Defence Statutory Bodies & Commissions/Committees Closing in 9 days TDR #58469431

Tender For Special Repairs To (P-1) Ships Armoury Building At installation Kardip, Kamorta Under Ge 866 Ews. 8872/E8

Issued by Statutory Bodies & Commissions/Committees · Nicobars, Andaman And Nicobar Islands
Tender Value
30 Lakhs
Estimated cost
Bid Submission
01 Dec 2026
9 days left
EMD
60000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Nicobars → Andaman And Nicobar Islands
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Special Repairs To (P-1) Ships Armoury Building At installation Kardip, Kamorta Under Ge 866 Ews. 8872/E8

BOQ

Name of Work:- SPECIAL REPAIRS TO (P-1) SHIPS ARMOURY BUILDING AT INS KARDIP, KAMORTA UNDER GE 866 EWS. 8872/E8
Sl. No. Item Description
1Taking down cement plastering on concrete or Brick works surface racking out joints, hacking for key , scrubbing down with water, removing rubbish/debris etc complete all as specified and as directed.
2Material and labour for 15 mm thick rendering on brick/concrete surfaces in two layers in CM 1:4, finishing coat of 5mm thick, finished even and smooth without using extra cement complete all as specified and as directed.
3Material and labour for rendering 15 mm on fair faces of brick or concrete surfaces in CM 1:6, finished even and smooth without using extra cement complete all as specified and directed.
4Material and Labour for rendering 5 mm thick in cement mortar 1: 3 on fair faces of concrete surfaces of ceiling finished even and smooth with out using extra cement, complete all as specified.
5Material and labour for applying Two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/ 10 sqm over new surfaces complete all as specified and directed.
6M&L for preperation of old/new plastered surfaces on brick/concrete of walls etc and applying Two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 1.43 litre/ 10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/ 10 sqm over new surfaces complete all as specified and directed.
7Material and labour for preparation of of new plastered/concrete surfaces of walls and applying two coats of acrylic distemper of approved shade/tint over a coat of primer, over 1mm thick wall care putty finish to achieve uniform smooth surface of wall all as specified and as directed.
8Material and Labour for preparing old distemper and painted surfaces of wall including washing rubbing down and brooming down smoke soot mould mass and applying one coats of Oil emulsion distemper old surface complete all as specified and directed by Engr-in-charge.
9Material and labour for preparation of of new plastered/concrete surfaces of ceiling and applying two coats of acrylic distemper of approved shade/tint over a coat of primer, over surface of wall all as specified and as directed.
10Material and Labour for preparing old distemper and painted surfaces of ceiling including washing rubbing down and brooming down smoke soot mould mass and applying one coats of Oil emulsion distemper old surface complete all as specified and directed by Engr-in-charge.
11Taking down chowkats or frame with shutter (without taking out shutter from the frame) not exceeding 1.50 Sqm each as doors, windows & ventilators etc. and removal from site complete all as specified and directed by Engr-in-charge.
12Taking down Chowkats or frames exceeding 1.5 Sq. M but not exceeding 4 Sq. M each (without taking off shutters from the frame) complete all as specified and directed.
13Taking down shutter of any description, exceeding. 1 Sqm and not exceeding 2 sqm each and removing from site all as specified.
14Supply and fixing 2nd class hardwood factory made plain framed panelled shutters 35mm thick with lock rail and with panels of 12mm thick commercial veneered particle board veneers on both side or with 9mm thick BWP commercial ply, size of members of shutters as specified in IS 1003-Part-I, kiln seasoned and chemically pressure treated complete all as specified and as directed.
15Supply and Fix 2nd class HW glazed and skeleton shutters 35mm thk, open rebated and prepared to receive glass, gauze, etc. (without sash bars), edges of framing plain, chamfered or rounded. fitted with cut and mitred beads for securing glass, etc.; sizes of me-mbers of shutters as specified in SSR Part I, Section 8, clause 8.24 (a); supplied and fitted to chowkats complete all as specified and directed.
16Supply and fix 4.00 mm thick sheet glass, ordinary quality and glazing with oil putty in square n.exc 0.5 sqm in each pane, complete all as specified and as directed.
17Supply and fix 4.00 mm thick Figured glass, pin head type and glazing with oil putty in square n.exc 0.5 sqm in each pane, complete all as specified and as directed.
18S&F aluminium alloy wire cloth 0.45mm nominal dia of wire and average width of operature 1.40mm and fixed with aluminium wire staples
19Supply and fixing Solid PVC Door Frame of size 50 mm x47mm made out of 5 mm plain colour PVC sheet reinforced with M.S. Square tube, supporting & fixing in opening as per specification & drawing complete all as specified and directed.
20Supply and fix factory made solid panel PVC door shutter 30 mm thick (style) consisting of frame made out of mild steel tubes for top & bottom rails, mild steel frame shall be covered with heat moulded plian colour PVC 'C' channel having a PVC sheet strip of 20 mm width struck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail & bottom rail on either side & as gap insert for top rail & bottom rail, panelling of plain colour PVC sheet to be fitted in the mild steel frame welded/sealed to the stiles & rails with suitable PVC sheet beading, and jointed together with solvent cement supplying and fixing in the frame at site as per specification & drawing of SSR Part II.
21Supply and fix in 100mm size Butt hinges, Stainless steel with Stainless stee hinge pin, type B-21complete all as specified and directed.
22Supply and fix in 75mm size Butt hinges, Stainless steel with Stainless stee hinge pin, type B-21complete all as specified and directed.
23Supply and fix extruded aluminium alloy handles, fabricated type, anodised 150mm size complete all as specified and as directed
24Supply and fix in repairs extruded aluminium alloy handles, fabricated type, anodised 100mm size complete all as specified and as directed
25Supply and Fix 150mm long aluminium anodised barrel tower bolt all as specified and as directed by Eng-in-charge.
26Supply and Fix 100mm long aluminium anodised barrel tower bolt all as specified and as directed by Eng-in-charge.
27Supply and fixing aluminium alloy,anodised, sliding door bolt of length 250mm with hasp, staple (bolt type) & fixing clips of sheet, cast or extruded sections & fixing bolts & sliding bolts of extruded section or cast-aluminium alloy complete all specified and as directed.
28Dismantling of floor, hearth or wall tiling including cement mortar bedding but not backing) removing serviceable tiles to store and rubbish of the premises all as specified.
29Material and Labour for non-skid coloured ceramic tiles 7 to 8mm thick (square/ rectangular) area of each tiles exceeding 0.11 Sqm but not exceeding 0.18 Sqm in floors etc, set and jointed in cement mortar and pointed in white of coloured cement to match over and including 15mm thick screed bed in CM 1:6 complete all as specified and as directed.NOTE: No extra cost shall be allowed for removing and re-fixing and necessary cutting of door etc if any required during execution of work.
30Material and Labour for glazed ceramic coloured tiles in vertical surface 450x300x7-8mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the tiles over and including 10mm thick backing coat in CM 1:4 cmplete all as specified.
31Demolition of cement concrete in ground floors and pavings not exceeding 15 cm thickness (below or above ground level) complete all as specified and as directed.
32Material and Labour for 75mm thick Plain Cement Concrete 1:3:6 type C2 using 40 mm graded stone aggregate as in plinth protection, floors, pavings and hardstanding etc, finished even smooth without using extra cement etc including necessary forwork, complete all as specified and as directed.
33Material and labour for 40mm thick plain cement concrete 1:2:4 type B0 using 12.5 mm graded stone aggregate as in as in leveling course, flooring and finishing cement concrete surface even and smooth Without using extra cement, including use of form work as necessary complete all as specified and as directed.
34Supply and fix glass dividing strips 3mm thick and 38mm wide all as specified and as directed.
35Material and labour for plain cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate as in foundation filling and mass concrete including necessary form work complete all as specified and as directed.
36Material and labour for chequered cement concrete tiles 30cm x 30cm x 25mm with grey cement and pigment, hydraulically machine pressed, set, jointed and pointed in neat cement slurry to match colour of tiles, over and including 15mm thick screed in CM 1:6 in floors complete all as specified and as directed.
37Demolition of reinforced cement concrete of any description ad in any position not otherwise specifically provided for (reinforcement cut as required to facilitate demolition) complete all as specified and directed.
38Use and waste of formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings, and similar work, not exceeding 200 mm thick etc, fair finshed surfaces of concrete (Horizontal or sloping) complete all as specified and as directed.
39Material and Labour for TMT bar 10mm dia and over, cut to length, bent to shape required, including cranking,bending spirally for hooping ,for columns,hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
40Material and labour for reinforced cement concrete design mix M-30 using 20 mm graded granite stone aggregate as in Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and as directed. Note : Reinforcement and form work shall be measured and paid separately.
41Supply and Fix in repairs vitreous china wash down water closet Pedastal pattern white (excluding flushing cistren ) including trap set, seat cover and fixing of flushing cistern, brackets, flushing pipe etc, etc. with 'P' or 'S' trap, making good the floor to match with existing floor complete all as specified and as directed.
42Supply and fix in repair 10 Ltr capacity PVC valveless, syphonic action type, flushing cistern low level, white, with inlet ball valve, float and handle including brackets, flushing pipe, 450mm long PVC Connection and connection to trap, and to flushing and making good to floor complete all as specified .
43Supply and fixing in repairs vitreous China wash hand basin, white (flat back or angle back type or counter top) of size 630X450mm including 32mm brass chromium plated waste fitting, a pair of cast iron bracket duly painted including cutting and pinning in ends making good disturbed surfaces in CM 1:3 excluding pillar tap, chain , plug and porcelain stopper, and brackets etc all as specified and as directed.
44Supply and fix in repairs waste coupling of PTMT 32 mm size (half or full threaded) suitable for urinals/ WHB/Sink etc (Minimum weight 32 mm - 45 gms) all as specified and as directed.
45Supply and fix in repairs PVC connections 15mm size with PTMT nuts of length 600mm complete all as specified and directed.
46Supply and fix in repair 15mm dia pillar tap, cast copper alloy, chromium plated, fancy type, with capstan head screwed down high pressure with or without lettered hot or cold with long screw shank and fly nutt screw for iron pipe Make: CERA /Parryware/Hindware
47Supply and fix in repairs stop valves/angle cock, 15mm bore, fancy type, chromium plated, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and directed.
48Supply and fix in repairs 15mm dia bib taps cast copper alloy fancy type chromium plated with crutch or butterfly handle screwed down , screwed for iron pipe or union complete all as specified and directed.
49Supply and fixing in repairs Towel rails tubular brass chromium plated 20 mm dia 'D' type 60 cm long between flanges complete all as specified and directed.
50Supply and fixing in repairs 6 mm thick bevelled edge looking mirror of size 600 x 450 mm mounted on 6 mm thick AC Building board or commercial plywood/hard board backing and fixed to wooden plugs with CP Screws and cup washers all as specified and as directed.
51Taking up or down steel tubing /CPVC pipe 15 mm bore including connections, cleaning for refixing or removal to store all as directed.
52Supply and fixing galvanised steel water tubing medium grade 15 mm bore including all necessary fittings such as bends, L bows, short piece connections, backnuts, caps plugs, unions couplings, flanges, sockets etc, fixed to wall/floor/ceiling including necessary cutting/chauging in walls made of brick/concrete surface complete all as specified and as directed.
53S&F in repair PVC (SWR) pipes 110 mm dia. single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specified and as directed.
54Supply and fix in repairs PVC (SWR) bends any radius 110 mm bore complete all as specified and directed.
55S&F PVC (SWR) pipes 75 mm dia. single socketed, in any length with rubber ring joints, laid in trenches or floors complete all as specified and as directed.
56S&F PVC (SWR) bend 75 mm dia with access door complete all as specified and as directed.
57Dismantling wrought iron or mild steel work of any description not otherwise specifically provided for complete all as specified and as directed.
58Supply and fix Rolled mild steel Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete conforming to Fe 290 (Gde-E-165) complete all as specified and directed.
59Supply and fix Rolled mild steel Framed work such as grills, gratings, etc.. with ends of barsshouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors;ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and directed.
60M&L for preparation of new or previously untreated steel surfaces of any description not otherwise described over 10cm in width or girth and applying two coats of synthetic enamel paint (ordinary tint) over a coat of red oxide primer complete all as specified and as directed
61M&L for water proofing treatment to RCC roof slab including parapet comprising with the following course of treatment/ specifications from bottom to top:- (a) Applying bituminous primer @ 0.40 ltrs per sqm over plastered surfaces of roof including parapet surfaces.(b) One layer of APP based polymeric membranes of approved manufacturers, 3 mm thick, weight not less than 3.6 kg/sqm, reinforced with non woolen polyester fabric or weight not less than 150 gms/sqm. Polymeric membrane shall be taken to a height of 60 cm (minimum) and then inserted inside the groove of parapet walls and shall be finished by a membrane flashing.Note: (i) Laying of APP based membranes shall be done by torch on method or as per manufacturer's instructions.(ii) A minimum overlap of 100 mm and 75 mm should be made in the end sides of polymeric membranes respectively and sealed all overlaps and joints as manufacturer's instructions.(c) Applying two coats of Aluminium paint on top of APP membranes.
62Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, alongwith UNSV fitting/fixtures such as switches, ceiling roses, pendants, regulators, sockets, electrical fittings, light fittings and making good disturbed surface of walls, ceiling floor to match with the existing surface complete all as specified and as directed.
63M&L point wiring complete with 1.5 Sqm sincle core PVC insulated unsheathed FRLS cable 1100 volts grade (ISI marked) with multi stranded copper conductor drawn through and including non-metallic rigid PVC medium grade conduit and conduit accessories (ISI) marked concealed in wall/fixed to roof, ceiling etc and incl provn of 1.5 sqmm PVC insulated multistranded unsheathed copper conductor cable FRLS (ISI marked) as earth continuity conductor, fabricated sunken terminal box made out of 1.60 mm thick sheet steel duly painted concealed in walls, with 3mm thick bakelite/PVC sheet ISI marked top cover with brass/chromium plated screws and cup washers for housing switches, socket outlets, fan regulators etc, all as specified and as directed for the following :- (a)One light point or one light point controlled by one switch
64M&L for point wiring with two single core PVC insulated, unsheathed, FRLS multistranded unsheathed copper conductor cable of size 2.5 sqmm and one single core PVC insulated unsheathed FRLS stranded copper conductor of size 2.5 sqmm green in colour as earth lead through and including PVC casing & caping with all fittings & accessories ISI marked including provn of MS sunken boxes of appropriate size & thickness fixed flush to wall for 15/16 A switch-socket point on independent board complete.
65Supply and Fixing of Flameproof cum Waterproof LED light fitting of 2x16W, CMRI certified recommended for gas/vapor group of IIA & IIIB, Zone 1 & 2 and IP65 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size.complete all as specified and as directed.Make:Bajaj/ L&T/Crompton Greaves/Havells
66Supply and fix Flame proof exhaust fan of size 300 mm sweep with louvers,having air discharge capacity of 1120CFM with metal body AC 230 V, 50 Hz, 1440 RPM and connecting to ceiling rose terminals with 23/.0076 flexible cable complete all specified and directed. Make:Havells/ Usha/Crompton Greaves.
67Supply and fix Switch flame proof, rotary type with termination box in LM6,16 A, single pole, 250 V complete all specified and as directed.
68Supply and fix Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16A, 250V, 2P+earth complete all as specified and as directed.
69Material and labour for Sub main wiring using two runs of single core PVC insulated cable (FRLS) 4 sqmm copper conductor multi stranded and one run of 4 sqmm copper conductor insulated cable (FRLS)using as earth wire drawn through and including suitable size casing capping including taking down old aluminium/Copper Sub main wirng, complete all as specified and directed. Note- 3 run of 4 sq mm PVC copper wire and One run of PVC casing caping shall be measured and paid as one unit.
70Supply & fixing in repairs Distribution board (DB) made out of sheet metal enclosure (CRCA sheet), dust and vermin proof, SPN 12 way with 200 Amps rated copper bus bar double door protection, neutral bar,earth bar, single pole and neutral 240 volts, MCBs used as incommer flush to wall complete all as specified and as directed.
71Supply and fix MCB SP 6-32 amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of single pole in the MCB DB,IP 20 transparent lebel holder fully insulated safety shutters suitable for cable up to 35 Sqmm cross sectional area complete including suitable size copper Lugs complete all as specified and directed. Make: Indo Asian/ L&T/Crompton Greaves/Havells
72Supply & fixing MCB DP 32 Amps 240V 10KA 'C' curve miniature circuit breaker (MCB) in the DB complete with connection testing and commissioning complete all as specified and directed. Make: Indo Asian/ L&T/Crompton Greaves/Havells
73M&L for earthing complete with Galvanised steel earth plate electrode of size 600mmx600mmx6mm, buried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of earth plate not less than 1.5 Mtrs deep below normal ground level, connected to GI earth wire of size 4 mm by means of brazing and connected to earthing test point / distribution board/equipments or any other indicated situation by means of brazing all as shown in electrical plate No.3 of SSR Part I (2009) and testing on completion including necessary excavation and earth work in any type of soil, returning filling, removing of soil. GI medium grade pipe 20 mm dia 1.5 mtr long with funnel wire mesh as watering pipe, and GI medium GI medium grade pipe 15mm dia as earth lead protection pipe.Earth pit chamber made of PCC 1:2:4 type B1 using 20mm graded stone aggregate including 40mm thick chamber cover made of 1:2:4 type B1 using 20mm graded stone aggregate and reinforced with 8mm dia TMT bars at 100 c/c on both ways precast chamber cover with lifting handle 16mm dia round bars including charcoal and common salt in alternate layer of 15cm thick covering all faces of earth electrode plate complete all as specified and directed.(Note :- (i) The rates quoted for the complete earthing shall deemed to include the cost of GI wire 4.00 mm dia and GI medium grade protection pipe up to 7.5 Mtrs.(ii) GI earth wire and GI medium grade protection pipe beyond 7.5 Mtrs length shall be measured and paid separately.
74Taking down existing unserviceable water tank after disconnecting water supply line and Supply and fix Rotational moulded Polyetheylene Water Storage Tank 1000 Ltr capacity Triple Layer (Cylinderical verticle with closed top) including 20mm dia GI Medium Grade 450mm long overflow and wash out pipe each with all required fittings, Checknut, Stopper etc complete hoisted and fixed in position, including all incoming and outgoing connection of GI pipe complete and including 25mm PTMT Ball valves high pressure wiith epoxy coated aluminium rod and high density plastic ball screwed for iron pipe complete for 20mm dia pipe fixed on roof top complete all as specified and directed.
75M&L for Cutting existing CI/GI/DI water supply line with the help of electric cutting tools or manually, reducing to required length before laying and blockage removal, cleaning of particular joint etc and making good after repairing of size 25mm to 50mm including leakage testing all as specified and as directed by Engineer-in-Charge.NOTE: Excavation and earth work shall be measured and paid separately.(ii) DI/GI specials such as Tee / reducer shall be measured and paid separately
76Supply and fixing galvanised steel water tubing medium grade 25 mm bore including all necessary fittings such as bends, L bows, short piece connections, backnuts, caps plugs, unions couplings, flanges, sockets etc, fixed to wall/floor/ceiling including necessary cutting/chauging in walls made of brick/concrete surface complete all as specified and as directed.
77Supply and fix in repair Gun metal (brass body) globe or gate valve of25 mm dia with iron wheel head screwed both ends for jointing iron pipes, non rising, forged brass spindle class-1, ISI marked conforming to IS 778 of 84 for iron pipe of following size complete all as specified and directed:- Make- Zoloto/Bir/Prakash.
78Cutting the existing bituminous road/cement concrete surface to the required width and depth for laying UG cable/pipe and making good the disturbed surface of road/path to even surface to match with existing level of road using cement concrete and removing and depositing the debris to a place complete all as specified and as directed. NOTE: Plain Cement concrete shall be measured and paid separately under relevant items of BOQ.
79Material and Labour for 100mm thick plain cement concrete 1:2:4 type B2 using 40mm graded granite stone aggrgate as floor and other similar type of work, laid in panels and finishing cement concrete surface even and smooth Without using extra cement, complete all as specified and as directed.
80Supply & fixing in repair single pointed Air termination rod, single pointed, aluminium rod 12mm dia and 300mm long complete all as specified & directed
81Supply and fix in repair aluminium strip 25mmx3mm complete with saddles epoxy base and fixing screws for fitting the strip for roof conductors and down conductors above ground complete all as specified and directed.
82M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required but 25x4mm galvanised iron strip including taking up the old unserviceable strip, complete all as directed by Engr-in-charge.
83Supply & Fix in repair 40 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc including clamps, nut, bolt and washers etc after taking out unserviceable pipe complete all as specified and directed.
84Supply & fixing in repair Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified & directed
85Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 25 X 4 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 3 of MES SSR part-I(2009)Note: Unit rate quoted shall be deemed to be included the following (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe 7.5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
86Excavation in trenches in Hard/dense soil not exceeding 1.5 mtr wide and not exceeding 1.5 meter in depth for taking out and laying UG cable and getting out, excavated earth, forming bottom surfaces to required level complete all as specified and directed.
87Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and as directed.
88Removing excavated material (soil) n.exc 50 m and depositing where as directed at a level n.exc 1.5 m above the starting point complete all as specified and as directed.
89Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable conforming to IS:7098 (Pt-I)-1988, heavy duty with stranded aluminium conductor 1100 Volts grade of size 16 Sqmm 4 core with necessary fixing arrangements such as lugs, glands and terminal etc including connecting/testing after taking out unserviceable LT UG cable from trenches/ pole complete all as specified and directed.NOTE: Excavation, earth work shall be measured and paid for separately.
90Supply and laying double wall corrugated pipe (DWC) conforming to IS 19430 Part - I of size 63 mm outer dia and 50 mm inner dia complete all as specified and as directed
91Schedule of Credit (Minus) Rs.28608.00NOTE: Bidder shall insert credit amount of Rs. 28608.00 as rate in Green field under Col-13. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58469431
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 30 Lakhs
LAST DATE 01-12-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repairs To (P-1) Ships Armoury Building At installation Kardip, Kamorta Under Ge 866 Ews. 8872/E8
Basic Detail
Tender No 8872/E8
Bidding Type Tender
Location
City Nicobars
State Andaman And Nicobar Islands
Key Dates
Publish Date 10 Nov 2026
Submission Date 01 Dec 2026
Open Date 08 Dec 2026
Finance
Tender Value 30 Lakhs
Tender Fee 500
EMD 60000
Exemption Available
Document List
8872TenderDocu.pdf
8872Testing.pdf
bc84a375-69f8-4c80-9735-26c266245985.html
BOQ_895365.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 10, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 01, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 9 days
Dec 08, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 16 days

Tender Documents

Download All (ZIP) ↓
pdf

8872TenderDocu.pdf

pdf

8872Testing.pdf

html

bc84a375-69f8-4c80-9735-26c266245985.html

xls

BOQ_895365.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender