Tender For Biennial Contract For O & M Of Sewage Treatment Plant, Pump House And miscellaneous Cosmetic Maintenance Works At Zirconium Complex Plant & Township, Pazhayakayal, Tuticorin -628152.
Tender Value
1 Crore
Estimated cost
Bid Submission
27 Nov 2026
4 days left
EMD
2 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Tuticorin → Tamil Nadu
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Biennial Contract For O & M Of Sewage Treatment Plant, Pump House And miscellaneous Cosmetic Maintenance Works At Zirconium Complex Plant & Township, Pazhayakayal, Tuticorin -628152.
BOQ
| Sl. No. | Item Description |
| 1 | ZC Plant STP-O&M |
| 2 | Operation & Maintenance of Sewage Treatment Plant at ZC plant including all personnel, consumables, accessories, material, tools & tackles necessary for smooth operation of the plant including up keeping of the rooms, STP area and the surroundings neat and clean, maintenance of the Greenary developed in and around STP in ZC Plant, providing fertilizer as required, trimming of Trees , lawn & Hedges, Mulching, Water Ponding for trees as per specification & as directed by the Engineer In Charge.Note: 1. BOD & COD of the Treated water report have to be submitted every month. 2. Logging of all the day to day activity Carried out STP Plant.3. Recording of all the basic parameter of Treated Water quality ( Day to Day ) like PH, TDS, Conductivity, DO, Turbidity &Etc) 4. Maintaining the required documentation.5. Minimum one skilled operater and one helper (unskilled) shall be deployed for the work each day. |
| 3 | Supply and replacement of Fine Pore Diffuser (T type) of size 63 mm Dia and 600 mm long in various tank at STP . The Rate inclusive of Material, labour cost, tools & tackles etc.as per specification and as per the direction of Engineer in Charge.Note : Item shall be operated at the time of failure of Existing diffuser. |
| 4 | Supply and Replacement of .157 m3 of filter media of various sizes in layer in the Pressure sand filter (PSF) including the Cost of Sand, removal of existing filter media, cleaning the tank, placing the filter in specified layer, tool & tackles etc. as per the specification and as directed by the Engineer in Charge.Dia of PSF is 0.4 M and Height of PSF is 1.25 M Note: Item Shall be operated once in Six month. Payment shall be made on production of Documentary evidence for the purchase of the filter media. Rate Quoted by you shall be inclusive of Disposal of waste. |
| 5 | Supply and Replacement of .157 m3 of sand of various sizes as a layer in Activated Carbon filter (ACF). The Rate includes the Cost of Sand, Cost of Activated carbon , Cost of Cleaning the Tank, Cost of Restoration of the New Sand, Activated carbon , tool & tackles and etc., as shown in the Drawing, as per specification and direction of the Engineer in Charge.Dia of ACF is 0.4 M and Height of PSF is 1.25 M Note: Item Shall be operated once in Six month. Payment shall be made on production of Documentary evidence for the same. Rate Quoted by you shall be inclusive of Disposal of waste. |
| 6 | Supply and Recharging of Oil lubricant of SS 320 Grade oil in Air blower Pump at STP . The Rate inclusive of Oil, Cleaning of the Pump, inspection of Oil seal, Gland packing, Checking of IR Value of the Pump & Etc as per specification and direction of the Engineer in Charge.Note : Item Shall be operated in every Month. Quantity of oil to be changed is 0.5 litre/month for 2 nos. of blowers. Payment shall be made on production of Documentary evidence for the same. |
| 7 | Supply, replacement, installation & Commisioning of sewage transfer pump as per the specification given below as directed by the Engineer in charge. Type : Submersible Non clog , Capacity: Minimum 2 Cum/hr, Head: Minimum 10 m, Model No. CRI - CSL-CS07-CT ( for reference), Speed: Minimum 2500 RPM , MOC: CI , Rating : Minimum 1HP , Phase & Frequency: 3 Phase, 50Hz. |
| 8 | Supply, replacement, installation & Commisioning of Air blower including suitable electrical motor as per the specification given below as directed by the Engineer in charge. Type : Twin Lobe Rotary Capacity: Minimum 30 Cum/hr Pressure: Minimum 0.40 kg/sq.cm Make : Kay – 42 AC ( For reference) Blower, Electrical Motor ( Suitable), Speed: Minimum 1000 RPM, MOC: CI, Rating : 2HP Phase & Frequency: 3 Phase, 440V, 50Hz |
| 9 | Supply, replacement, installation & Commisioning of return sludge pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Non Clog, Capacity: Minimum 0.5 Cum/hr , Head : Minimum 10 m, Speed : Minimum 2700 RPM, Model: CRI SMB 140 ( for reference) , MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 1HP, Phase & Frequency: 3 Phase, 50Hz |
| 10 | Supply, replacement, installation & Commisioning of dosing pump including as per the specification given below as directed by the Engineer in charge.Type: Electronic metering pump, Capacity: Minimum 0-6 l/hr , Head : Minimum 10 m, Speed : Minimum 2700 RPM, Model: CRI or Kirloskar or any other equivalent make , MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 0.25HP, Phase & Frequency: 3 Phase, 50Hz |
| 11 | Supply, replacement, installation & Commisioning of filter feed pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Mononbloc, Capacity: Minimum 0.75 Cum/hr , Head : Minimum 25 m, Speed : Minimum 1400 RPM, Model: CRI ACM 2 ( for reference) or Kirloskar or any other equivalent make , MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 2HP, Phase & Frequency: 3 Phase, 50Hz |
| 12 | Supply, replacement, installation & Commisioning of Backwash pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Mononbloc, Capacity: Minimum 1.5 Cum/hr , Head : Minimum 25 m, Speed : Minimum 2900 RPM, Model: CRI ACM 2 ( for reference) or Kirloskar or any other equivalent make , MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 2HP, Phase & Frequency: 3 Phase, 50Hz |
| 13 | Supply, replacement, installation & Commisioning of Treated water transfer pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Mononbloc, Capacity: Minimum 1.5 Cum/hr , Head : Minimum 25 m, Speed : Minimum 2900 RPM, Model: CRI ACM 2 ( for reference) or Kirloskar or any other equivalent make , MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 2HP, Phase & Frequency: 3 Phase, 50Hz |
| 14 | ZC Township STP- O & M |
| 15 | Operation & Maintenance of Sewage Treatment Plant at ZC Township including all personnel, consumables, accessories, tools & tackles necessary for smooth operation of the plant including up keeping of the rooms, STP area and the surroundings neat and clean in shifts as per specification & as directed by the Engineer In Charge.Note: 1. BOD & COD of the Treated water report have to be submitted every month. 2. Logging of all the day to day activity Carried out STP Plant.3. Recording of all the basic parameter of Treated Water quality ( Day to Day ) like PH, TDS, Conductivity, DO, Turbidity &Etc) 4. Maintaining the required documentation.5. Minimum one skilled operater shall be deployed for the work in one shift. |
| 16 | Operation & Maintenance of Drinking water Pump house and Intermediate Pump house of ZC Township site including all personnel, consumables, accessories, tools & tackles necessary for smooth operation of the pump including keeping of Pump house rooms, Electrical panel, up keeping the surroundings neat and clean, Monitoring the water level in individual water tank at regular interval, log maintenance, working in shifts as per specification & direction of the Engineer In ChargeNote: Minimum one skilled operater shall be deployed for the work in one shift. The Operator should be skilled in Electrical & Mechanical to attend basic problem at Pump house. |
| 17 | Supply and replacement of Fine Pore Diffuser (T type) of size 90mm Dia and 1 m long in various tank at STP . The Rate inclusive of Material, labour cost, tools & tackles etc.as per specification and as per the direction of Engineer in Charge.Note : Item shall be operated at the time of failure of Existing diffuser. |
| 18 | Supply and Replacement of 1.2 m3 of filter media of various sizes in layer in the Pressure sand filter (PSF) including the Cost of Sand, removal of existing filter media, cleaning the tank, placing the filter in specified layer, tool & tackles etc. as per the specification and as directed by the Engineer in Charge.Dia of PSF is 1.0 M and Height of PSF is 1.5 M Note: Item Shall be operated once in 06 Months.Payment shall be made on production of Documentary evidence for the purchase of the filter media. Rate Quoted by you shall be inclusive of Disposal of waste. |
| 19 | Supply and Replacement of 1.7 m3 of sand of various sizes as a layer in Activated Carbon filter (ACF). The Rate includes the Cost of Sand, Cost of Activated carbon , Cost of Cleaning the Tank, Cost of Restoration of the New Sand, Activated carbon , tool & tackles and etc., as shown in the Drawing, as per specification and direction of the Engineer in Charge.Dia of ACF is 1.2 M and Height of PSF is 1.5 M Note: Item Shall be operated as and when requirement basis.Payment shall be made on production of Documentary evidence for the same. Rate Quoted by you shall be inclusive of Disposal of waste. |
| 20 | Supply and Recharging of Oil lubricant of SS 320 Grade oil in Air blower Pump at STP . The Rate inclusive of Oil, Cleaning of the Pump, inspection of Oil seal, Gland packing, Checking of IR Value of the Pump & Etc as per specification and direction of the Engineer in Charge.Note : Item Shall be operated in every Month. Quantity of oil to be changed is 4 litre/month for 4 nos. of blowers. Payment shall be made on production of Documentary evidence for the same. |
| 21 | Supply , installation, replacement & Commisioning of sewage transfer pump as per the specification given below as directed by the Engineer in charge. Type : Submersible Non clog , Capacity: Minimum 12.5 Cum/hr, Head: Minimum 12 m, Model No. CRI - CSL-CS07-CT ( for reference) or Kirloskar or any other equivalent make, Speed: Minimum 2500 RPM , MOC: CI , Rating : Minimum 2HP , Phase & Frequency: 3 Phase, 50Hz., |
| 22 | Supply , installation, replacement & Commisioning of Air blower including suitable electrical motor as per the specification given below as directed by the Engineer in charge. Type : Twin Lobe Rotary Capacity: Minimum 120 Cum/hr Pressure: Minimum 0.40 kg/sq.cm Make : Kay – 42 AC ( For reference) or Kirloskar or any other equivalent make, Blower, Electrical Motor ( Suitable), Speed: Minimum 1000 RPM, MOC: CI, Rating : 5HP Phase & Frequency: 3 Phase, 440V, 50Hz |
| 23 | Supply , installation, replacement & Commisioning of return sludge pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Non Clog, Capacity: Minimum 9.5 Cum/hr , Head : Minimum 12 m, Speed : Minimum 2700 RPM, Model: CRI SMB 140 ( for reference) or Kirloskar or any other equivalent make, MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 2HP, Phase & Frequency: 3 Phase, 50Hz |
| 24 | Supply , installation, replacement & Commisioning of Filter feed pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Non Clog, Capacity: Minimum 9.5 Cum/hr , Head : Minimum 12 m, Speed : Minimum 2700 RPM, Model: CRI SMB 140 ( for reference) or Kirloskar or any other equivalent make, MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 2HP, Phase & Frequency: 3 Phase, 50Hz |
| 25 | Supply, installation, replacement & Commisioning of UASBR feed pump including as per the specification given below as directed by the Engineer in charge.Type: Horizontal Centrifugal Non Clog, Capacity: Minimum 57 Cum/hr , Head : Minimum 18 m, Speed : Minimum 2700 RPM, Model: CRI or Kirloskar or any other equivalent make, MOC : CI Make, Suction Size: Minimum 40 mm ( Suitable at site), Delivery Size: Minimum 40 mm ( Suitable at site) , Rating 3 HP, Phase & Frequency: 3 Phase, 50Hz |
| 26 | Charges for conducting laboratory Analysis of raw sewage & treated water (collected from Plant STP and township STP) at STP lab and submitting the Test result in every month. The Rate quoted by you shall be inclusive of Chemical required for doing Lab analysis, Man power, Tools & tackles required and Etc as per specification and direction of the Engineer in Charge.Note : Lab analysis report shall be submitted at the end of the each Month.Payment shall be made on production of Documentary evidence on purchase of chemical for the same. |
| 27 | BOD Value |
| 28 | COD Value |
| 29 | Miscellaneous Cosmetic Maintenance |
| 30 | Charges for terrace cleaning of various buildings at ZC Plant & township. Cost including manpower, material, Tools & tackles etc., as per specification, and as directed by the Engineer in charge. Note : Item shall be operated at the 6 months period of intervals. |
| 31 | Charges for De chocking of Man hole chambers at ZC Plant & township of various sizes including manpower , material, Tools & tackles etc as per specification, and as directed by the Engineer in charge. Note : Item shall be operated at the Time of Chocking of Sewer line. |
| 32 | Cleaning of under ground sump RCC, Over Head R.C.C. Tank, STP various tank of size varying from 10 KL to 250 KL including disposal of slit and rubbish, all as per direction of Engineer-in-Charge. The cleaning shall consist following operations:-(i)T ank shall be emptied of water by pumping & bottom shall be cleaned of silt and other deposits.(ii) Entire surface area of the sump shall then scrubbed thoroughly with wire brush etc. and pressure washed with water.(iii) Chlorination of RCC internal surface using bleaching powder as applicable (iv) The treated surface shall be dried using air jetting and all loose particles shall be removal from the surface. as per direction of Engineer-in-Charge. |
| 33 | Drain cleaning mechanical/manual means cleaning, desilting, removing weeds, algae growth silt, slushy soil, mud, earth, debris, waste chemicals, Elephant grass of any height etc., accumulated in the various drains of the complex including all labour, tools, tackles, T & P, machinery, including removing and refixing of top RCC precast cover or steel grating (if available), if required (rate for the hired charges for hydra to be paid in respective line items) etc., complete as directed by EIC. Carting away the same with lead upto 5KM within or outside the ZC complex as directed by EIC, including all labour, machineries, T & P etc., complete. Measurement shall be paid on running meter basis of the completed job. Note: For drains having cross section area upto 1 sqm |
| 34 | Cleaning of terrace/loft water storage tank (inside surface area) upto 2000 litre capacity at all heights with coconut brushes, duster etc., removal of silt, rubbish from the tank and cleaning the tank with fresh water disinfecting with bleaching powder @ 0.5gm per litre capacity of tank including marking the date of cleaning on the side of tank body with the help of stencil and paint and disposing of malba all complete as per direction of Engineer-in-Charge. (The old date already written on tank should be removed with paint remover or black paint and if date is not written with the stencil or old date is not removed deduction will be made @ Rs. 0.10 per litre) (if during cleaning any GI fittings or ball cock is damaged that is to be repaired by contractor at his own cost and nothing extra will be paid on this account) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 4 daysNov 28, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender