Tender For Upgradation Of Electrical Infrastructure (Phase-I) By Way Of Creation Of 11/0.44Kv Sub-Stations Along With D.G Sets, Lt Power Panels Along With Electric Panel Room, Lt & Ht Ab Cable Networks.

Issued by Boards / Undertakings / PSU · Pulwama, Jammu and Kashmir
Tender Value
2.29 Crore
Estimated cost
Bid Submission
30 Nov 2026
8 days left
EMD
4.59 Lakhs
Bank guarantee accepted
Document Fee
6000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Pulwama → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Upgradation Of Electrical Infrastructure (Phase-I) By Way Of Creation Of 11/0.44Kv Sub-Stations Along With D.G Sets, Lt Power Panels Along With Electric Panel Room, Lt & Ht Ab Cable Networks.

BOQ

Name of Work:- Upgradation of Electrical Infrastructure (Phase-I) by way of Creation of 11/0.44KV Sub-Stations along with D.G Sets, LT Power Panels along with Electric Panel Room, LT & HT AB Cable Networks.
Sl. No. Item Description
1Supply, Installation, Testing & Commissioning of 250-KVA, 11/0.44Kv, 3-phase Distribution Transformers with Bimetallic Terminal Connectors of Energy Level-2, (Copper wound) , and with LV Cable Box having detachable Al.Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable.( X-mer without OCTC (Off Ckt Tap Changer))
2Supply & Erection of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Typeas per the drawings and standards of KPDCL.
3Supply & Erection of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type as per the drawings and standards of KPDCL.
4Supply & Erection of 11 kV Horn Gap Fuse Set 3 Phase 200A as per the drawings and standards of KPDCL.
5Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover as per drawings and standards of KPDCL.
6Supplying & laying of 300 Sq.mm Single Core Armoured Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, 1100V grade.
7Supplying & laying of 240 Sq.mm Single Core Armoured Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, 1100V grade.
8Supplying & making Aluminium Lugs for 240 -300 Sq.mm Al. Cable with 200mm length minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
9Supplying & Making End termination of 240-300 Sq.mm Single Core Armoured Power Cables with resin cast heat shrinkable kit with required size of Aluminium thimbles,etc, complete in all respects.
10Supply, loading, unloading, installation, testing & commissioning of Diesel Genset 320- KVA, 3phase, 50Hz, 1500RPM, 6Cylinder alternator complete with acoustics enclosure, CPCB IV+ Compliance, including PC1.1 Microprocessor / relay based AMF control panel, Inbuilt R.M.S(Remote Monitoring Sysytem) with all fittings, control cables of required length as per site requirement with all accessories including bottle copper thimbles, pvc tags, accessories.
11Supply, loading, unloading, installation, testing & commissioning of Diesel Genset 200- KVA, 3phase, 50Hz, 1500RPM, 6Cylinder alternator complete with acoustics enclosure, CPCB IV+ Compliance, including PC1.1 Microprocessor / relay based AMF control panel, Inbuilt R.M.S(Remote Monitoring Sysytem) with all fittings, control cables of required length as per site requirement with all accessories including bottle copper thimbles, pvc tags, accessories including the below Concrete Foundation as per Cost data 2024-25 of KPDCL including the following:
12Excavation in any type of soil including hard laterite soil.= 18.69 Cum
13Dry stone pitching any thickness hand packed on Horizontal plane = 3.74 Cum
14Refilling of excavated soil = 8 Cum
15Providing and laying in position cement concrete 1:3:6( 1 cement: 3 coarse sand: 6 graded stone agg. 20mm nominal size ) excluding cost of centering & shuttering = 14.95 Cum
16Cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20mm nominal size for foundations) excluding cost of centering& shuttering = 16.99 Cum
1715 mm thick Cement Plaster = 35.29 Sq.m
18Earthing of Substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mmx3 mm for connection of substation body as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover = 4 Nos
19Supplying & laying of 50 Sq.mm (11Kv) 3-Core Armoured Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, 11Kv grade , complete in all respects.
20Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :50-70 Sq.mm
21Providing & Erection of 1.1Kv Aerial Bunched Cable of 120 mm² AB (LT) Cable: 3x120 mm²+ 1x95 mm²(insulated) + 1x25mm² XLPE Aluminium on the ST Poles, complete in all respects as per the Drawings, standards and specifications of KPDCL.
22Providing & Erection of 1.1Kv Aerial Bunched Cable of 70 mm² AB (LT) Cable: 3x70 mm²+ 1x50 mm²(insulated) + 1x16mm² XLPE Aluminium on the ST Poles, complete in all respects as per the Drawings, standards and specifications of KPDCL.
23Providing & Erection of 1.1Kv Aerial Bunched Cable of 35 mm² AB (LT) Cable: 3x35 mm²+ 1x25 mm²(insulated) + 1x16mm² XLPE Aluminium on the ST Poles, complete in all respects as per the Drawings, standards and specifications of KPDCL.
24Providing & Erection of Main Service Distribution Box Along with MCCB /MCB as per REC Drawing complete in all respects.
25Providing & Erection of LT 16Sq.mm 2 Core XLPE armoured Cable, complete in all respects as per the Drawings, standards and specifications of KPDCL.
26Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.2 x 4 sq. mm
27Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.2 x 6 sq. mm
28Supplying & making Aluminium Lugs for 120 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
29Supplying & making Aluminium Lugs for 95 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
30Supplying & making Aluminium Lugs for 70 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
31Supplying & making Aluminium Lugs for 50 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
32Supplying & making Aluminium Lugs for 35 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
33Supplying & making Aluminium Lugs for 25 Sq.mm Al. Cable with 200mm minimum PVC Insulated seleeves, complete in all respects including thimbling, crimping and shrinking of Seleeves.
34Providing & Erection of 11Kv Aerial Bunched Cable of size 3x120 mm²+ 1x95 mm²(insulated messanger) XLPE Aluminium (11 kV, 3C + Earth) on the ST Poles, complete in all respects as per the Drawings, standards and specifications of KPDCL.
35Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :120 Sq.mm (AB cable)
36Providing & Erection of 50 mm² ACSR Conductor (Rabbit) on ST Poles, complete in all respects as per the drawings, standards and specifications of KPDCL.
37Providing & Fiixng of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm as per the drawings and standards of KPDCL
38Providing & Fiixng of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting,as per the drawings and standards of KPDCL.
39Providing & Fiixng of Wedge Connectors / PG Clamps ,as per the drawings and standards of KPDCL
40Supply, Installation, Testing & Commissioning of 3-Ø, 4-Wire Trivector Meter (Prodigy ) with suitable ring type CT 200 Amp, complete in all respects.
41Providing & Erection of Steel Tubular Pole as per IS:2713(Part-I-II) :1980 as amendedup to date with approximate weight of 164 Kg and length of 9 Metres as per the approved drawing and specifications of the KPDCL Standards.
42Painting of Pole with Red Oxide as per KPDCL Standards.
43Painting of Pole with Aluminium Paint as per KPDCL Standards.
44Cement bottoming 1:2:4 mix as per Standards 0.48 cum /pole, including shuttering, removal of deribs, cleaning of the surface, etc as required, complete in all respects.
45Earthing of poles Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm as per KPDCL Standards.
46Providing , fabrication and erection of G.I cross-arm, fabrication of Channels, Angle, Flat Iron of sizes, Transformer Bed including clamps,nuts, bolts and washers on St poles, complete in all respects as per the approved standards of KPDCL and as approved by the Engineer Incharge.
47Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6) mm, nut-bolts, 2 Nos turn- buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
48Providing & Erection of Insulated Suspension/Tension Clamp with eye hook, including nuts, bolts, washers, etc as required, complete in all respects as per the KPDCL Standards.
49Providing & Erection of Suspension Fitting (2 Bolt) / Tension Fitting for 11KV (4 Bolt) including nuts, bolts, washers, etc as required, complete in all respects as per the KPDCL Standards.
50Providing, design and fabrication of outdoor type feeder pillar made out of 2mm thick CRCA coated MS sheets, water and weather prooof (Double Door) with following Switchgears:1. 1No. 320A ATAM release, 36KA breaking capacity, 100% Icu, FP MCCB (I/c).2. 1 Set of 320A 4 Way Aluminium Busbar.3. 1 No. of 250A, FP, 36KA breaking capcity, 100% Icu, ATAM release MCCB (OG-I)4. 1 No. of 160A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-2)5. 1 No. of 63A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-3)6. 2 Nos of 40A DP MCCB.(OG-4)7. Voltmeter and phase indication for each outgoing and incommer.The feeder pillah should have legs and mounting structure of made out of G.I angle iron and the feeder pillar must be fixed in the concrete cement.
51Providing, design and fabrication of outdoor type feeder pillar made out of 2mm thick CRCA coated MS sheets, water and weather prooof (Double Door) with following Switchgears:1. 1No. 250A ATAM release, 36KA breaking capacity, 100% Icu, FP MCCB (I/c).2. 1 Set of 250A 4 Way Aluminium Busbar.3. 1 No. of 160A-200A, FP, 36KA breaking capcity, 100% Icu, ATAM release MCCB (OG-I)4. 1 No. of 125A-160A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-2)5. 1 No. of 63A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-3)6. 2 Nos of 40A-63A DP MCCB.(OG-4)7. Voltmeter and phase indication for each outgoing and incommer.The feeder pillah should have legs and mounting structure of made out of G.I angle iron and the feeder pillar must be fixed in the concrete cement.
52Providing, design and fabrication of outdoor type feeder pillar made out of 2mm thick CRCA coated MS sheets, water and weather prooof (Double Door) with following Switchgears:1. 1No. 320A ATAM release, 36KA breaking capacity, 100% Icu, FP MCCB (I/c).2. 1 Set of 320A 4 Way Aluminium Busbar.3. 1 No. of 250A, FP, 36KA breaking capcity, 100% Icu, ATAM release MCCB (OG-I)4. 1 No. of 125A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-2)5. 1 No. of 63A, FP, 25-27KA breaking capcity, 100% Icu, ATAM release MCCB (OG-3)6. 2 Nos of 40A-63A DP MCCB.(OG-4)7. Voltmeter and phase indication for each outgoing and incommer.The feeder pillah should have legs and mounting structure of made out of G.I angle iron and the feeder pillar must be fixed in the concrete cement.
53Supplying and laying of ACSR to Cable Connector/Insulating Piercing Connectors.
54Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required and stacking in the Store.
55Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
56Above 8.0 metre and upto 10.0 metre
57Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required.
58Providing & Installation of 11 kV Isolator, Double Break,3-pole, 630Amp, horizontal mounting Type, with Earth Switch, complete in all respects.
59Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, bolted with the Iron base Including G.I. bolts & nuts, etc. as required.300 mm width X 50 mm depth X 1.6 mm thickness.
60Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.90 mm dia (OD-90 mm & ID-76 mm nominal)
61Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.120 mm dia (OD-120 mm & ID-103 mm nominal)
62Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket,bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.120 mm dia (OD-120 mm & ID-103 mm nominal)
63Supplying and fixing of light class G.I. pipe of 100 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
64Cable trench of size 750mmx750mm for laying of 11Kv/1.1kv Cable in concrete Mix 1:2:4 with shuttering, earth work in all kind of soil, backfilling and RCC concrete Mix 1:1.5::3 with 100mm thickness, making holes in shuttering for every Meter in staircase way, with support of Angle Iron of size 50x50x5mm on RCC cover and Base of the trench, Perforated Cable Trays in stair cases structure, complete in all respects. Complete drawing of the trench with details of Mix will be given by the Incharge Engineer.
65Design, Supply, fabrication, Assembling, Installation & Commissioning LT Main Power Panel for for 250-KVA Substaion-I & II of cubical main type panel board from high quality 14 SWG 2mm wall thickness CRCA sheet angle/flat iron mounted with hinged lockable front double door for each meter compartment to accomadate with fixing arrangement of energy meter, Multi function meter (MFM),MCCB, Bus bar ways in separate compartments painted with powder coated conforming to CPWD specification IP-55 .The LT Distribution panel must be free standing ,floor mounting and front execution type suitable for 415 V +/- 3% , 3 phase and neutral ,50 Hz system conforming I.E rules with necessary provision to connect cables of various sizes from the rear bottom side., 50 Hz, 4 wire power supply system.The assembly comprising of chassis ,famework, and fixed parts of metal casing of the switchgear shallbe provided with separte earthing terminal.The formation must be compartmentalised in form 3b construction and must be supplied and installed. The Panel is comprising of the following switchgears:
66(i) 1 No. 400A, FP, Microprocessor based release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-I)(ii). 1 No. of Onload Changeover of capcity 400A. (I/C C/O -I)(iii) 1 Set of 400A, 4 Way Aluminium Busbar with PVC Insulation. (BB-I)(iv) 1 No. 320A, FP, Microprocessor based release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-II)(v). 1 No. of Onload Changeover of capcity 320A. (I/C C/O -II)(vi). 1 Set of 320A, 4 Way Aluminium Busbar with PVC Insulation. (BB-II)(vii). Outgoings -I:1 No. of 320A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No. of 125A - 160A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 40A-63A DP MCCB.2 No.s of 63A TPN MCB.2 No's of 40A TPN MCB(ix) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
67(viii). Outgoings -II:3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No. of 125A - 160A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 40A-63A DP MCCB.2 No.s of 63A TPN MCB.2 No's of 40A TPN MCB1 Set of Automatic Lighting Panel with 40A DP, 10kA MCB, 40A 2P Contactor with add on Blocks, Selector witch 6A 1P 2W OFF, Ststus Indication Lamps. & Astro Timer, etc as required, complete in all respects.1 No. of 160A Onload Changeover(ix) 2 Nos of Digital VAF, PF Meter Calss 1.0 with CT's and Phase Indications.(x) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
68Design, Supply, fabrication, Assembling, Installation & Commissioning LT Main Power Panel for for 250-KVA Substaion-III of cubical main type panel board from high quality 14 SWG 2mm wall thickness CRCA sheet angle/flat iron mounted with hinged lockable front double door for each meter compartment to accomadate with fixing arrangement of energy meter, Multi function meter (MFM),MCCB, Bus bar ways in separate compartments painted with powder coated conforming to CPWD specification IP-55 .The LT Distribution panel must be free standing ,floor mounting and front execution type suitable for 415 V +/- 3% , 3 phase and neutral ,50 Hz system conforming I.E rules with necessary provision to connect cables of various sizes from the rear bottom side., 50 Hz, 4 wire power supply system.The assembly comprising of chassis ,famework, and fixed parts of metal casing of the switchgear shallbe provided with separte earthing terminal.The formation must be compartmentalised in form 3b construction and must be supplied and installed. The Panel is comprising of the following switchgears:
69(i) 1 No. 400A, FP, Microprocessor based release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-I)(ii). 1 No. of Onload Changeover of capcity 400A. (I/C C/O -I)(iii) 1 Set of 400A, 4 Way Aluminium Busbar with PVC Insulation. (BB-I)(iv) 1 No. 320A, FP, Microprocessor based release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-II)(v). 1 No. of Onload Changeover of capcity 320A. (I/C C/O -II)(vi). 1 Set of 320A, 4 Way Aluminium Busbar with PVC Insulation. (BB-II)(vii). Outgoings -I:3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 125A - 160A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 40A-63A DP MCCB.1 No's of 63A TPN MCB.1 No's of 40A TPN MCB(ix) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
70(viii). Outgoings -II:3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 125A - 160A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 40A-63A DP MCCB.1 No's of 63A TPN MCB.1 No's of 40A TPN MCB1 Set of Automatic Lighting Panel with 40A DP, 10kA MCB, 40A 2P Contactor with add on Blocks, Selector witch 6A 1P 2W OFF, Ststus Indication Lamps. & Astro Timer, etc as required, complete in all respects.(ix) 2 Nos of Digital VAF, PF Meter Calss 1.0 with CT's and Phase Indications.(x) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
71Design, Supply, fabrication, Assembling, Installation & Commissioning LT Main Power Panel for for 400-KVA Substaion of cubical main type panel board from high quality 14 SWG 2mm wall thickness CRCA sheet angle/flat iron mounted with hinged lockable front double door for each meter compartment to accomadate with fixing arrangement of energy meter, Multi function meter (MFM),MCCB, Bus bar ways in separate compartments painted with powder coated conforming to CPWD specification IP-55 .The LT Distribution panel must be free standing ,floor mounting and front execution type suitable for 415 V +/- 3% , 3 phase and neutral ,50 Hz system conforming I.E rules with necessary provision to connect cables of various sizes from the rear bottom side., 50 Hz, 4 wire power supply system.The assembly comprising of chassis ,famework, and fixed parts of metal casing of the switchgear shallbe provided with separte earthing terminal.The formation must be compartmentalised in form 3b construction and must be supplied and installed. The Panel is comprising of the following switchgears:
72(i) 1 No. 630A, FP, Microprocessor based release, 50 KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-I)(ii). 1 No. of Onload Changeover of capcity 630A. (I/C C/O -I)(iii) 1 Set of 630A, 4 Way Aluminium Busbar with PVC Insulation. (BB-I)(iv) 1 No. 400A, FP, Microprocessor based release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle. (I/C-II)(v). 1 No. of Onload Changeover of capcity 400A. (I/C C/O -II)(vi). 1 Set of 400A, 4 Way Aluminium Busbar with PVC Insulation. (BB-II)(vii). Outgoings -I:1 No. of 320A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.5 No's of 160A - 200A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.1 No's of 100A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 63A DP MCCB.2 No's of 125A DP MCCB1 No.s of 63A TPN MCB.1 No's of 40A TPN MCB(ix) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
73(viii). Outgoings -II:3 No.s 250A, FP, ATAM release, 36KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.5 No's of 160A - 200A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.1 No's of 100A, FP, ATAM release, 25-27KA breaking capacity, 100% Icu, MCCB with spreader and extended rotary Handle.2 No's of 63A DP MCCB.2 No's of 125A DP MCCB1 No. of 63A TPN MCB.1 No. of 40A TPN MCB.1 No of 250A Onload 4 Pole Changeover.1 Set of Automatic Lighting Panel with 40A DP, 10kA MCB, 40A 2P Contactor with add on Blocks, Selector witch 6A 1P 2W OFF, Ststus Indication Lamps. & Astro Timer, etc as required, complete in all respects.(ix) 2 Nos of Digital VAF, PF Meter Calss 1.0 with CT's and Phase Indications.(x) RYB Indication lamps and Digital Voltmeter for each Outgoins and also for changeovers.
74Dismanteling, Loading, Unloading at another site within 1km range with mechanical means, reinstallation of already exisiting 01 Number of 400-KVA Distribution Transformer, 03 Number of 100-250 KVA DG Sets with all accessories including connection, testing on site with commissioning, etc as required,complete in all respect.
75Proviidng, Installation, testing and commisisoning of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) on the exisitng structure, including connections, etc as required, complete in all respects.
76Supply, installation , tetsing & commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (SCADA Compatible) with single busbar duly interlocked, horizontal isolation and horizontal drawout switchboard to be coupled with the exisitng 11KV Panels using buscoupler and adaptor Panel . (Outgoing Panel to be synchronised and fixed with the exisitng 11-KV VCB Panels)
77CONSTRUCTION OF (02) TWO NUMBERS OF ELECTRIC POWER PANEL ROOMS
78Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed, within a lead of 50 metres: All kinds of soil
79Providing and Laying Stone Soling including cost of stones and preparation of surface using quarry stones/ Complete item including material and labours.
80Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with: 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
81Providing and laying in position specified grade of reinforced cement concrete including curing but excluding the cost of centering, shuttering, finishing and reinforcement. All works upto plinth level; 1:1½:3 (1 cement : 1½ coarse sand : 3 graded stone aggregate 20 mm nominal size)
82Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level: hermo-Mechanically Treated bars of grade Fe-500D or more.
83Centering and shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases of Columns
84Lintel, beams, plinth beams, girders, bressumers and cantilevers
85Suspended floors, roofs, landings, balconies and access platforms
86Providing and laying damp-proof Course 50 mm thick with cement concrete 1:2:4 (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and curing complete
87Cement concrete flooring 1:2:4 (1cement: 2 coarse sand: 4 graded stone aggregate) finished with a floating coat of neat cement including cement slurry and curing complete, but excluding the cost of nosing of steps etc. complete.50 mm thick with 20mm nominal size stone aggregate.
88Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm bed of dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand including finishing the top smooth and curing complete
89Brick work with common burnt clay (non-modular) bricks of class designation 7.5 in foundation and plinth including curing in : Cement mortar 1:6 ( 1 cement : 6 coarse sand)
90Extra for brick work with common burnt clay bricks/cement concrete bricks in superstructure above plinth level upto floor five level
91Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paid for separately): First class kail wood
92Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size).
93Providing and fixing glazed shutters for doors, windows and clerestory windows using 4mm thick float glass panes including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. First class kail wood (30 mm)
94Providing and fixing wire gauze shutters using galvanized M.S. wire gauze of average width for aperture 1.4 mm in both directions with wire of dia. 0.63 mm for doors, windows and clerestory windows with ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws as per direction of Engineer-in-charge. First class kail wood. (30 mm)
95Providing and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.With ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws. 35mm
96Providing and fixing aluminum tower bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete : 150x10 mm
97Providing and fixing aluminum handles ISI marked anodized (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade with necessary screws etc. complete.100 mm
98Providing and fixing aluminum sliding door bolts ISI marked anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete : 300 x 16 mm
99Providing and fixing aluminum casement stays, ISI marked, anodized (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :
10012mm cement plaster of mix 1:6 (1 cement: 6 fine sand)
101Providing and applying white cement based putty of specified thickness, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. 1 mm thick
102Distempering with dry distemper of approved brand and manufacture (two or more coats) and of required shade on new work, over and including water thinnable priming coat to give an even shade
103Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface.
104Painting with synthetic enamel paint of approved brand and manufacture to give an even shade.Two or more coats on new work
105Structural steel work in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. Welded
106Providing and fixing precoated galvanized iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58464559
AUTHORITY Boards / Undertakings / PSU
TENDER VALUE 2.29 Crore
LAST DATE 30-11-2026
Authority
Authority Name Islamic University Of Science And Technology
Work Description Tender for Upgradation Of Electrical Infrastructure (Phase-I) By Way Of Creation Of 11/0.44Kv Sub-Stations Along With D.G Sets, Lt Power Panels Along With Electric Panel Room, Lt & Ht Ab Cable Networks.
Basic Detail
Tender No IUST/EW26/TEND/ELE/UEI-P1/08
Bidding Type Tender
Location
City Pulwama
State Jammu and Kashmir
Key Dates
Publish Date 09 Nov 2026
Submission Date 30 Nov 2026
Open Date 01 Dec 2026
Finance
Tender Value 2.29 Crore
Tender Fee 6000
EMD 4.59 Lakhs
Exemption Not Available
Document List
acf00ba4-fabc-439c-a111-5b80abcc56e2.html
BOQ_1119140.xls
Tendernotice_1.pdf
Tendernotice_2.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 09, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 30, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 8 days
Dec 01, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 9 days

Tender Documents

Download All (ZIP) ↓
html

acf00ba4-fabc-439c-a111-5b80abcc56e2.html

xls

BOQ_1119140.xls

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2.pdf