA with HART / Sensor Cable : 10 mt / Flow Tube or Sensor housing protection IP68 / Process Flange : SS316 / Display : 3 1/2 LCD Display / Cable Connection : 1/2\\"NPT /Accuracy : 0.5% |
| 286 | (ii) CVT with control cables |
| 287 | LIFTING TACKLE:Indef/Morris make |
| 288 | Supply, installation and commissioning of 5 T Mono Rail Single Girder having suitable lift (as per sump depth) with chain, pulley block and traveling geared trolley electric operated complete |
| 289 | Tools & Plants as megger,Hydraulic crimping tool,Manual crimping tool,Clamp multimeter,Chain wrench,HT Megger,LT Megger- Sprit level set,Power Drill,Other Tools as specified as per direction of engineer incharge |
| 290 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher. |
| 291 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 292 | Steel revolving chairs. |
| 293 | Fire bucket with stand |
| 294 | Steel Almirah of 6’x3’ |
| 295 | Steel Tubular Table |
| 296 | Installation & Commissioning: |
| 297 | Installation & Commissioning of all 10 Nos. pump sets, piping & valves, guide rail, lifting tackle etc. complete. |
| 298 | Painting |
| 299 | Provision for painting of all pumps, piping and valves with two coat enamel paint as per direction of engineer incharge. |
| 300 | Light Wiring |
| 301 | Light wiring of Pump House, L.T. control room, Meter room, D.G. room, Store and Staff Quarters: |
| 302 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.mm FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles,18 SWG M.S. box with earth terminal, screwless cage connectors for neutral looping in switch board & false ceiling point. 6 A switch, 3.0 mm thick phenolic laminated sheet, zinc plated / brass screws, cup washers, making connections, testing etc. as as per direction of engineer incharge. |
| 303 | Wiring point for LED/ power plug with 2.5 sq mm PVC insulated multi core cable in heavy gauge rigid PVC conduit concealed in wall complete with 1/18 copper wire. Earth continuity wire with 16 Amp. metal clad SPN switch/ 15 Amp. piano type switches complete in all respect as per direction of engineer incharge. |
| 304 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting systemas per direction of engineer incharge. |
| 305 | Supply and fixing of factory wired industrial fluorescent tube fitting with reflector fabricated from CRCA sheet and finished with powder coating / vitreous enamelled complete with accessories complete including tube etc. on wall. |
| 306 | Supply and fixing of 125 watt LED fixture with lamp and its all accessories for campus lghting |
| 307 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 308 | Supply and laying of 95 sq mm/suitable size Cu conductor XLPE insulated 3.5 core submersible cable from Composite panel to pumps (130 HP) |
| 309 | Aluminium Junction Box as per direction of engineer incharge. |
| 310 | SITC of Exhaust fans of suitable sweep/capacity with MS net arrangement as per direction of engineer incharge |
| 311 | Complete double earthing of all pumping plant with all accessories as earth pipe of size (40 mm dia x 5 mm thick),earth strip of size (75 mm x 10 mm) and required material as per direction of engineer incharge and as per specification given in tender documents |
| 312 | Necessory safety equipments such as safety helmet with led head lamp,Yelllow helmet-7 nos,white helmet-3 nos,green helmet-1 no(explosion proof),safety belt with rope-4 nos,protective gloves for Lt Line & Ht Line,fluroscent jacket-6 nos,gas masks and self-contained breathing appratus-2 nos,eye protector-2 nos,air blowers,Electronic Multi Gas Detector,portable alluminum ladder,safety sign board-6 nos,first add box and sewage sump cleaning equipment as per direction of EIC |
| 313 | L.T. Pannel |
| 314 | 2mm thick CRCA sheet fabricated factory wired dust, damp and vermin proof metal clad cubical and floor mounted single row type control panel for system voltage 400+10%, 50 Hz, comprising of following items-L.T. control panel having 4 Nos. (or suitable nos for synchronization) incoming having 1400 amp ACB draw out type & outgoing Panels (10 No.) 250 amp MCCB microprocessor based capacity 01 spare , 3 Nos -100 Amp microprocesor based MCCB for 2 Nos -63 Amp aux light & 5 Nos -32 Amp 5 Nos -16 Amp suitable to operated on 400 ± 6 % volt , 3 Phase , 50 Hz, AC supply ,with C.Ts,P.T AVF Meter,KWH meter P.F Meter, Bus Bar chamber, Relays and other Protective Devices Complete in all Respects.Control panel is also suitable to meet the basic requirements of motor protection such as No volt and under voltage protection and thermal over load protection. Panel will be connected with PLC/RTU. Panel will include synchronization systems for Transformer and DG set, Suitable capacity APFC panel for non VFD Load,Bus Coupler complete with internal wiring and 7 nos. air insulated extensible type aluminium bus bars,as per mentioned in tender documents and direction of EIC |
| 315 | Supply and making end termination/joints of the above cable |
| 316 | Supply and making end termination of the above cable |
| 317 | Complete double Earthing of panel with SUITABLE GI pipe & suitable earthing strip of size electrical equipments as per IS/ IER & direction of engineer encharge |
| 318 | Proper fencing of sub-station portion with size of angle 50 mm X 50 mm X 5mm and cross support with MS strip 5 mm size thick also as per IE Rules as per direction of engineer incharge and as per technical specifications |
| 319 | Charges of Electrical safety clearance. |
| 320 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher.as per direction of engineer incharge |
| 321 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 322 | Supply and laying of 4R*630 sq mm alluminium conductor armoured insulated 3.5 core cable from transformer to LT panel |
| 323 | Erection L.T. panels, laying of required cables & filling L.T. Cable end boxes as detailed above.laying of cable should be through channel of brick work and as per direction of engineer in charge |
| 324 | Exhaust fans of suitable sweep/capacity with safety guard/MS Net arrangement |
| 325 | Commissioning and testing of panel at site |
| 326 | Testing at manufacturer works L.T. Panels |
| 327 | Construction of Sub-Station |
| 328 | (A) 11 KV floor mounting, single row type ABB/Siemens/CG H.T. panel having 1 No. incoming and 2 Nos. outgoing VCB with suitable breaking capacity , panels complete with insulated bus bars, all necessary metering and safety equipments.as per EIC |
| 329 | (B) 11 KV / 0.400 KV,1000 KVA kirloskar/siemens/ABB/Schneider make outdoor, step down transformers |
| 330 | (C) 11 KV XLPE cable of 3 x 120 sqmm/suitable size Al. armoured cable |
| 331 | (E) Cable Jointing Kit |
| 332 | (i) H.T. indoor type |
| 333 | (ii) H.T. outgoing type |
| 334 | (iii) L.T. indoor type |
| 335 | (F) Double earthing of all sub-station equipments complete with salt, charcoal, G.I. earth electrode, C.I. earth boxes, G.I. watering pipe, G.I. earth strip of adequate capacity as required ,labour & t&p, .as per direction of engineer incharge |
| 336 | (H) Internal electrification of H.T. and L.T. control room and switch yard with supplu of all light fittings and exhaust fan with campus lighting |
| 337 | (I) Supply & fixing of M.S. checkered plate over cable trenches |
| 338 | (J) Miscllenous work as barbad wire fencing of switch yard construction of cable trenches, Safety Equipments i.e Fire Extinguisher ,Sand Bucket ,etc etc. |
| 339 | (K) Erection and commissioning of all sub-station equipments |
| 340 | (L) Testing of all equipments of sub-station at manufacturer’s works |
| 341 | (L) Construction of foundations of Transformers and panels |
| 342 | Manual bar Screen |
| 343 | Provision of Stainless Steel(SS 316) manual coarse bar screen having clear gap between screen bar- 50 mm, size of flat shall be 50mm x 10mm angle of installation 70º . Complete |
| 344 | Mechanical Bar Screen |
| 345 | Provision of Huber make Stainless Steel (SS 316) mechanical finebar screen having clear gap between screen bar- 6 mm, size of SS flat shall be 50 mm x 10 mm, angle of installation - 70º duly suitable for 2.44 m wide followed with conveyer system, electric motor, starter, cable, panel, bins etc. (for peak flow upto 115.75 MLD) |
| 346 | Sluice Gate Jash Make |
| 347 | Provision of CI Thimble Mounted Sluice Gate with motor, actuator operated, Rising Spindle type. Sluice gates are as per IS 13349 Including all taxes, Freight, loading, unloading, fitting in position including Sluice gates are upward opening wall thimble mounted suitable for isolating the flow of sewer into out of the opening in the wall. It consists Gate frame, wall thimble, gate slide, shutter, seating/sealing faces .The gates will be provided with pads on sides, top and bottom to mount the wedges. The gate shall be designed in such a manner, so that it can be operated at 2 meter head. Gate frame & Shutter of CI Grade IS 210 FG 260, Head Stock assembly bolts & SS ASTM A276 Type316, Stem, Operating Nut SS ASTM A276 Type 316., Duly tested for tensile strength, Tested for over all dimensions as per approved GA drawing complete in all respect as per specification and direction of Engineer,115.75MLD also at bypass |
| 348 | Testing of above equipment at manufacturer works |
| 349 | Installation & commissioning of all screens and sluice gates complete. |
| 350 | Diesel Generating sets. KOEL / Jackson |
| 351 | SITC of 500 kva DG Set complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled.Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage). Engine shall have residential silencer, up to 10 M exhaust piping , electronic / Mechanical governor, Manual & electric Start ,Batteries, Fuel tank ( with Stand) & piping , control panel (16 G) with MCCB (4P; 25 KA), Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engine instruments,panel, AVM and with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 2.0 mmCRCA sheet steel (structure) with side wall fabricated from 2.0 mm CRCA sheet & filled with 100mm thick glass wool(96Kg/m3) as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, floor of MS chequrred plate 5.0mmthick, canopy fixed with axial flow fan of Alstom, CG, Almonard make. All doors/ opening are sealed with neoprene/EPDN gaskets.The enclosure has residential silencer (isolated from main DG chamber) with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside theenclosure with DG control panel mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level is less than 74 db(A) at a distance of 1 Mtrs. Complete in all respect of 500 KVA at 0.8 pf(lag) 415 V, 3 Ø, 50 Hz capacity Method of cooling- Water. Method of aspiration - Turbo Charged,The control panel will be dust and vermin proof of sheet metal construction, floor mounting type suitable for indoor use in IP- 41 Enclosure. The control panel will comprises of: included in DG set rate |
| 352 | Auto Mains Failure Panel |
| 353 | Provision for PLC based AMF Panel fabricated from CRCA sheet steel 2 mm thick, powder coated finish, START & STOP commands, control relays, selector switches for Ammeter and Voltmeter, Ammeter & Voltmeter, Control & Power contactors, timers, electronic hooters, Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for above DG set |
| 354 | Fuel tank |
| 355 | Batteries 24 volt 360AH dry and uncharged with battery leads and battery charger |
| 356 | Double earthing of DG set and all electrical equipment as per IS |
| 357 | POWER CABLE/BUS BAR |
| 358 | Supplying and laying of Power cable of Suitable size of 1.1KV Volt grade 2R* 400* 3.5 core armoured XLPE sheathed aluminium conductor from DG set To Panel |
| 359 | Supply and making end termination/joints of the above cable |
| 360 | Provision for 12/20mm thick electric resistance rubber sheets |
| 361 | Installation, Testing of D.G. set, cable, AMF panel etc.,Commissioning of the above including supply of diesel and oil for during 3 months trial |
| 362 | AUTOMATION WORK OF MPS |
| 363 | GPRS/GSM based redundant Remote Terminal Unit(RTU) with CPU, Analog & Digital parameters as specified to store and transmit data on GSM backbone to LCS and should be able to send & receive SMS from registered mobile parallel mode. |
| 364 | GSM/GPRS based wireless communication hardware for RTUs. Capable to transfer data from site to LCS with all accessories etc complete. |
| 365 | Intelligent energy meter |
| 366 | Smart Pressure transmitter |
| 367 | Auto phase reversal unit/Automatic transfer switch with inbuilt time delay and enclosure (Conforming to IEC 60947-1 & IEC 60947-6-1) of suitable rating |
| 368 | Cabling & control cabling works |
| 369 | Security survelliance IP camera with recorder |
| 370 | Radar type level transmitter with RTU communication |
| 371 | Control Panel with IP 65 protection, industrial grade 24 V power supply and other required items |
| 372 | 3 phase Surge protector for all AC control supplies to all the equipment |
| 373 | 7\\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 374 | LOCAL CONTROL STATION |
| 375 | CE/UL certified local conrol room PLC with redundant CPU& power supply at LCS in IP 54 enclouser as per spec mentioned in technical bid documents. |
| 376 | CE & BIS approved manufacturer's industrial grade 65 inch LCD monitor with latest configuration as per specification of size 65\\" |
| 377 | Desktop/PC i7 for LCS as per spec. mentioned |
| 378 | CE/UL approved manufacturer's 3 KVA UPS with batteries as spec. mentioned for LCS |
| 379 | Full development version of required TAGS SCADA software suitable for digital and analog input/output features with customization of software as per requirement as per spec. mentioned with unlimited digital and analog Input/Output features specified in detailed technical document with customization of software as requirement |
| 380 | GSM based wireless communication system for PLC capable to transfer and gather data from remote sites to control stations, including all accessories complete |
| 381 | Mobile App facility system architecture ( Industria internet based & viewed through mobile apps for increased local & remote visibility) |
| 382 | CE/UL approved manufacturer's Firewall for network protection |
| 383 | Lightning surge protector for ethernet communication protection |
| 384 | CE/UL approved manufacturer's industrial grade ethernet switch |
| 385 | Canon/HP 1018/equivalent Laser printer |
| 386 | Installation,Commissioning ,testing including required furniture as 2 Tables, 10 Chair, Control Desk,meeting table,almirah & other necessary Furniture items for LCS room internal wiring,PVC panelling of walls/false ceiling work etc. |
| 387 | Split AC suitable for the control room 1.5 tonnes 5 star |
| 388 | Security Survelliance IP camera for LCS with recorder |
| 389 | FOR Lift Station-1 AND THEIR APPURTENANT WORK |
| 390 | VFD starter Required capacity of pump set |
| 391 | SUBMERSIBLE PUMP SET: |
| 392 | Submersible sewage non-clog pumps withJacket cooled Integreated Motor of IP 68Protection for 400±10% V AC, 3phase 50 Hz. suitable to pump raw sewage with specific gravity of 1.05 and also capable to handle solids up to 135mm size with all suitable piping and specials having following material of construction.Casing- 2%NiCIImpeller- ASTM CF8MShaft & Shaft sleeve- ASTM SS 410 including Automatic Coupling system,Guide rail system comprises of Pedestal, bracket, upper guide rail holder etc. |
| 393 | 154 LPS, 21 m Head, 980 RPM |
| 394 | CAPACITOR Panel:(APFC) |
| 395 | Provision for supply of shunt type power factor improvement capacitor panel of suitable to boost the power factor up to 0.95. |
| 396 | MAIN PIPING & VALVES: IVC/ Kirloskar make |
| 397 | Provision for main piping and valves for 350 mm dia, and 800 mm dia common header line |
| 398 | Motor operated Sluice Valve with actuator |
| 399 | CIDF800 mm ø |
| 400 | CIDF 350 mm ø /suitable size |
| 401 | Reflex Valve |
| 402 | CIDF 350 mm ø /suitable size |
| 403 | CIDF 800mm ø |
| 404 | Piping |
| 405 | DIDF Pipe dia 350 mmX 3 m |
| 406 | DIDF Pipe dia 800 mm X 3M |
| 407 | CIDF Tee 800x350x800 mm,CI blind flange dia 800 mm,CIDF 90 degree bend dia 800 mm,CIDF 90 degree bend dia 350 mm,CIDF 90 degree duckfoot bend dia 350 mm,CIDF Reducer/Enlarger 200 mmx350 mm |
| 408 | Dismenaling joints 350 mm |
| 409 | Dismenaling joints 800 mm |
| 410 | Nut and bolts with washer(SS) M20x120,M24x120,M27x140 |
| 411 | Necessary Piping pump set foundation rubber packing, insertion and other material |
| 412 | Electromagnetic Flow Meter: Chronne Marshall make |
| 413 | (i) Providing, Installation, Testing and commissioning of 800 mm ELECTRO MAGNETIC FLOW METER cum totalizer having following charecteristics/MOC: Liner: Polyurethane or Hard Rubber / Electrode MOC: SS316L /Housing : Die Cast Aluminium or CS / Power Supply: 90-230 V AC / Output: 4-20mA with HART / Sensor Cable : 10 mt / Flow Tube or Sensor housing protection IP68 / Process Flange : SS316 / Display : 3 1/2 LCD Display / Cable Connection : 1/2\\"NPT /Accuracy : 0.5% |
| 414 | (ii) CVT with control cables |
| 415 | LIFTING TACKLE:Indef/morris |
| 416 | Supply, installation and commissioning of 5 T Mono Rail Single Girder having suitable lift (as per sump depth) with chain, pulley block and traveling geared trolley electric operated complete |
| 417 | Tools & Plants as megger,Hydraulic crimping tool,Manual crimping tool,Clamp multimeter,Chain wrench,HT Megger,LT Megger- Sprit level set,Power Drill,Other Tools as specified as per direction of engineer incharge |
| 418 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher. |
| 419 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 420 | Steel revolving chairs. |
| 421 | Fire bucket with stand |
| 422 | Steel Almirah of 6’x3’ |
| 423 | Steel Tubular Table |
| 424 | Installation & Commissioning: |
| 425 | Installation & Commissioning of all 10 Nos. pump sets, piping & valves, guide rail, lifting tackle etc. complete. |
| 426 | Provision for painting of all pumps, piping and valves with two coat enamel paint as per direction of engineer incharge. |
| 427 | Light Wiring |
| 428 | Light wiring of Pump House, L.T. control room, Meter room, D.G. room, Store and Staff Quarters: |
| 429 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.mm FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles,18 SWG M.S. box with earth terminal, screwless cage connectors for neutral looping in switch board & false ceiling point. 6 A switch, 3.0 mm thick phenolic laminated sheet, zinc plated / brass screws, cup washers, making connections, testing etc. as as per direction of engineer incharge. |
| 430 | Wiring point for LED/ power plug with 2.5 sq mm PVC insulated multi core cable in heavy gauge rigid PVC conduit concealed in wall complete with 1/18 copper wire. Earth continuity wire with 16 Amp. metal clad SPN switch/ 15 Amp. piano type switches complete in all respect as per direction of engineer incharge. |
| 431 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting systemas per direction of engineer incharge. |
| 432 | Supply and fixing of factory wired industrial fluorescent tube fitting with reflector fabricated from CRCA sheet and finished with powder coating / vitreous enamelled complete with accessories complete including tube etc. on wall. |
| 433 | Supply and fixing of 125 watt LED fixture with lamp and its all accessories for campus lighting |
| 434 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 435 | Supply and laying of 70 sq mm /suitable size Cu conductor XLPE insulated 3.5 core submersible cable from Composite panel to pumps (125 HP) |
| 436 | Aluminium Junction Box as per direction of engineer incharge. |
| 437 | SITC of Exhaust fans of suitable sweep/capacity with loovers & safety guards as per direction of engineer incharge |
| 438 | Complete double earthing of all pumping plant with all accessories as earth pipe of size (40 mm dia x 5 mm thick),earth strip of size (50 mm x 6 mm) and required material as per direction of engineer incharge and as per specification given in tender documents |
| 439 | Necessory safety equipments such as safety helmet with led head lamp,Yelllow helmet-7 nos,white helmet-3 nos,green helmet-1 no(explosion proof),safety belt with rope-4 nos,protective gloves for Lt Line & Ht Line,fluroscent jacket-6 nos,gas masks and self-contained breathing appratus-2 nos,eye protector-2 nos,air blowers,Electronic Multi Gas Detector,portable alluminum ladder,safety sign board-6 nos,first add box and sewage sump cleaning equipment as per direction of EIC |
| 440 | L.T. Pannel |
| 441 | 2mm thick CRCA sheet fabricated factory wired dust, damp and vermin proof metal clad cubical and floor mounted single row type control panel for system voltage 400+10%, 50 Hz, comprising of following items- |
| 442 | Incoming/Outgoing panels |
| 443 | L.T. control panel having 4 Nos. (or suitable nos for synchronization) incoming having 800 amp ACB draw out type & outgoing Panels (10 No.) 250 amp microprocesor based mccb & 01 No spare , 2 Nos -125 Amp mccb, 02 No. 63 & 32 AMP, 02 No. 16AMP MCCB for aux light & suitable to operated on 400 ± 6 % volt , 3 Phase , 50 Hz, AC supply ,with C.Ts,P.T AVF Meter,KWH meter P.F Meter, Bus Bar chamber, Relays and other Protective Devices Complete in all Respects.Control panel is also suitable to meet the basic requirements of motor protection such as No volt and under voltage protection and thermal over load protection. Panel will be connected with PLC/RTU. Panel will include synchronization systems for Transformer and DG set, Suitable capacity APFC panel for non VFD Load,Bus Coupler complete with internal wiring and 7 nos. air insulated extensible type aluminium bus bars as per technical spec. & direction of EIC |
| 444 | Supply and making end termination/joints of the above cable |
| 445 | Supply and making end termination of the above cable |
| 446 | Complete double Earthing of panel with GI pipe & earthing strip As IEC rule electrical equipments as per IS/ IER & direction of engineer encharge |
| 447 | Proper fencing of sub-station portion with size of angle 50 mm X 50 mm X 5mm and cross support with MS strip 5 mm size thick also as per IE Rules as per direction of engineer incharge and as per technical specifications |
| 448 | Charges of Electrical safety clearance. |
| 449 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher.as per direction of engineer incharge |
| 450 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 451 | Supply and laying of 2R*400sq mm alluminium conductor armoured insulated 3.5 core cable from transformer to lt panel |
| 452 | Erection L.T. panels, laying of required cables & filling L.T. Cable end boxes as detailed above.laying of cable should be through channel of brick work and as per direction of engineer in charge |
| 453 | Exhaust fans of suitable sweep/capacity with safety guard/MS Net arrangement |
| 454 | Commissioning and testing at site |
| 455 | Testing at manufacturer works L.T. Panels |
| 456 | Construction of Sub-Station |
| 457 | (A) 11 KV floor mounting, single row type ABB/Siemens/CG make H.T. panel having 1 No. incoming and 2 Nos. outgoing VCB of suitable capacity panels complete with insulated bus bars, all necessary metering and safety equipments. |
| 458 | (B) 11 KV / 0.400 KV,500 KVA kirloskar/siemens/ABB/Schneider make outdoor, step down transformers |
| 459 | (C) 11 KV XLPE HT Power cable of 3c x 95sqmm / suitable size |
| 460 | (E) Cable Jointing Kit |
| 461 | (i) H.T. indoor type |
| 462 | (ii) H.T. outgoing type |
| 463 | (iii) L.T. indoor type |
| 464 | (F) Double earthing of all sub-station equipments complete with salt, charcoal, G.I. earth electrode, C.I. earth boxes, G.I. watering pipe, G.I. earth strip of adequate capacity and should not less than 75 mmX 10 mm and required labour &t&p, .as per direction of engineer incharge |
| 465 | (H) Internal electrification of H.T. and L.T. control room and switch yard with supply of all light fittings and exhaust fan |
| 466 | (I) Supply & fixing of M.S. checkered plate over cable trenches |
| 467 | (J) Miscllenous work as barbad wire fencing of switch yard construction of cable trenches, Safety Equipments i.e Fire Extinguisher ,Sand Bucket ,etc etc. |
| 468 | (K) Erection and commissioning of all sub-station equipments |
| 469 | (L) Testing of all equipments of sub-station at manufacturer’s works |
| 470 | (L) Construction of foundations of Transformers and panels |
| 471 | Manual bar Screen |
| 472 | Provision of Stainless Steel(SS 316) manual coarse bar screen having clear gap between screen bar- 50 mm, size of flat shall be 50mm x 10mm angle of installation 70º . Complete |
| 473 | Mechanical Bar Screen-Huber make |
| 474 | Provision of Stainless Steel (SS 316) mechanical finebar screen having clear gap between screen bar- 6 mm, size of SS flat shall be 50 mm x 10 mm, angle of installation - 70º duly suitable for 2.44 m wide followed with conveyer system, electric motor, starter, cable, panel, bins etc. (for peak flow upto 65MLD) |
| 475 | Sluice Gate-Jash Make |
| 476 | Provision of CI Thimble Mounted Sluice Gate with motor, actuator operated, Rising Spindle type. Sluice gates are as per IS 13349 Including all taxes, Freight, loading, unloading, fitting in position including Sluice gates are upward opening wall thimble mounted suitable for isolating the flow of sewer into out of the opening in the wall. It consists Gate frame, wall thimble, gate slide, shutter, seating/sealing faces .The gates will be provided with pads on sides, top and bottom to mount the wedges. The gate shall be designed in such a manner, so that it can be operated at 2 meter head. Gate frame & Shutter of CI Grade IS 210 FG 260, Head Stock assembly bolts & SS ASTM A276 Type316, Stem, Operating Nut SS ASTM A276 Type 316., Duly tested for tensile strength, Tested for over all dimensions as per approved GA drawing complete in all respect as per specification and direction of Engineer,upto 65 MLD |
| 477 | Testing of above equipment at manufacturer works |
| 478 | Installation & Commissioning |
| 479 | Installation & commissioning of all screens and sluice gates complete. |
| 480 | Diesel Generating sets-KOEL/Jackson Make |
| 481 | SITC of 250 KVA DG Set complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled.Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage). Engine shall have residential silencer, up to 10 M exhaust piping , electronic / Mechanical governor, Manual & electric Start ,Batteries, Fuel tank ( with Stand) & piping , control panel (16 G) with MCCB (4P; 25 KA), Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engine instruments,panel, AVM and with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 2.0 mmCRCA sheet steel (structure) with side wall fabricated from 2.0 mm CRCA sheet & filled with 100mm thick glass wool(96Kg/m3) as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, floor of MS chequrred plate 5.0mmthick, canopy fixed with axial flow fan of Alstom, CG, Almonard make. All doors/ opening are sealed with neoprene/EPDN gaskets. he enclosure has residential silencer (isolated from main DG chamber) with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside theenclosure with DG control panel mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level is less than 74 db(A) at a distance of 1 Mtrs. Complete in all respect of 325 KVA at 0.8 pf(lag) 415 V, 3 Ø, 50 Hz capacity .Method of cooling- Water.Method of aspiration - Turbo ChargedControl panelThe control panel will be dust and vermin proof of sheet metal construction, floor mounting type suitable for indoor use in IP- 41 Enclosure. The control panel will comprises of: |
| 482 | Auto Mains Failure Panel |
| 483 | Provision for PLC based AMF Panel fabricated from CRCA sheet steel 2 mm thick, powder coated finish, START & STOP commands, control relays, selector switches for Ammeter and Voltmeter, Ammeter & Voltmeter, Control & Power contactors, timers, electronic hooters, Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for above DG set |
| 484 | Fuel tank |
| 485 | Batteries 24 volt 180AH dry and uncharged with battery leads and battery charger |
| 486 | Double earthing of DG set and all electrical equipment as per IS |
| 487 | POWER CABLE/BUS BAR |
| 488 | Supplying and laying of Power cable of Suitable size of 1.1kVolt grade 2Rx 185 sq mm/suitable size *3.5 core armoured XLPE sheathed aluminium conductor from DG set to Main LT Panel |
| 489 | Supply and making end termination/joints of the above cable |
| 490 | Electric Resistance Rubber sheets. |
| 491 | Provision for 12/20mm thick electric resistance rubber sheets |
| 492 | INSTALLATION, COMMISSIONING AND TESTING |
| 493 | Installation, Testing of D.G. set, cable, AMF panel etc.,Commissioning of the above including supply of diesel and oil for during 3 months trial |
| 494 | Testing of D.G set at manufacturer works |
| 495 | AUTOMATION OF Lift Station-1 |
| 496 | GPRS/GSM based redundant Remote Terminal Unit(RTU) with CPU, Analog & Digital parameters as specified to store and transmit data on GSM backbone to LCS and should be able to send & receive SMS from registered mobile parallel mode. |
| 497 | GSM/GPRS based wireless communication hardware for RTUs. Capable to transfer data from site to LCS with all accessories etc complete. |
| 498 | Intelligent energy meter |
| 499 | Smart Pressure transmitter |
| 500 | Auto phase reversal unit/Automatic transfer switch with inbuilt time delay and enclosure (Conforming to IEC 60947-1 & IEC 60947-6-1) of suitable for load. |
| 501 | Cabling & control cabling works |
| 502 | Security survelliance IP camera with recorder |
| 503 | Radar type level transmitter with RTU communication |
| 504 | Control Panel with IP 65 protection, industrial grade 24 V power supply and other required items |
| 505 | 3 phase Surge protector for all AC control supplies to all the equipment |
| 506 | 7\\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 507 | FOR Lift Station-2 AND THEIR APPURTENANT WORK |
| 508 | VFD starter Required capacity of pump set |
| 509 | SUBMERSIBLE PUMP SET: |
| 510 | Submersible sewage non-clog pumps withJacket cooled Integreated Motor of IP 68Protection for 400±10% V AC, 3phase 50 Hz. suitable to pump raw sewage with specific gravity of 1.05 and also capable to handle solids up to 135mm size with all suitable piping and specials having following material of construction.Casing- 2%NiCIImpeller- ASTM CF8MShaft & Shaft sleeve- ASTM SS 410 including Automatic Coupling system,Guide rail system comprises of Pedestal, bracket, upper guide rail holder etc. |
| 511 | 219 LPS, 21 m Head, 980 RPM |
| 512 | CAPACITOR Panel:(APFC) |
| 513 | Provision for supply of shunt type power factor improvement capacitor panel of suitable to boost the power factor up to 0.95. |
| 514 | MAIN PIPING & VALVES: IVC/ Kirloskar make |
| 515 | Provision for main piping and valves for 400 mm dia, and 1100 mm dia common header line |
| 516 | Motor operated Sluice Valve with actuator |
| 517 | CIDF1100mm ø |
| 518 | CIDF 400 mm ø/suitable size |
| 519 | Reflex Valve |
| 520 | CIDF 400 mm ø/suitable size |
| 521 | CIDF 1100mm ø |
| 522 | Piping |
| 523 | DIDF Pipe dia 1100 mmX 3 m |
| 524 | DIDF Pipe dia 400 mm (3M) |
| 525 | CIDF Tee 1100x400x1050 mm,DI blind flange dia 1100 mm,CIDF 90 degree bend dia 1100 mm,CIDF 90 degree bend dia 400 mm,CIDF 90 degree duckfoot bend dia 400 mm,CIDF Reducer/Enlarger 1100 mmx400 mm ,DIDF Reducer/Enlarger 1100 mmx 400 mm as per site requirement |
| 526 | Dismenaling joints 400 mm |
| 527 | Dismenaling joints 1100 mm |
| 528 | Nut and bolts with washer(SS) M20x120,M24x120,M27x140 as per site requirement |
| 529 | Necessary Piping pump set foundation rubber packing, insertion and other material |
| 530 | Electromagnetic Flow Meter: Khronne Marshall make |
| 531 | (i) Providing, Installation, Testing and commissioning of 1100 mm ELECTRO MAGNETIC FLOW METER cum totalizer having following charecteristics/MOC: Liner: Polyurethane or Hard Rubber / Electrode MOC: SS316L /Housing : Die Cast Aluminium or CS / Power Supply: 90-230 V AC / Output: 4-20mA with HART / Sensor Cable : 10 mt / Flow Tube or Sensor housing protection IP68 / Process Flange : SS316 / Display : 3 1/2 LCD Display / Cable Connection : 1/2\\"NPT /Accuracy : 0.5% |
| 532 | (ii) CVT with control cables |
| 533 | LIFTING TACKLE:indef/morris |
| 534 | Supply, installation and commissioning of 5 T Mono Rail Single Girder having suitable lift (as per sump depth) with chain, pulley block and traveling geared trolley electric operated complete |
| 535 | Tools & Plants as megger,Hydraulic crimping tool,Manual crimping tool,Clamp multimeter,Chain wrench,HT Megger,LT Megger- Sprit level set,Power Drill,Other Tools as specified as per direction of engineer incharge |
| 536 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher. |
| 537 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 538 | Steel chairs. |
| 539 | Fire bucket with stand |
| 540 | Steel Almirah of 6’x3’ |
| 541 | Steel Tubular Table |
| 542 | Installation & Commissioning: |
| 543 | Installation & Commissioning of all 8 Nos. pump sets, piping & valves, guide rail, lifting tackle etc. complete. |
| 544 | Painting |
| 545 | Provision for painting of all pumps, piping and valves with two coat enamel paint as per direction of engineer incharge. |
| 546 | Light Wiring |
| 547 | Light wiring of Pump House, L.T. control room, Meter room, D.G. room, Store and Staff Quarters: |
| 548 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq.mm FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles,18 SWG M.S. box with earth terminal, screwless cage connectors for neutral looping in switch board & false ceiling point. 6 A switch, 3.0 mm thick phenolic laminated sheet, zinc plated / brass screws, cup washers, making connections, testing etc. as as per direction of engineer incharge. |
| 549 | Wiring point for LED/ power plug with 2.5 sq mm PVC insulated multi core cable in heavy gauge rigid PVC conduit concealed in wall complete with 1/18 copper wire. Earth continuity wire with 16 Amp. metal clad SPN switch/ 15 Amp. piano type switches complete in all respect as per direction of engineer incharge. |
| 550 | Provision for supply & fixing of main suitable distribution boards with MCBs for controlling the lighting systemas per direction of engineer incharge. |
| 551 | Supply and fixing of factory wired industrial fluorescent tube fitting with reflector fabricated from CRCA sheet and finished with powder coating / vitreous enamelled complete with accessories complete including tube etc. on wall. |
| 552 | Supply and fixing of 125 watt LED fixture with lamp and its all accessories. |
| 553 | Supply & fitting of steel swaged tubular poles of 9M length as per I.E. rules. |
| 554 | Supply and laying of 70 sq mm Cu conductor XLPE insulated 3.5 core submersible cable from Composite panel to pumps (125 HP) |
| 555 | Aluminium Junction Box as per direction of engineer incharge. |
| 556 | SITC of Exhaust fans of suitable sweep/capacity with loovers & safety guards as per direction of engineer incharge |
| 557 | Complete double earthing of all pumping plant with all accessories as earth pipe of size (40 mm dia x 5 mm thick),earth strip of size (75 mm x 10 mm) and required material as per direction of engineer incharge and as per specification given in tender documents |
| 558 | Necessory safety equipments such as safety helmet with led head lamp,Yelllow helmet-7 nos,white helmet-3 nos,green helmet-1 no(explosion proof),safety belt with rope-4 nos,protective gloves for Lt Line & Ht Line,fluroscent jacket-6 nos,gas masks and self-contained breathing appratus-2 nos,eye protector-2 nos,air blowers,Electronic Multi Gas Detector,portable alluminum ladder,safety sign board-6 nos,first add box and sewage sump cleaning equipment as per direction of EIC |
| 559 | L.T. Pannel |
| 560 | 2mm thick CRCA sheet fabricated factory wired dust, damp and vermin proof metal clad cubical and floor mounted single row type control panel for system voltage 400+10%, 50 Hz, comprising of following items-L.T. control panel having 4 Nos. (or suitable nos for synchronization) incoming having 1000 Amp ACB draw out type & outgoing Panels (10 No.) 320 amp 01 spare microprocesor based mccb , 2 Nos -100 Amp microprocesor based MCCB for aux light & suitable to operated on 400 ± 6 % volt , 3 Phase , 50 Hz, AC supply ,with C.Ts,P.T AVF Meter,KWH meter P.F Meter, Bus Bar chamber, Relays and other Protective Devices Complete in all Respects.Control panel is also suitable to meet the basic requirements of motor protection such as No volt and under voltage protection and thermal over load protection. Panel will be connected with PLC/RTU. Panel will include synchronization systems for Transformer and DG set, Suitable capacity APFC panel for non VFD Load,Bus Coupler complete with internal wiring and 7 nos. air insulated extensible type aluminium bus bars as per direction of EIC |
| 561 | Supply and making end termination/joints of the above cable |
| 562 | Supply and making end termination of the above cable |
| 563 | Complete double Earthing of panel with GI pipe (40 mm dia x 5 mm thick) & earthing strip of size (50 mm x 6 mm) electrical equipments as per IS/ IER & direction of engineer encharge |
| 564 | Proper fencing of sub-station portion with size of angle 50 mm X 50 mm X 5mm and cross support with MS strip 5 mm size thick also as per IE Rules as per direction of engineer incharge and as per technical specifications |
| 565 | Charges of Electrical safety clearance. |
| 566 | Supply of 5 kg Capacity Dry Powder/ABC type fire extinguisher.as per direction of engineer incharge |
| 567 | 12/20 mm. thick rubber electric resistance rubber sheet as per ISS. |
| 568 | Supply and laying of 3R*400sq mm/suitable size alluminium conductor armoured insulated 3.5 core cable from transformer to lt panel |
| 569 | Erection L.T. panels, laying of required cables & filling L.T. Cable end boxes as detailed above.laying of cable should be through channel of brick work and as per direction of engineer in charge |
| 570 | Exhaust fans of suitable sweep/capacity |
| 571 | Commissioning and testing at site |
| 572 | Testing at manufacturer works L.T. Panels |
| 573 | Construction of Sub-Station |
| 574 | (A) 11 KV floor mounting, single row type H.T. panel ABB/Siemens/CG having 1 No. incoming and 2 Nos. outgoing VCB(630Amp) panels complete with insulated bus bars, all necessary metering and safety equipments. |
| 575 | (B) 11 KV / 0.400 KV,630 KVA kirloskar/siemens/ABB/Schneider make outdoor, step down transformers |
| 576 | (C) 11 KV XLPE cable of 3 x95 sqmm size Al. armoured cable |
| 577 | (E) Cable Jointing Kit |
| 578 | (i) H.T. indoor type |
| 579 | (ii) H.T. outgoing type |
| 580 | (iii) L.T. indoor type |
| 581 | (F) Double earthing of all sub-station equipments complete with salt, charcoal, G.I. earth electrode, C.I. earth boxes, G.I. watering pipe, G.I. earth strip of adequate capacity and should not less than 75 mmX 10 mm and required labour &t&p, .as per direction of engineer incharge |
| 582 | (H) Internal electrification of H.T. and L.T. control room and switch yard with supplu of all light fittings and exhaust fan |
| 583 | (I) Supply & fixing of M.S. checkered plate over cable trenches |
| 584 | (J) Miscllenous work as barbad wire fencing of switch yard construction of cable trenches, Safety Equipments i.e Fire Extinguisher ,Sand Bucket ,etc etc. |
| 585 | (K) Erection and commissioning of all sub-station equipments |
| 586 | (L) Testing of all equipments of sub-station at manufacturer’s works |
| 587 | (L) Construction of foundations of Transformers and panels |
| 588 | Manual bar Screen |
| 589 | Provision of Stainless Steel(SS 316) manual coarse bar screen having clear gap between screen bar- 50 mm, size of flat shall be 50mm x 10mm angle of installation 70º . Complete |
| 590 | Mechanical Bar Screen-Huber make |
| 591 | Provision of Stainless Steel (SS 316) mechanical finebar screen having clear gap between screen bar- 6 mm, size of SS flat shall be 50 mm x 10 mm, angle of installation - 70º duly suitable for 2.44 m wide followed with conveyer system, electric motor, starter, cable, panel, bins etc. (for peak flow upto 85 MLD) |
| 592 | Sluice Gate-Jash Make |
| 593 | Provision of CI Thimble Mounted Sluice Gate with motor, actuator operated, Rising Spindle type. Sluice gates are as per IS 13349 Including all taxes, Freight, loading, unloading, fitting in position including Sluice gates are upward opening wall thimble mounted suitable for isolating the flow of sewer into out of the opening in the wall. It consists Gate frame, wall thimble, gate slide, shutter, seating/sealing faces .The gates will be provided with pads on sides, top and bottom to mount the wedges. The gate shall be designed in such a manner, so that it can be operated at 2 meter head. Gate frame & Shutter of CI Grade IS 210 FG 260, Head Stock assembly bolts & SS ASTM A276 Type316, Stem, Operating Nut SS ASTM A276 Type 316., Duly tested for tensile strength, Tested for over all dimensions as per approved GA drawing complete in all respect as per specification and direction of Engineer, for 85 MLD also at bypass side |
| 594 | Testing of above equipment at manufacturer works |
| 595 | Installation & Commissioning |
| 596 | Installation & commissioning of all screens and sluice gates complete. |
| 597 | Diesel Generating sets-KOEL/Jackson Make |
| 598 | SITC of 500 KVA DG Set complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled.Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage). Engine shall have residential silencer, up to 10 M exhaust piping , electronic / Mechanical governor, Manual & electric Start ,Batteries, Fuel tank ( with Stand) & piping , control panel (16 G) with MCCB (4P; 25 KA), Ammeter, Voltmeter, Frequency Meter, Energy Meter & Hour Meter, Engine instruments,panel, AVM and with Weatherproof,turbocharged,water cooled powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 2.0 mmCRCA sheet steel (structure) with side wall fabricated from 2.0 mm CRCA sheet & filled with 100mm thick glass wool(96Kg/m3) as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, floor of MS chequrred plate 5.0mmthick, canopy fixed with axial flow fan of Alstom, CG, Almonard make. All doors/ opening are sealed with neoprene/EPDN gaskets. The enclosure has residential silencer (isolated from main DG chamber) with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside theenclosure with DG control panel mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level is less than 74 db(A) at a distance of 1 Mtrs. Complete in all respect of 500 KVA at 0.8 pf(lag) 415 V, 3 Ø, 50 Hz capacity .Control panelThe control panel will be dust and vermin proof of sheet metal construction, floor mounting type suitable for indoor use in IP- 42 Enclosure. The control panel will comprises of:Auto Mains Failure PanelProvision for PLC based AMF Panel fabricated from CRCA sheet steel 2 mm thick, powder coated finish, START & STOP commands, control relays, selector switches for Ammeter and Voltmeter, Ammeter & Voltmeter, Control & Power contactors, timers, electronic hooters, Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for above DG set |
| 599 | Fuel tank |
| 600 | Batteries 24 volt 360AH dry and uncharged with battery leads and battery charger |
| 601 | Double earthing of DG set and all electrical equipment as per IS |
| 602 | POWER CABLE/BUS BAR |
| 603 | Supplying and laying of Power cable of Suitable size of 1.1kVolt grade 3Rx 240*3.5 core armoured XLPE sheathed aluminium conductor from DG set to Main LT Panel |
| 604 | Supply and making end termination/joints of the above cable |
| 605 | Provision for 12/20mm thick electric resistance rubber sheets |
| 606 | Installation, Testing of D.G. set, cable, AMF panel etc.,Commissioning of the above including supply of diesel and oil for during 3 months trial |
| 607 | Testing of D.G set at manufacturer works |
| 608 | AUTOMATION OF Lift Station-2 |
| 609 | GPRS/GSM based redundant Remote Terminal Unit(RTU) with CPU, Analog & Digital parameters as specified to store and transmit data on GSM backbone to LCS and should be able to send & receive SMS from registered mobile parallel mode.(one iRTU for two pumps) |
| 610 | GSM/GPRS based wireless communication hardware for RTUs. Capable to transfer data from site to LCS with all accessories etc complete. |
| 611 | Intelligent energy meter |
| 612 | Smart Pressure transmitter |
| 613 | Auto phase reversal unit/Automatic transfer switch with inbuilt time delay and enclosure (Conforming to IEC 60947-1 & IEC 60947-6-1) of suitable for 4000Amp. rating |
| 614 | Cabling & control cabling works |
| 615 | Security survelliance IP camera with recorder |
| 616 | Radar type level transmitter with RTU communication |
| 617 | Control Panel with IP 65 protection, industrial grade 24 V power supply and other required items |
| 618 | Surge protector for all AC control supplies to all the equipment |
| 619 | 7\\" HMI touchscreen suitable to communicate with PLC/RTU, for local display & control of process parameters |
| 620 | 3 months trial run for MPS,SPS-1 & SPS-2 with all consumables Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 13, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 11, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysDec 11, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender