Tender For Provision Of Dg Set (200 Kva) And Transformer (500 Kva) For New Proposed High Explosives Test Center At Hemrl, Sutharwadi, Pune
Tender Value
72 Lakhs
Estimated cost
Bid Submission
08 Dec 2026
16 days left
EMD
1.33 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Pune → Maharashtra
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provision Of Dg Set (200 Kva) And Transformer (500 Kva) For New Proposed High Explosives Test Center At Hemrl, Sutharwadi, Pune
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, commissioning & testing of silent, Diesel engine driven factory assembled, generating set of capacity 200 KVA, 3 phase, 4 wire, 50 Hz, 1500 RPM complete with Engine and alternator mounted on a common MS fabricated base frame with AVM pads, Acoustic enclosure, relay panel for automatic starting on mains failure safety control and metering equipment mounted on & including common base frame and installed on PCC/RCC foundation as recommended by manufacturer and approved by GE and suitable for ambient conditions at Pune, environmental eco-friendly as per CPCB IV+ norms including the following all as specified and directed.Note: PCC foundation work as per manufacturer instructions, anti-vibration pads and other standard accessories and comprising of the following complete all as specified and directed |
| 2 | Diesel Engine: Multicylinders, Inline arrangement, Gross Engine power (HP) 237 and (KWm) 178, water cooled turbocharged with after cooled, rated output 1500 RPM and overspeed trip 1650 RPM, Engine Is with electric start, compression ignition, stroke cycle designed to run continuously at 1500 RPM conforming to IS 10000/IS 10002, ISO-3046, BS 5514 standards. Diesel engines should comply with CPCB IV+ norms.The Diesel Engine are comprising of following: (1) Radiator with Fan (2) Fuel Injection equipment with Electronic Governor having CRS (Common Rail system) and DG performance class G3 (3) Dry type air cleaner (4) Exhaust silencer type NA, Max allowable backpressure (kPa) 17, Exhaust temperature (Deg C) 550, (5) Lub oil filter (Spin on type), (6) Fuel oil filter (Spin on type), (7) 24V electric starting system, (8) Battery charging alternator, (9) Stop Solenoid, (10) Lube Oil pressure Gauge, (11) Water Temperature Gauge, (12) lube oil temperature Gauge, (13) Battery voltage, (14) Extended life coolant, (15) First fill lube Oil |
| 3 | Alternator: Alternator type 4 Pole, rotating field, automatic voltage regulator and voltage regulation +-1%, suitable for continuous duty operations rated at 1500 RPM, 415V, 0.8PF, 50 Hz, current (3Ph) Amps-278 in SPDP enclosure, Self-Excited & Self-regulated, Brushless, ‘H’ class insulation, temperature rise (Deg C) 125, coupling type Flexible Disc, unbalanced load capability 25% of rated amps, Floor mounted with anti-friction Sealed ball bearing on end. Alternator charging 12V DC/35A, the alternator conforms to IS: 13364 (Part-II) suitable for tropical condition including making cable connection. |
| 4 | Acoustic Enclosure: (a) Specially designed to meet stringent MoEF / CPCB IV+ norms of 75 dBA @ 1 Mtr at 75% Load under free field conditions.(b) The followings are some technical features of Acoustic Enclosure: (1) The Enclosure is modular in construction.(2) Base Frame is made of Sheet metal. (3) Durable industrial locking system is provided on Doors. (4) Door Gaskets are made in high quality EPDM material.(c) Corrosion Resistance: To make the Enclosure weather proof:-(1) All sheet metal parts/components are hot dipped in seven tanks process, Pretreated and Passivated (2) Sheet metal components are with Pretreated and Passivated Base Powder Coated. (3) Base Frame is Epoxy Coated/Powder Coated. (4) Zinc Passivated Hardwares are used to avoid rusting. Acoustic insulation: (1) Sound proofing of the Enclosure is done with Quality Rockwool conforming to IS:8183 Standard. (2) Acoustic foam shall be fire retardant and fire resistant. (3) Attenuators are provided to control sound at entry and exit of container. (4) Specially designed Residential Silencer is provided.(d) Ventilation And Air Circulation:Exhaust pipe inside Enclosure is thoroughly insulated by Cladding of Rock wool and Sheet.(e) ELECTRICAL: Neutral Body Earthing points at the sides of enclosure are isolated through Moulded compound.(f) SAFETIES: Emergency Push button to Stop the DG set from outside, Low Fuel oil level, Low Lube oil pressure, Low Coolant Level, High Engine Temperature. The canopies being offered are for output of Noise Level ≤ 75 dbA at a distance of 1-meter average, as per the CPCB IV Norms. |
| 5 | Batteries: 2 Nos. 12V 110Ah batteries with leads for electric starting.Paint: DG set and panel package will be painted with powder coated type paint.STANDARD GENSET CONTROLLER UNIT WITH CONTROL PANEL: -Genset Controller unit with totally enclosed, Steel Construction Control Panelsuitable for indoor floor /wall mounting installation having standard safeties and display parameters.” |
| 6 | AMF PANEL: Supply, install, testing and commissioning of AMF Panel for 200 KVA DG Set factory made, outdoor cubical type as per IE/CPRI rules with IP-54 protection, dust and vermin proof, compartmentalised, made of 3.15 mm thick CRCA sheet, fixed on MS angle iron frame of 50 x 50 x 6 mm thick of required type for supporting double door both sides open type with necessary locking arrangement with sloped roof on top duly painted with two coats of powder coated sense grey paint with seven tank process complete and having separate doors inside for accommodating all incoming/outgoing cables and other relevant standards mounted on and including provision of necessary plinth in PCC 1:3:6, type C1 for foundation and PCC pillars with suitable size of nut, bolts & washers grouted as required at site and as per manufacturer's instructions including provision of the following items complete all as specified and directed.(a) Bus bar with electrolytic copper bus bar (for Mains and DG supply incoming and outgoing) suitable for 450 amps capacity for 3 phase and neutral(TPN) (all connection inside the panel shall be through aluminium strip and the joint interfaces between aluminium strip and copper bus bar shall be made through bimettalic inserts or elctroc tinned faces to prevent galvanic corrision) connected duly supported with FRP insulators including colour code heat shrink insulating sleeves |
| 7 | (b) Three phase 4 Pole, Power contactor, 315 Amps for ON-OFF the DG and mains supply -02 Nos (c) MCCB 315 Amps, 36KA for ON-OFF the DG and mains supply -02 Nos. (d) On Load Change over switch 320 Amps for Bypass AMF Panel in case of Power contactor faulty - 01 No. (e) Automatic Generator controller unit, with total control wiring with necessary relays and control fuses, auxiliary contacts etc - 01 No. (f) Digital type voltmeter panel mounted flush type of size 96 X 96 sq mm three phase class 1.0 within built selector switch complete. Each –02 Nos(g)Digital type Ammeter panel mounted flush type of size 96 X 96 sq mm three phase class 1.0 within built selector switch and suitable CTS complete. Each – 02 Nos. (h) RYB phase indicators LED Type with control fuses -02 setsNOTE: - Drawing of LT Panel board and connections shall be got approved by GE before manufacture of panel board.” |
| 8 | Material and labour for earthing with galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 M deep below ground level with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip 32 x 6 mm by means of nuts, bolts, check nuts, washers of galvanised iron or steel all as shown in electrical plate No. 03 of SSR Part I connected to earthing test point including excavation/ earth work in any type of strata, removal of surplus excavated material, GI pipe for watering and funnel, PCC 1:3:6 type C1 chamber including necessary formwork / mould for fair and even surfaces, precast RCC 1:2:4 type B0 chamber cover slab, GI funnel, with GI watering pipe 20 mm bore med gde, wire mesh, protection pipe 40 mm bore, charcoal and salt, GI pipe light gde for earth lead upto 7.50 m long including testing complete all as specified and directed by Engineer-in-Charge.Note : (i) GI strip beyond 7.5 mtr will be measured and paid seperately. |
| 9 | Earth continuity conductor or main earthing lead fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated situation for loop earthing as required 32x6 mm size galvanised strip. |
| 10 | Material and labour for special factory made solid electrolytic grade Pure Copper Single Pipe earthing, the pipe dia is of 76 mm Pipe, & wall thickness of pipe is 2.0 mm & the cavity is filled with highly conductive, non corrosive material along with supply of Fast Electrode Earth Enhancing Compound 2 Bag of 25 Kgs each. The Earth Enhancing Compound should have Test certification from NABL accredited Lab. It should be tested as per IS 3043/ AHPA guideline’s. The pH value of Compound should be 7.59, Moisture % by mass should be 8.91% & Solubility in 1:1 HCL should be 32.29 %. The Compound should have test certification ELV Test as per protocol IEC 62321/111/54/CDV/ICP-OES for contains of Lead (23.0 ppm), Cadmium (15.0ppm), Mercury (Below Detection Level) & Hexa-chromium(Below Detection Level). The manufacturer of Earthing should be registered under Udyam registration and certified for ISO 9001:2015 including necessary boring in ground of 150/200 mm dia in any type of strata connecting to test point including provision of chamber cover complete all as requiredNote: (i) The earth resistance shall be less than 1 ohms. (ii) Contractor shall improve the desired earthing resistance within the permissible limit without any extra cost. |
| 11 | Supply & fix copper strip of high conductivity and corrosion resistance, ensuring reliability for earthing applications, the strip has a cross-section of 25 mm width and 5 mm thickness, the strip is buried in the ground according to the required depth and alignment, ensuring effective dissipation of fault currents complete all as required |
| 12 | Supply, installation, testing and commissioning of outdoor type, stepdown, copper wound transformer of capacity 500 KVA, 22KV / 0.433KV, BIS Level-II, ONAN cooled, oil immersed, conforming to specification EEL-2 of IS : 1180-2014 with amd. no. 1,2,3 & 4. Formerly EEL-3 (till 30.3.2022), complete with first filling of IS:335, ISI marked, filtered & dehydrated transformer oil and other standard fittings/accessories and offload tap changer complete all as specified and directed by Engineer-in-Charge and comprising fo the following accessories: -(i) HV Bare Bushing (ii) LV Cable Box (without Cable Glands) (iii) Buchholz Relay (having Contacts for Alarm & Trip) (iv) OTI (having Contacts for Alarm & Trip) (v) WTI (having Contacts for Alarm & Trip) (vi) Marshalling Box (having TTB Only) (vii) Lifting Lugs, Top Cover Lugs (viii) Earthing Terminals Please Enable Macros to View BoQ information |
| 13 | Supply, installation, testing and commissioning of outdoor type, stepdown, copper wound transformer of capacity 500 KVA, 22KV / 0.433KV, BIS Level-II, ONAN cooled, oil immersed, conforming to specification EEL-2 of IS : 1180-2014 with amd. no. 1,2,3 & 4. Formerly EEL-3 (till 30.3.2022), complete with first filling of IS:335, ISI marked, filtered & dehydrated transformer oil and other standard fittings/accessories and offload tap changer complete all as specified and directed by Engineer-in-Charge and comprising fo the following accessories: -(i) HV Bare Bushing (ii) LV Cable Box (without Cable Glands) (iii) Buchholz Relay (having Contacts for Alarm & Trip) (iv) OTI (having Contacts for Alarm & Trip) (v) WTI (having Contacts for Alarm & Trip) (vi) Marshalling Box (having TTB Only) (vii) Lifting Lugs, Top Cover Lugs (viii) Earthing Terminals Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 08, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysDec 10, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 18 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender