Tender For Providing Fire Fighting Arrangements To 50 Bedded Critical Care Block Building In Government Hospital At Mettupalayam In Coimbatore District

Issued by Government Departments · Coimbatore, Tamil Nadu
Tender Value
Ref. Documents
Estimated cost
Bid Submission
26 Nov 2026
10 days left
EMD
62000
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Coimbatore → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Providing Fire Fighting Arrangements To 50 Bedded Critical Care Block Building In Government Hospital At Mettupalayam In Coimbatore District

BOQ

Name of Work:- Providing Fire Fighting Arrangements to 50 Bedded Critical Care Block Building in Government Hospital at Mettupalayam in Coimbatore District
Sl. No. Item Description
1Supply, erection, testing and commissioning of Fire Fighting Application Horizontal Centrifugal Type Pump Rated for 2280 LPM at 70 metres head with Electrical Motor of 60 HP of 415 volt 3 phase connection complete with base plate and accessories. The rate inclusive of necessary vibration, bad mounting etc., as per standard method as directed by the Deparmental Officers.
2Supply, erection, testing and commissioning of 180 LPM, 70 metres Head Pressurization Pump with 10HP electrical motor of Kirloskar make with suitable base frame including necessary vibration bad mounting etc., including conveying, fixing and incidental charges, etc., complete as per standard specification and as directed by the Departmental Officers.
3Supplying, installation, testing and commissioning of Fire Fighting Electrical Control Panel of cubical construction, floor mounted type fabricated using CRCA sheet, compartmentalised with hinged lockable door dust and vermin proof, cable alley, inter connection having switch gears and accessories mounting and internal wiring, earth terminals, numberings, necessary metering protections and indications complete in all respect suitable for operation on 415volt, 3 phase, 50 Hz AC supply with enclosure protection class IP 54 and mounted with the followings.A. Common Panel in Fire Pump House(i). Incomera. 1 No. 600A TP & N SDFU with HRC fuses b. 1 set of 600A, 4 bar aluminium bus bar, 415 V, 50 HZ AC supply c. 1 No. (0-500A) digital ammeter with selector switch & CTs d. 1 No. (0-500V) digital voltmeter with selector switch and control fuses e. 3 Nos. phase indication lamp LED type with toggle switches with control fuses(ii). Outgoinga. Main Fire Pump 400 A TPN SDFU with HRC fuses with sutable HP fully automatic starter / delta starter with over load protection, digital ammeter with built-in selector switch and suitable CTs, current sensing type single phasing preventer complete with all accessories and internal wiring required for automatic operation, selector switch for auto / manual /OFF operation - 1 No
4b. Jockey Pump 125 A TPN SDFU with HRC fuses with suitable HP fully automatic starter / delta starter with over load protection, current sensing type single phasing preventer complete with all accessories and internal wiring required for automatic operation, selector switch for auto / manual operation - 1 No.c. Diesel Engine Control comprising of:1. Auto / manual selector switch and 3 attempt starting device, timers and relays as required, push buttons, start / stop in manual mode.2. Indication lamp for high / low lubricant oil pressure, high water temperature and engine ON indication.3. Battery charger suitable for 12V /24V DC with boost and tickle selector switch, 0-15V / 0-30V DC volt meter, 0-20A DC ammeter. 4. All standard relays and accessories for automatic operation of diesel engine.5. The above combined panel mounted over MS channel fabricated frame with cement concrete platform, all other connection works carried out as per standard methods and including conveying, fixing and incidental charges, etc., complete as per standard specification and as directed by the Departmental Officers.
5Supply, installation, testing and commissioning of Diesel Engine Driven Main Fire Pump suitable for automatic operation and consisting of following and complete in all respects as required. a. End suction, top discharge centrifugal pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg. / sq. cm at highest and farthest outlet at specified flow of 2280 LPM at 70m head conforming to IS 1520. b. 68 BHP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant BS & IS standard complete. Auto starting mechanism, 12 volts / 24 volts electric starting equipment like self motor, dyanamo, solenoid switches etc. c. 110 litres capacity diesel tank mounted over stand fabricated using 25mm x 25mm x 6mm size MS angle, providing with level indicator, inlet port, outlet port, drain port and diesel return line port and fuel pre-filter, after filter etc. d. Exhaust system having flexible metallic mufler, 100mm dia MS heavy pipe extended upto 1m, outside pump house duly insulated with 50mm thick glass wool with 1mm thick aluminium sheet cladding, residential silencer with necessory MS support arrangements from wall or ceiling as per site condition.
6e. Dash board consisting the instruments like temperature gauge, galvano type DC Ammeter, lubricant oil pressure gauge, ignition switch, emergency stop and all other protection equipment as per specification, stop seleneid for auto stop in the event of fault with audio indications, painted with post office red colour etc., as required. f. 12 V / 24 V storage battery, maintenance free tape, 180 AH rating, MS fabricated common base plate, coupling guard, foundation bolts etc., as required. g. Positioning the diesel engine driven fire pump over cement concrete foundation using suitable size anti-vibration mounting arrangement. All works carried out as per standard methods and as instructed by the manufacturer and as directed by the Departmental Officers. (Make: Kirloskar / Equivalent)
7Supply and laying of following sizes of Armoured Aluminium / Copper Cables for electrical motor, control panel, pressure switch, jockey motor etc., all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
83 core 10 sq.mm. armoured copper cable
9Supply and installation of Cast Iron Butterfly Valves with top and bottom of S.S. 410 Shaft, Wafer Liner / with reduction Gear Unit (Conforming to BS 5155 & ISI 3095 / 1996) with 5 years warranty including operating handle marked open / shut as per standard methods and as directed by the Departmental Officers.
10150mm dia
11100mm dia
1280mm dia
1350mm dia
14Supply, erection, testing and commissioning of Cast iron body and Gun metal or stainless steel internal Non-return valve of following sizes to control one way flow of water to be installed pump room at delivery line and near overhead tank at terrace level near to jockey pump and motor including necessary MS flange of table ‘E’, gaskets, bolts & nuts, etc. as per IS 5312 including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
15150mm dia
16100mm dia
17Supply, erection, testing and commissioning of cast iron body and gun metal or stainless steel Internal Non-Return Valve of size of 80mm dia to control one way flow of water to be installed pump room at delivery line and near overhead tank at terrace level near to jockey pump and motor including necessary MS flange of table ‘E’, gaskets, bolts & nuts, etc. as per IS 5312 including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
18Supply, erection, testing and commissioning of Gun Metal Gate Valve of size 50mm dia size including necessary MS flange of table ‘E’, gaskets, bolts & nuts etc., installed at pump house delivery line for the purpose of priming water to suction line including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
19Supply, erection, testing and commissioning of following MS ‘C’ Class Heavy Duty Pipe as per IS 1239 to withstand a developing pressure of 10 kg. / sq.cm including necessary fittings like MS flange of table ‘E’, elbows, reducers, gaskets, bolt, nuts with washers & joints as per standard method of arc welding, including one coat metal primer and two coat Post Office Red painting including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
20200mm dia
21150mm dia
22100mm dia
2380mm dia
2450mm dia
2525mm dia
26Supply, installation of Fire Fighting Application 180 degree swinging type, hose reel drum with 20mm dia braided thermoplastic hose of 30 metres long, so as to extend to necessary distance by self rolling spindle wheel including necessary 20mm dia ball valve and open and close spray nozzle, warm clip, etc., as per the standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers.
27Supply and fixing of Fire fighting application oblique type stainless steel Hydrant Valve of size 63mm dia with oblique type instantaneous coupling with rotating wheel to open and close the valve including MS flange of table E, bolts & nuts with washer as per IS 5290 at ring main around the building and wet riser inside the building including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers.
28Supply, and fixing in position of Fire Fighting Application Hose of 63mm dia of 15 metres length binded by copper wire with 63mm dia stainless steel male and female instantaneous fire fighting special coupling as per IS 901 as directed by the Departmental Officers. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers.
29Supply, and fixing in position of Fire Fighting Application 63mm dia stainless steel short length Branch Pipe with hexagonal type spray nozzle of 15mm (or) 20mm jet bore. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
30Supply of Fire Fighting Application MS Hose Box to keep two number of hoses and 1 No. of branch pipe with nozzle having proper glass window type double door with universe open key, painted inside white and outside Post Office Red. Near every hydrant point including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
31Supply, erection, testing and commissioning of Fire Fighting 4 Way Fire Brigade Inlet with necessary gun metal 63mm dia non return spring shutter arrangements, so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
32Supply, erection, testing and commissioning of Pressure Gauge with 0 to 14 kg. range of reputed make with necessary valve, milling thread MS coupling fixed at delivery pipe line in pump house to read the developing pressure including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
33Supply, erection, testing and commissioning of Air Release Valve of 20mm dia, so as to release airlock in 100mm dia MS pipe at top most wet riser, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
34Supply, erection, testing and commissioning of suitable Pressure Switch of reputed make line Indfoss or Donfoss including necessary valves, couplings, etc., connected with electrical main control panel and setup at proper differential so as to auto start and auto stop the electrical motor, jockey motor including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., completed as per standard specification and as directed by the Departmental Officers.
35Supply and fixing of stored pressure ABC (Mono Ammonium Phospate) Powder Type Fire Extinguisher of 6 kg. capacity as per IS:15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc, complete as per standard specification and as directed by the Departmental Officers.
36Supply, installation, testing and commissioning of Micro Processor based conventional 8 Zone Fire Alarm Control Panel having the rating of 24 volt DC power supply, consisting 230 / 24 volt SMPS unit, 2 Nos. of 12 volt 7 AH standby batteries, suitably mounted on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers.
37Supply, installation, testing and commissioning of Manual Call Point (MCP) providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers.
38Supply, installation, testing and commissioning of Electronic Hooter / Sounder providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers
39Supply and laying of 2 core 1.5 sq.mm. armoured copper cable for control wiring to the Terrace Pump Motor with runs of 14 SWG TC wire for earthing, providing in wall with suitable size GI clamps, screws, wooden plug, end termination by using suitable size cable glands, copper sockets and etc., as directed by the Departmental Officers.
40Supply, installation, testing and commissioning of Conventional Smoke Detector suitably mounted on ceiling with MS juction box / false ceiling using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers.
41Priming Tank mounted with the supporting arrangement fabricated using MS angle for the height of 3 metres from the floor level, inlet, outlet, and drain arrangements inside the fire fighting pump room, as directed by the Departmental Officers.
42Earth work excavation for foundation by manual means for RR/Brick and Other step type footings for Load bearing structures in all soils and sub-soils and to full depth as may be directed except in rock requiring blasting inclusive of shoring shuttering, bailing out water wherever necessary and depositing the surplus earth within the compound in places shown by the departmental officers with an initial lead of 10 mts and initial lift of 2.00mts. and clearing and levelling the site, etc., complete complying with standard specification and as directed by the departmental officers.
43Supply, erection, testing and commissioning of following sizes of Heavy Duty Foot Valve including all accesories, such as, MS flange of table ‘E’, gaskets, bolts & nuts, etc., installed at end of 150 / 200mm dia suction pipe line at sump including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete and as per standard specification and as directed by the Departmental Officers.
44200mm dia
45100mm dia
46Wrapping and coating anti-corrosive treatment for the following under ground MS pipe having one coat of anti-corrosive metal primer, one layer of asphalt tar tape wound over the MS Pipe as per standard methods as per standard specifications and as directed by the Departmental Officers.
47150mm dia
48Supply and fixing nominal bore quartized bulb type sprinkler bulb 68 Deg C fast response pendent type including GI collar for each sprinkler bulb, mounted in MS pipe line using suitable size MS threaded coupling, thread, shellac etc., as per standard methods and including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
49Supply, Installing, testing and commissioning of Stainless Steel Corrugated Flexible Braided Pipe (Hose) for dropping sprinklers below false ceiling. Pipe shall be 16 bar pressure rating and 1500mm long, 25mm dia with union / reducer, collar, clamps, etc. It shall have UL listed and FM approved.
50Supplying and installing of approved type Rosette Plates (Recessed Type in Two Pieces) for sprinklers below false ceiling area. The Rosette shall be fabricated by MS plate of 2mm thick and the finish shall be powder coated and colour, as directed by the Departmental Officers.
51Supply & installation of Emergency EXIT lights with double halogen lamps wall / ceiling mounted type with battery backup for 120 minutes etc., complete complying with the standard specification and as directed by the departmental officers.
52Supply & installation of glow type wall mounted indicators for fire exit points with battery backup for 120 minutes etc., complete complying with the standard specification and as directed by the departmental officers.
53Supply and erection of Double Leaves Fire Rated Door with Frame having the dimension of 1800mm x 1400mm with following specification:a. Door Frame 1.6mm: Galvanized 120 GSM branded make JSW b. Door Leaf 1mm: Galvanized 120 GSM branded make JSW c. Shutter Thickness: 46mm d. Honeycomb: In-fill e. Glue Macroplast UR-7221 f. Door Hinges: 4 x 3 x 3mm, Double Ball: Ball bearing Butt Hinges Grade SS 304 - Finish SS g. Door Closer with Standard Arm Finish: Silver h. Lock Set: Dead Lock with both side key i. Door Orientation: To be confirmed by client j. Mounting of door: Brick wall mounted k. Powder Coating: Powder coated in standard RAL paint colour of PO Red (60 to 90) Microns l. Single Point Panic Bar (2 Horizontal) m. Dead Lock with both side key n. Vision Panel 200 x 300mm 2 Hrs. Fire Glass with Frame o. Rated Glass with Frame p. Anchor Bolt with EndcapsThe above assembly mounted on concrete or brick wall including the cost of cutting, chipping, concrete packing, pastering, scaffolding all other conveyence as per standard methods and as directed by the Departmental Officers.
54GST 18% Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58487790
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 26-11-2026
Authority
Authority Name Public Works Department
Work Description Tender for Providing Fire Fighting Arrangements To 50 Bedded Critical Care Block Building In Government Hospital At Mettupalayam In Coimbatore District
Basic Detail
Tender No 22BCMCBE03112026(1)
Bidding Type Tender
Location
City Coimbatore
State Tamil Nadu
Key Dates
Publish Date 11 Nov 2026
Submission Date 26 Nov 2026
Open Date 26 Nov 2026
Finance
Tender Value Ref. Documents
Tender Fee Ref. Documents
EMD 62000
Exemption Not Available
Document List
07f4f1e7-29ba-4d65-94be-6655b3641c50.html
BOQ_867263.xls
GenConditionGHMTP1.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 11, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 26, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 10 days
Nov 26, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 10 days

Tender Documents

Download All (ZIP) ↓
html

07f4f1e7-29ba-4d65-94be-6655b3641c50.html

xls

BOQ_867263.xls

pdf

GenConditionGHMTP1.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender