Tender For Provision Of Air Conditioners For Main Signal Office And Telephone Maintenace Cell At Icgas Ratnagiri And Provision Of 3 Phase Socket For Electrical Steamer At Tilak Block Of Icgs Ratnagiri
Tender Value
3.80 Lakhs
Estimated cost
Bid Submission
03 Dec 2026
14 days left
EMD
7600
Bank guarantee accepted
Document Fee
300
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ratnagiri → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Air Conditioners For Main Signal Office And Telephone Maintenace Cell At Icgas Ratnagiri And Provision Of 3 Phase Socket For Electrical Steamer At Tilak Block Of Icgs Ratnagiri
BOQ
| Sl. No. | Item Description |
| 1 | Supply and Fixing of air cooled split unit air conditioner electric driven, single phase, complete with cordless remote control unit and within built air ionizer and Plasma filter for better indoor air quality of capacity of 2.0 TR, BEE 5 star rated invertor type and making the surface good to match the existing complete all as specified and directed. |
| 2 | Supply and Fixing of Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 130 Volts to 280 Volts with output voltage stabilized at 230 Volts with accuracy of ± 2.5% and of capacity 5 KVA suitable up to 2 ton AC complete all as specified and directed. |
| 3 | Supply and Fixing of rigid non-metallic PVC conduit as drain pipe of size 20 mm dia for AC water outlet inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc fixed along wall and leaving the outlet in the drain nearby complete all as specified and directed. |
| 4 | Supply and Fixing of Single pole and Neutral enclosure with a two pin and earth plug and socket pvc box type complete with one single pole MCB 25 Amp all as specified and directed. Note: AC box include three pin plug and 25 Amps MCB in their connection. |
| 5 | Material and Labour for wiring for circuit/submain wiring along with earth wire with the 2x10.0 sqmm +1x10.0 sqmm earth wire size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC casing capping complete all as specified and directed. |
| 6 | Material and Labour for wiring for circuit/submain wiring along with earth wire with the 2x6.0 sqmm +1x6.0 sqmm earth wire size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC casing capping complete all as specified and directed. |
| 7 | Supply and Fixing of MCB DB made of sheet steel double Door, powder painted with neutral bus bar with suitable rating neutral link earth bar and din rail with Single pole & neutral Single pole & neutral, 8 Way all as specified and directed by Engineer-in-charge. |
| 8 | Supply and Fixing of amp rating 240 Volts, 10KA 'C' curve miniature circuit breaker (MCB) of SPN, 40 Amps capacity in the MCB DB complete with connection testing and commissioning all as specified and directed. |
| 9 | Supply and Fixing of Amp rating 240 Volts, 10KA 'C' curve miniature circuit breaker (MCB) of SP, 6-32 Amps current capacity in the MCB DB complete with connection testing and commissioning all as specified and directed. Note: Rate includes the fixing of MCB in existing DB. |
| 10 | Supply and fixing TP MCB of rating 415 Volts, 10KA 'C' curve miniature circuit breaker (MCB) of TP,63 Amps capacity in the MCB DB complete with connection testing and commissioning all as specified an directed. |
| 11 | Material and Labour for wiring for circuit/submain wiring along with earth wire with the 4x10.0 sqmm +1x10.0 sqmm earth wire size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC casing capping complete all as specified and directed. |
| 12 | Supply and fixing of insulated Plug & Socket TPN enclosure with 3P+N+E, 3 pole, Neutral and Earth Metal Plug and Socket for Incorporating, 32 Amps TPN MCB all as specified and directed.Note:32 Amps TPN MCB to be measured and paid separately. |
| 13 | Supply and fixing TPN MCB of rating 32 Amps, 415 Volts, 'C' curve miniature circuit breaker (MCB) of breaking capacity 10KA in Solution with Insulated Plug & Socket TPN enclosure with connection testing and commissioning complete all as specified and directed. |
| 14 | Supply and installation of fast earth electrode 3.0 meter length size model F84, having two M S pipe one inside the other with proper not deep galvanized outer dia 88 mm and inner dia 48 mm and the cavity between the rod pipes is filled with ground resistance improvement powder, sealed with both end the outer pipe of electrode should be zinc coated, the electrode should buried directly in the ground by making boring of diameter 10\\" with boring machine highly conductive nonmagnetic and non-corrosives is to be connected with GI wire of 4 Sqmm of 2 to 3 meter length to facilitate further connection to earth dolly and provision of earthing chamber in bricks wall size 45 x 45 x 15 cm an having PCC cover of required size complete all as directed and all as per IS 3034 (1981) complete all as specified and directed. Note:Gl Wire to be measured and paid separately. |
| 15 | Material and Labour for earth continuity conductor or main earthing lead fixed wall on batten or recess or chases or buried in ground or drawn in conduit /pipe or fixed to pole or any other indicated situation for loop earthing etc as required 4 mm dia galvanized iron wire all as specified and directed. |
| 16 | Supply and fixing of GI tubing medium grade (ISI marked) of size 15 mm dia with all fitting/accessories for protection of cable on pole / wall an under road crossing including clamps, nuts bolts etc all as specified and directed |
| 17 | Supply and fixing distribution board sheet metal enclosure double door shutter type factory made fixed flush with wall or outside on wall surface suitable for MCB ,Single pole and neutral 4 Way , with rated bus bar and powder painted with neutral bus bar with suitable rating nutral link earth bar, complete all as specified an directed. |
| 18 | Material and Labour for circuit/submain wiring along with earth wire with the 2x2.5 sqmm +1x 2.5 sqmm earth wire size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed as required in PVC casing capping complete all as specified and directed. |
| 19 | Supply and fixing of modular White cover plate with frame, 6 module, laser marking complete all as specified and directed. . |
| 20 | Supply and fixing of switch modular type 6 Amps one way, 1 module, AC 230 Volts, shrouded terminal, ISI marked complete all as specified and directed. |
| 21 | Supply and fixing of modular type socket 6 Amps 3 pin round socket with child safety shutter (ISI marked), AC 230 Volts, shrouded terminals, smooth plug removal and insertion complete all as specified and directed. |
| 22 | Supply and fixing of switch modular type 16 Amps one way, 1 module, AC 230 Volts, LED based indicator, shrouded terminal, ISI marked complete all as specified and directed. |
| 23 | Supply and fixing of modular type socket 6 Amps/ 16 Amp 3 pin socket with child safety shutter (ISI marked), AC 230 Volts, shrouded terminals, smooth plug removal and insertion complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 12, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 03, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 14 daysDec 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender