Tender For External Electrification And Lighting Arrangements For E.W.S. And L.I.G. Buildings In Sector-10 Of The Greater Bareilly Residential Scheme.
Tender Value
5.14 Crore
Estimated cost
Bid Submission
04 Dec 2026
20 days left
EMD
10.30 Lakhs
Bank guarantee accepted
Document Fee
15000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Bareilly → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For External Electrification And Lighting Arrangements For E.W.S. And L.I.G. Buildings In Sector-10 Of The Greater Bareilly Residential Scheme.
BOQ
| Sl. No. | Item Description |
| 1 | Design, Engineering, Manufacturing, Fabrication, Supply, Installation, Testing and Commissioning of LT Meter Board Panel, complete in all respects, fabricated from minimum 1.6 mm / 2.0 mm thick CRCA sheet steel, duly pre-treated through a seven-tank chemical process and finished with electrostatic powder coating of 60–80 microns thickness. The panel shall have a minimum degree of protection of IP42 and shall be equipped with suitably rated aluminium busbars, energy meter mounting arrangements, requisite meter cut-outs, separate neutral and earth busbars, internal wiring, terminal blocks, cable entry arrangements, identification labels, hardware and all other necessary accessories required for complete and safe operation. The panel shall be designed, manufactured and tested in accordance with applicable IS8623/IEC 61439 standards and the latest relevant guidelines, technical requirements and regulations of MVVNL/concerned DISCOM. The scope shall include complete installation, testing, pre-commissioning inspection, verification of electrical connections, functional testing and load testing to ensure safe, reliable and trouble-free operation of the complete LT Meter Board Panel. Note – Mandatory Manufacturer Eligibility Criteria: The LT Meter Board Panel shall be manufactured and supplied exclusively by a manufacturer having valid GTP approval from MVVNL. The manufacturer shall also possess valid Type Test Reports issued by CPRI, ERDA or any other NABLaccredited and competent Government-recognized testing laboratory, as applicable to the offered panel design and construction. The Type Test Reports shall not be older Than three (05) years as on the date of submission of the tender. Incoming :- 160A FP MCCB 25KA-1 No. Phase Indicator (R,Y,B)-1 Set. Multifunction meter – 1 No. Outgoing:- 32A DP MCB 10KA -24 Nos. Space of Energy Meter Single Phase – 24 Nos. Busbar :- 150A FP Electrolytic Grade 25kA for 1 Sec. 1x2x12 Block |
| 2 | Design, Engineering, Manufacturing, Fabrication, Supply, Installation, Testing and Commissioning of LT Meter Board Panel, complete in all respects, fabricated from minimum 1.6 mm / 2.0 mm thick CRCA sheet steel, duly pre-treated through a seven-tank chemical process and finished with electrostatic powder coating of 60–80 microns thickness. The panel shall have a minimum degree of protection of IP42 and shall be equipped with suitably rated aluminium busbars, energy meter mounting arrangements, requisite meter cut-outs, separate neutral and earth busbars, internal wiring, terminal blocks, cable entry arrangements, identification labels, hardware and all other necessary accessories required for complete and safe operation. The panel shall be designed, manufactured and tested in accordance with applicable IS8623/IEC 61439 standards and the latest relevant guidelines, technical requirements and regulations of MVVNL/concerned DISCOM. The scope shall include complete installation, testing, pre-commissioning inspection, verification of electrical connections, functional testing and load testing to ensure safe, reliable and trouble-free operation of the complete LT Meter Board Panel. Note – Mandatory Manufacturer Eligibility Criteria: The LT Meter Board Panel shall be manufactured and supplied exclusively by a manufacturer having valid GTP approval from MVVNL. The manufacturer shall also possess valid Type Test Reports issued by CPRI, ERDA or any other NABLaccredited and competent Government-recognized testing laboratory, as applicable to the offered panel design and construction. The Type Test Reports shall not be older Than three (05) years as on the date of submission of the tender. Incoming :- 125A FP MCCB 25KA-1 No. Phase Indicator (R,Y,B)-1 Set. Multifunction meter – 1 No. Outgoing:- 32A DP MCB 10KA -24 Nos. Space of Energy Meter Single Phase – 16 Nos. Busbar :- 150A FP Electrolytic Grade 25kA for 1 Sec. 1x4x6 Block. |
| 3 | Suyply and laying of Aluniniun Conduetor PVC insulnted armoured sevest sheathed cables 110oV grade in existing masonary open duct as dinetedby bngincer in Charge complete in all respect including exeasation and refllling. The armouring of the cable shall be properly oonnevtesl with the eatth conductor by clamps ete. (a) 400 sqmm 3-1/2 Core UP PWD SCHEDULE 2024 (CHAPTER-20a SI NO 1.20)(3376X0.8475=2861) |
| 4 | (b) 185 sqmm 3-1/2 Core UP PWD SCHEDULE 2024 (CHAPTER-20E SI NO 1.17)(1517X0.8475=1285) |
| 5 | (c) 120 sqmm 3-1/2 Core UP PWD SCHEDULE 2024 (CHAPTER-20E SI NO 1.15)(1041X0.8475=882) |
| 6 | (d) 16 sqmm 4 Core UP PWD SCHEDULE 2024 (CHAPTER-20a SI NO 1.9)(618X0.8475=524) |
| 7 | supply and erection of plain /pin type cable socket (lugs) of the cable leads insulating with tape and connection etc. 400 Sq mm (504 o) UP PWD SCHEDULE 2018 |
| 8 | supply and erection of plain /pin type cable socket (lugs) of the cable leads insulating with tape and connection etc. 185 Sq mm (504 L)UP PWD SCHEDULE 2018 |
| 9 | Supply and burring of safe earthing electrode T-19, (Hot Dip Galvanised), length up to 3000 mm, outer dia 50mm, inner dia 25 mm, terminal dia 12 mm, outer G.I. pipe of 16 swg and inner G.I. pipe of 12 swg with hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kg activated soil (BFC) capable of reducing the soil resistivity with good mixture of retating capacity and one earthing lead of 25×3 G.I. strip, up to switch board aloang with 30 cm. square C.I. frame with hinged cover and manosary housing. make: As approved in UP PWD SCHEDULE 2018 (SI NO 725 (b) |
| 10 | Supply and erection of 11 meter loang tubular pole SP 55, 1/6 over all length pole grouted in cement concrete with 1:3:6 (cement concrete) of pole 30 cm above the ground levels including excavation, back filling etc. rates includes all materials, labour, T&P etc. required for proper completion. PSR |
| 11 | S/F 11 KV pin insulator with on steel poles or any where specified including bolts to fasten the pole cap/cross arm with the pole. AR SI.No 13.10 CPWD 2018 |
| 12 | S/F of straight M.S. channal 100×50×6 mm 9.56Kg/Mt. long 1.15 mtr as per design for cross arm with clamp, nuts, bolts, red enamel painting etc. PSR |
| 13 | S/F OF 11KV Disc insulator with gun fitting for fixing on cross arms /clamps to be fixed on poles including all bolts nuts , washer etc. (insulator not less than 41KMN) for proper completion of the work. AR SI.No 13.11 CPWD 2018 |
| 14 | Supply and fixing of straight M.S. channel 75×40×6 mm 5.7Kg/Mt 2.24 Mt loang for guarding with two nos of eye bolts, clamp red enamel painting etc.(Item No 13.16) CPWD SCHEDULE 2018 |
| 15 | S/F of 11 KV T.P.M.O. of with D.O. fuse set complete in all respect. PSR |
| 16 | S/F of 11 Kv lighterning arrestor (comprising of 3 units) complete with base short with G.S. strip. (Item No 13.13) CPWD SCHEDULE 2018 |
| 17 | Supply Installation and Commissioning of 400 KVA, 11/.44 KV copper wound out door type Transformer including loading, unloading, local carriage with all material, labour etc complete in all respect Whose GTP Approved in MVVNL having valid CPRI/ERDA type test |
| 18 | Supply Installation and Commissioning of 63 KVA, 11/0.433 KV Transformer including loading, unloading, local carriage with all material, labour etc complete in all respect Whose GTP Approved in MVVNL having valid CPRI/ERDA type test |
| 19 | Construction of Solid B/W Transformer Plinth of size ( 2×1.5×1 mt) above G.L.The top of the plinth shall be of RCC 15 cm thick with material & labour all complete as per direction of E/Ic. PSR (Existing one Plinth made Also.) |
| 20 | Trenchless boring with more than 2 mtr and upto 6mt below ground level by machine technology including oilaying of 33000 V HT cable 150mm Sqm to 400 Sqmmm |
| 21 | 120 mm HDPE pipe by machine technology including o'cost of T&P, Labour and all required material suitable for laying of 11000 V HT cable 150mm Sqm to 400 Sqmm size with proper completion f the work. As per per direction of E/L. (Analysis Rate) |
| 22 | Supply and making suitable earthing of neutral/body of T/F/D.P./ACB/Lighting arrestor with 900×900×6 mm G.I. plate burried vertically bellow 6 meter G.L. 8 upto water level 7/10 SWG G.I. stay wire complete with all material, labour T&P etc. (Item No 702) UP PWD SCHEDULE 2018 |
| 23 | Supply and fixing of 2 metres high cage fabricated with 3 mm thick expanded metal fixed n 50 mm x 50 mm x 6 mm angle iron frame having vertical members spaced at 1 to 1.25 mts and horizonatal members spaced 1 mt The vertical members shall be grouted in floor and horizontal members in the walll to a depth of 300 mm with ends forked.The cage shall have 2000 mm x 1000 mm size one leaf door with locking device having door frame fabricated with 35 mm x 35 mm x 6 mm angle iron and 3 mm expanded metal duty fixed with the cage member with hinges etc. The cage shall be painted with red oxide primer and synthetic enamel paint. The job includes alll materials, labour, T&P etc for proper completion of work. (Item No 1142) UP PWD SCHEDULE 2018 |
| 24 | Supply and Laying of 3 core stranded Aluminium Conductar XLPE (Cross linked polyethylene) insulated PVC bedded, galvanized flat steel strip armoured cables confirming to 1.S, 709S (Part Il with latest amendments) 11 KV grade in existing epen masonary duct as directed by Engineer in Charge cemplete in all respect including exeavatien end Irfilling The armouwing of the cable shall be properly connected with the carth conductor by clamps ete, (a) 185 sqmm 3 core |
| 25 | S/M of out door push on type cable jointing kit suitable for 240/300/400 sq. mm XLPE cable make M seal/cab seal etc complete. (Item No 10.5.2) CPWD SCHEDULE 2018(2066X0.8475=12605) |
| 26 | S/F of cubical box dust and vermin proof 2/3/4 way distribution box of 16 SWG M.S. sheet of 15 mt weight with suitable size of copper 3 Nos tailness unit 500 Amp. Cut out inside looking arrangement hubdle danger plate etc including two coat of approved quailty paint and earthing by two nos 7/10 SWG wire which will be taken as loop from existing sub station earthing the job including all material labour T&P suitable foundation for mounting the bar's etc complete.(ps) PSR |
| 27 | S/M of Straight Through cable jointing kit suitable fo185/240 sq. mm XLPE cable make M seal/ Raychem and its equvalent per direction of E/I. |
| 28 | S/F of \\"B\\" class of 100 mm dia G.I. pipe with M.S clamp nuts & bolt complete in all respect as per direction of E/I.SI No. 14.13.3 CPWD SCHEDULE 2024 |
| 29 | Painting of the electric pole with 2 coats of aluminium paint over red oxide primer complete in all respect. . Approved by UP PWD SCHEDULE 2018. (SI NO 634) |
| 30 | Supply sagging, tensioning jumpering binding of suitable size A.C.S.R. Conductor including proper completion of work. Rabbit/DOG/weasel/REC RECON UP PWD SCHEDULE 2018 (Item No 627) |
| 31 | Making suitable earthing of electric pole atleast 2.5 m long 20 mm dia M.S rod 7/16 of SWG GI including the cast of all material labour T&P etc. required for proper completion of work PSR. |
| 32 | Supply & fixing of anticlimbing device fabricated from G.I.(flat) of 25 mm x 6mm size in a shape of ring of the pole size, having G.I. flat pointed fins of length 225 mm in 8 nos. including all the materials, labour, T&P and other material required for proper completion for work and to the satisfaction of Engineer-in-Charge.UP PWD SCHEDULE 2018 (SI NO 635) |
| 33 | Supply and errection of \\"D\\" clamps of 50mmx6mm flat iron on steel tubular poles/steel rail poles with bolts, nuts, etc. complete in all respects including painting with aluminium paint (S.I.623/2018) |
| 34 | S/F of stay set at least 3.5 mtr. Away from the pole complete with GI 19 mm dia. & 1.80 long stay rod 30 cm. x 63 cm. Anchor plate thimble stay clamp, stay insulator, 19x600 mm. double screw tightner, 7/8SWG GI stay wire etc in 1:3:6 cement concrete & grauting as per direction of E/I. S.I.No-631/18 |
| 35 | S/F of danger Board complete with clamps, bolts & nut complete in all respect as per direction of E/I. S.I 1109/18 |
| 36 | S/f of hexagonal/cradle type guard and 4 to 8 SWA G.I. wire including binding etc. complete in all respect. (S.I. 629/2018) |
| 37 | Supply and erection of over head line with G.I. Wire no 8 to 4 SWG on poles/ serivce bracket including binding etc. Complete in all respects (S.I. 628/2018) |
| 38 | Supply and laying of 120 Sqm x 3core +95Sqm+1x16SSqm ABC insulated cable with messenger wire complete in all respects |
| 39 | S/F Suspension clamp insulated complete in all respects. AR/2018 |
| 40 | S/F of dead end clamp complete in all respects AR/ 2018 |
| 41 | S/F of eye bolts/ hooks complete in all respects AR/2018 |
| 42 | Supply and errection of 9 meter long tubler pole SP 32, 1/6 over all length of pole grouted in cement concrete with 1:3:6 (cement concrete) of pole 30cm above the ground levels including excavation, back filling etc. rates includes all materials, labour, T&P etc. required for proper completion of the work as per E/I . (S.I. 613/2018) |
| 43 | Supply and fixing of 12.5 mtr. High mast shaft of approved make with rising system hot dip glavanized inside & out side dip, heaving pole sheet thickness 3mm. Top dia minimum 150 mm, bottom dia minimum 310mm, base plate 25mm thick, suitable for wind velocity as per IS 875 part 3 & having no circumferential weld, with accessories for high mast such as head frame suitable for 6 luminaries & its control gear boxes 0.75 HP power tool moter, 3 point suspension system with steel wire rope 6mm dia, double drum winch, including making suitable foundation as per manufature drawing/site reuiment along with foundation bolts nuts, washers, anchor plates etc complete in all respect. UP PWD SCHEDULE 2024 (CHAPTER-21 SI NO 21.3)246218X0.8475=208670) |
| 44 | S/F of \\"B\\" class of 150 mm dia G.I. pipe with M.S clamp nuts & bolt complete in all respect as per direction of E/I.SI No. 14.13.4 cpwd/2018 (1687x100/113=1492.00) |
| 45 | S/F of 0.60x0.30x0.15 mtr. Distribution box made of 16Sqm sheat with painting including 200 Amp aluminium bus bar TPN complete in all respects. AR/2018 |
| 46 | Supply and fixing of factory wired avtegral LED flood light Juminaires with die cast aluminiun housing with toughend glass UV stabilized PC Cover and lenses built with mandatory driver set suitable for 100 to 120 Watt. Confirming to IP 66 and IK 07 and above protection complete in all respect12000-14400 system lumens, High power LED with lenses, >120 Lm/W, P.F>0.95, THD <10% at full load, CRI >70, Potted driver Set in Metal housing (Not Circuitory) Phase to pliase Protection at 440V & >300V aute cut and re-start feature, 4 KV internal Surge protection, with 5 years warrantee. UP PWD SCHEDULE 2024 (CHAPTER-23 SI NO 23.24)10884.00X0.8475=9224) |
| 47 | Supply and fixing of LED Street light Fitting with mendatury driver det having die cast aluminium body with tougherd glass! UV Wabilized PC Cover and lenses suitable for 75 Watt, to 90 Watt and Cunfirming to IP 65, and IK07 and above protection having Gompany LOCO Engraved complete in all respect including Labour9000-10800 system lumens, High Power LED with lenset, 120 Lm/W, PF>0.95, THD <10% at full load, CRI >70, Potted driver Set in Metal housing (Not Circuitory) Phase to phase Protection at 440V & >300V auto cut and re-start feature, with 5 years warrantee UP PWD SCHEDULE 2024 (CHAPTER-23 SI NO 23.16) 10124X0.8475=8580) |
| 48 | Supply and fixing capacity of automatic street light cubicle control panel painted with anti corrosive alkali and acid proof paint consisting of time switch TSO 100 series with contractors, HRC fuses, isolating switch metering instrument & instrument box with CTs etc. in case of TPN, complete in all respect 40 A TPN SOR-807(f) (ii)/2018, inbuild three nos Himer phasewise. Complete in respect as per direction of E/I Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 04, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysDec 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender