Tender for Provision Of Standby Ht Cable To Dipas Substation Under Ge (I) R&D Delhi
BOQ
| Sl. No. | Item Description |
| 1 | Supply, laying, testing and commissionnig of HT cables 11KV Grade, XLPE insulated and PVC sheathed, armoured, with multi stranded aluminum conductor, heavy duty conforming to IS - 1554 part-l, including connection to RMU/VCB etc to suit the cable laid in trenches/fixed on walls /drawn through pipes complete of sizes 150 Sqmm 3 core complete all as specified and directed. |
| 2 | Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for indoor/out door termination complete with jointing material cold shrinkable type and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed. |
| 3 | Supply and fixing cable jointing kit for 11 KV (Earthed) grade cable for straight through complete with jointing material heat shrinkable type and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 to 185 sqmm complete all as specified and directed. |
| 4 | Supply and installation of indoor type Ring main unit (RMU) one incoming and two outgoing SF6 filled load break switch (LBS) each of 11 KV, 50 Hz, 630A including foundation with metering system complete all as specified and directed. |
| 5 | Supply and installation of HT 11 KV 3 phase 50 Hz indoor type totally enclosed metal clad switchgear complete with Vacuum Circuit Breaker having rupturing capacity 350 MVA overload and earth fault protection, ammeter, voltmeter and of rating upto 630A complete all as specified and directed. . |
| 6 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for pipe line, etc in soft/ loose soil getting out and levelling of bottom surface to required level complete all as specified and directed. |
| 7 | Excavation in trenches by cutting of road crossing PCC hard standing for taking out/laying of pipe including making good the existing surfaces with same finish to match the original finish complete all as specified and directed. |
| 8 | Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick soft / loose soil all as specified and as directed by Engineer-in-Charge. |
| 9 | Removing excavated material (Soils) from site to a distance not exceeding 50m away and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed by Engineer-in-Charge. |
| 10 | Supplying and laying synthetic rubber insulated mats 3mm thick for voltage upto 33 KV (size 2m x 1m) for electrical purpose as per IS 15652-2006 suitable for electrical shock safety complete all as directed by Engineer-in-charge. |
| 11 | M&L for PCC (1:3:6) type C-1 (using 20mm graded stone aggregates) for repairing of LT pole/ panel foundation etc including filling in road cuts/hard standing etc complete all as specified and directed. |
| 12 | S&F Aluminium Composite Panel (ACP) retro reflective sign board of size 1.5m x 1.1m using retro reflective high intensity prismatic reflective sheeting. The back ground of board is Blue Colour with white border and writing letter, numbers white colour mentioning the HT/LT substation Details, and Single line Schematic diagram of substation. Retro sign board shall be pasted over a 3mm thick ACP sheet The board shall be fixed over Wall including fixing of fastners, nuts, bolts, washer etc complete all as specified and directed. |
| 13 | M&L for excavation by Horizontal Directional Drilling (HDD)/boring method for laying of one 150 sqmm, 3-core, 11 kV XLPE aluminium armoured HT cable across roads, pavements, drains or other obstructions, including route marking, pit excavation at entry and exit points, drilling of pilot hole, reaming to the required diameter, pulling HDPE pipe of size 180mm in duct/ bore of size 200mm and cable, supply and use of drilling fluid/bentonite, dewatering wherever required, protection of existing underground utilities, backfilling of pits, disposal of surplus excavated material, restoration of the site to its original condition, testing of duct for free passage, all labour, machinery, T&P, fuel, consumables, complete in all respects as per specifications and directions of the Engineer-in-Charge. Note: The measurement shall be made in running metres (RM) of completed trenchless boring. |
| 14 | HT Danger Notice plate of 1.6mm thick, mild steel sheet, viterous enamelled white with letters, figures and conventional skull and bones in signal red color and fixed with MS clamp, bolts and nuts of approved size for HT, 25 x 20cm size complete all as specified and directed. |
| 15 | Supplying and fixing cable route marker with 10cm x 10cm x 5mm thick G.I. plate with inscription there on, bolted /welded to 35mm x 35mm x 6mm angle iron, 60cm long and fixing the same in ground as required complete all as specified and directed. |
| 16 | M&L for fabricated MS wall mounted bracket with angle iron, flat/round iron etc cutting, welding and drilling duly painted with two coat of synthetic enamel paint over a coat of red oxide primer and including fitting material such as Anchor, bolts, fastners, etc of HT, XLPE cable complete all as specified and directed. |
| 17 | Supply and fixing of MS steel plain/ chequered plate, 5mm thick or over in thickness for cable duct. Fe-290 (Grade E-165) complete all as specified and directed. |
| 18 | M&L earthing complete with GI earth plate electrode of size 60cm x 60cm x 6.0mm thick buried directly in ground vertically to a depth not less than 2.25m below normal ground level with top edge of earth plate at a depth not less than 1.5m below normal ground level connected to and including earth lead of GI strip 32 x 6mm by means of bolts, nuts and check nuts and washers etc made of GI and connected to Earthing test point and earth dolly all as shown in elect plate No 3 SSR Pt-I including all necessary excavation earth work, PCC chamber, chamber cover with handle PCC (1:2:4) including 40mm diameter protection pipe and 20mm diameter watering pipe and wire mesh funnel etc complete all as specified and directed. |
| 19 | M&L Earth continuity conductor or main earthing lead fixed to wall or on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles with 32 x 6mm GI strip including dismantling old unserviceable GI wire complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysDec 09, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender