Tender For Provision Of Electric Supply For Radar Station Kamorta And Teressa And Provision Of 250 Kva Servo Stabilizer At installation Kardip, Kamorta Under Ge 866 Ews. 8862/E8
Tender Value
24 Lakhs
Estimated cost
Bid Submission
01 Dec 2026
16 days left
EMD
48000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Nicobars → Andaman And Nicobar Islands
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Electric Supply For Radar Station Kamorta And Teressa And Provision Of 250 Kva Servo Stabilizer At installation Kardip, Kamorta Under Ge 866 Ews. 8862/E8
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 meter in depth for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, laying of underground cable etc etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out excavated earth, forming bottom surfaces to required level complete all as specified and as directed. |
| 2 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and as directed. |
| 3 | Removing excavated soil to a distance not exceeding 50 metre away and depositing where as directed at a level not exceeding 1.5m above the starting point, complete all as specified and as directed. |
| 4 | Supply and laying double wall corrugated pipe (DWC) conforming to IS 19430 Part - I of size 90 mm outer dia and 76 mm inner dia complete all as specified and as directed |
| 5 | Supply and laying double wall corrugated pipe (DWC) conforming to IS 19430 Part - I of size 63 mm outer dia and 50 mm inner dia complete all as specified and as directed |
| 6 | Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable conforming to IS:7098 (Pt-I)-1988, heavy duty with stranded aluminium conductor 1100 Volts grade of size 70 Sqmm 3.5 core with necessary fixing arrangements such as lungs, glands and terminal etc including connecting/testing after taking out unserviceable LT UG cable from trenches/ pole complete all as specified and directed.NOTE: Excavation, earth work shall be measured and paid for separately. |
| 7 | Supply, laying or passing through pipe LT, XLPE insulated, galvanised steel strip or wire armoured electric power cable conforming to IS:7098 (Pt-I)-1988, heavy duty with stranded aluminium conductor 1100 Volts grade of size 50 Sqmm 3.5 core with necessary fixing arrangements such as lugs, glands and terminal etc including connecting/testing after taking out unserviceable LT UG cable from trenches/ pole complete all as specified and directed.NOTE: Excavation, earth work shall be measured and paid for separately. |
| 8 | Supply, install, test and commission of LT Control panel board, indoor type, double door, cubical type, padestal mounted, of suitable size, CPRI approved having, IP 65, independent compartment for bus bar, incoming feeder and each out going feeders, dust and vermin proof & lockable, factory made, fabricated out of of 3.15 mm thick CRCA Sheet & MS angle iron section of 50X50X6 mm frame, front operated with locking arrangements suitable for 3 Phase 415 volts 50 Hz, AC supply, bus bar chamber with Horizontal aluminium bus bar of 200.Amp rating for 3 phase and neutral 4 wire system duly insulated with heat shrinkable type sleeves as per colour code, supported on epoxy insulators - 01 Set incl necessary copper cables of suitable size for MCCBs/MCBs / change over swicth / inter connections, common earth bus bar of GI Strip 32 x 6 mm at bottom with panel board at two earth terminals, cable glands with independent plates at bottom for each out going and in coming cables in cable alley panel board and painted with powder coating in siemens grey colour and provision for the following incoming and outgoing accessories all as approved and comprising as under : The LT Panel comprising of the following:- |
| 9 | (a) MCCB 125 A,415 Volt, 4 Pole, 25KA with thermal magnetic release- 01 Nos (Incomer)(b) MCCB 100 A,415 Volts, 4Pole, 16 KA- 01 Nos (out Going)(c) MCCB 40 A,415 Volts, 4Pole, 16 KA- 01 Nos (out Going)(d) MCB SPN 40A,C Curve 415 Volts, 10 KA- 02 Nos (out Going)(e) R Y B phase indicating lamp LED type -01 Sets of 03 Nos(f) 3Phase Digital Volt Meters - 01 Nos(g) 3Phase Digital Ammeter -01 Nos (h) Surge Protection device(i) Copper Busbar 200 A with support duly Heat shrinkable PVC Sleeved- 04 nos(j) Blank space for MountingMCCB- 01 No(h) One empty chamber for housing of MCB's in future Please Enable Macros to View BoQ information |
| 10 | (a) MCCB 125 A,415 Volt, 4 Pole, 25KA with thermal magnetic release- 01 Nos (Incomer)(b) MCCB 100 A,415 Volts, 4Pole, 16 KA- 01 Nos (out Going)(c) MCCB 40 A,415 Volts, 4Pole, 16 KA- 01 Nos (out Going)(d) MCB SPN 40A,C Curve 415 Volts, 10 KA- 02 Nos (out Going)(e) R Y B phase indicating lamp LED type -01 Sets of 03 Nos(f) 3Phase Digital Volt Meters - 01 Nos(g) 3Phase Digital Ammeter -01 Nos (h) Surge Protection device(i) Copper Busbar 200 A with support duly Heat shrinkable PVC Sleeved- 04 nos(j) Blank space for MountingMCCB- 01 No(h) One empty chamber for housing of MCB's in future Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 01, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysDec 08, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 23 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender