Tender For Proposed Upliftment Of Fire Fighting At Niryaat Bhawan At Qaiserbagh, Lucknow (Uttar Pradesh)
Tender Value
65.33 Lakhs
Estimated cost
Bid Submission
26 Nov 2026
10 days left
EMD
65400
Bank guarantee accepted
Document Fee
2360
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Lucknow → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Proposed Upliftment Of Fire Fighting At Niryaat Bhawan At Qaiserbagh, Lucknow (Uttar Pradesh)
BOQ
| Sl. No. | Item Description |
| 1 | Excavation of foundation in ordinary soil (loam clay or sand) including lift upto 1.50 meter and lead upto 30 meter and including filling, watering and ramming of excavated earth into the trenches or into the space between the building and sides of foundation trenches or into the plinth and removal and disposal of sur-plus earth as directed by the Engineer incharge up to a distance of 30 meters from the foundation trenches. |
| 2 | 0.00 to 1.50 mtr. |
| 3 | 1.50 to 3.00 mtr. |
| 4 | 3.00 to 4.50 mtr. |
| 5 | 4.50 to 6.00 mtr. |
| 6 | Providing and laying in cement concrete 1:4:8 (1 cement :4 coarse sand :8 graded Stone aggregate 40 mm nominal size) and curing complete,including cost of form- work, in foundation and floors. |
| 7 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear thecost of extra cement.Concrete of M-25 grade with minimum cement content of 330 kg /cumAll works upto plinth level |
| 8 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge, for the following grades of concrete.: Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear thecost of extra cement.Concrete of M-25 grade with minimum cement content of 330 kg /cumAll works Above plinth level |
| 9 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 10 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 11 | 15 mm cement plaster on rough side of single or half brick wall of mix: 1:6 (1 cement: 6 coarse sand) |
| 12 | 12 mm cement plaster of mix : 1:6 (1 cement: 6 coarse sand) |
| 13 | 12mm thick plaster in 1:4 on ceiling and soffits of stairs upto floor two level. |
| 14 | Cement concrete flooring 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate of Size 20mm nominal size laid in one layer neat cement (40 mm thick floor). |
| 15 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to openings /wooden frames with rawl plugs screws etc. |
| 16 | Providing and fixing factory made ISI marked steel glazed doors, windows and ventilators, side /top /centre hung, with beading and all members such as F7D,F4B, K11 B and K12 B etc. complete of standard rolled steel sections, joints mitred and flash butt welded and sash bars tenoned and riveted, including providing and fixing of hinges, pivots, priming coat of approved steel primer, but excluding the cost of other fittings,glass panes complete all as per approved design, (sectional weight of only steel members shall be measured for payment). Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 17 | Providing and fixing M.S. Tubular frames for doors, windows, ventilators and cupboard with rectangular/ L-Type sections, made of 1.60 mm thick M.S. Sheet, joints mitred, welded and grinded finish, with profiles of required size, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. |
| 18 | Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 19 | Providing and fixing ISI marked flush door shutters conforming to IS :2202 (Part I) non-decorative type, core of block board construction withframe of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters : 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 20 | (a) 35mm thick including ISI marked stainless steel butt hinges with necessary screws. |
| 21 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :4.0 mm thick glass panes |
| 22 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm) |
| 23 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Two or more coats applied on walls @ 1.25 ltr/10 Sqm over and including one coat of Special primer applied @ 0.75 ltr /10 Sqm |
| 24 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete. (a) 250mm x 16mm |
| 25 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete (a) 250 mm x 10mm |
| 26 | Providing and fixing ISI marked oxidised M.S. handles conforming to IS:4992 with necessary screws etc. complete. 125mm |
| 27 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 28 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture |
| 29 | Providing and fixing glass strips in joints of terrazo/ cement concrete floors. 40 mm wide and 4 mm thick |
| 30 | Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge decketc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying\ the same from negative (internal) side with the help of synthetic fiberbrush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage. |
| 31 | For vertical surface two coats @ 0.70 kg per sqm |
| 32 | For horizontal surface one coat @1.10 kg per sqm. |
| 33 | Centering and shuttering including strutting, propping etc. and removal of form for: |
| 34 | Suspended floors, roofs, landings, balconies and access platform |
| 35 | Foundations, footings, bases of columns, etc. for mass concrete |
| 36 | Walls (any thickness) including attached pilasters,butteresses, plinth and string courses etc. |
| 37 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 38 | Lintels, beams, plinth beams, girders, bressumers andcantilevers |
| 39 | PUMP ROOM |
| 40 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainlesssteel shaft, mechanical seal conforming to IS 1520. Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-325. supply , Installation, testing and commissioning of fire Hydrant valve , bearing to IS:5290 marks, S.S. ,IS: 304 Grade, 63mm oblique instantaneous single out let, 75mm N.B. flanged inlet, brass spindles complete with PVC blank cap . G.I. chain etc. guard,foundation bolts etc.as required. supply , Installation, testing and commissioning of Branch pipe . S.S. short type with 63mm male instantaneous inlet, male threaded outlet fitted with 15mm, Bore nozzle,having IS: 903 with anti vibration pads. |
| 41 | 1620 LPM 70 MTR HEAD |
| 42 | (a) Supplying, installation, testing andcommissioning of diesel engine driven main firepump conforming to IS 12469: 2019 suitable forautomatic operation and consisting of following,complete in all respects, as required : (Diesel DrivenPump)(b) Horizontal type, multistage, centrifugal pump ofcast of iron body and bronze impeller with stainlesssteel shaft, mechanical seal as required.193 DELHI SCHEDULE OF RATES (E&M)-2025(c) Suitable HP, 1500 RPM water cooled withradiator, diesel engine conforming to relevant ISstandard complete with auto starting mechanism, 12/24 volts electric starting equipment, diesel tank,exhaust pipe extended upto 10 m outside pumphouse duly insulated with 50 mm thick glass woolwith 1.0 mm thick aluminium sheet cladding,residential silencer, instruments and protection asper standard specification, stop solenoid for autostop in the event of fault with audio indications,painted with post office red colour etc. as required.(d) M.S fabricated, common base plate, coupling,coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation dulyplastered and with anti vibration pads. |
| 43 | 1620 LPM 70 MTR HEAD |
| 44 | Supplying, installation, testing andcommissioning of electric driven pressurisationpump conforming to IS 12469: 2019 suitable forautomatic operation and consisting of following,complete in all respects, as required : (JockeyPump)(b) Horizontal type, multistage, centrifugal pump ofcast iron body and bronze impeller with stainlesssteel shaft, mechanical seal as required.(c) Suitable HP squirell cage induction motor TEFCtype suitable for operation on 415 volts, 3 phase50 Hz AC supply with IP 55 class of protection forenclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.194 DELHI SCHEDULE OF RATES (E&M)-2025(d) M.S. fabricated Common base plate, coupling,coupling guard, foundation bolts etc. as required.(e) Suitable cement concrete foundation dulyplastered and with anti vibration pads.. |
| 45 | 180 lpm at 70 m Head |
| 46 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with. |
| 47 | INCOMING |
| 48 | Incomings |
| 49 | 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500A |
| 50 | Outgoings |
| 51 | ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
| 52 | Main Fire Pump |
| 53 | 160 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 54 | Jockey Pump |
| 55 | 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. |
| 56 | Diesel Engine Control |
| 57 | Control for diesel engine comprising - |
| 58 | Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. |
| 59 | Supply, erection and testing of ISI marked M.S. pipes (class C) and specials etc. (as per IS:1239) for above ground laying for hydrants system includeing transportation of materials upto the worksite, cuttings the pipes to required length, edge preparation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges expansion joints wherever required, washers, nuts, bolts etc. in proper position including all supports as per layout. |
| 60 | 150 mm dia |
| 61 | 100 mm dia. |
| 62 | 250 mm dia. |
| 63 | Providing, installation, testing and commissioning ofnon-return valve of following sizes confirming to IS:5312 complete with rubber gasket, GI bolts, nuts,washers etc.as required : |
| 64 | 100 mm dia |
| 65 | 150 mm dia |
| 66 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
| 67 | 150mm dia. |
| 68 | Installing ,testing and commissioning of butterfly valve , PN- 1.0,slim seal,standard lever operated type with required flanges, nuts ,bolts etc. complete. |
| 69 | 200 mm dia. |
| 70 | 150 mm dia. |
| 71 | 100 mm dia. |
| 72 | Providing and fixining pressure gauge. |
| 73 | Providing and fixining 25 mm dia Ball Valve. |
| 74 | Providing and fixining air release valve. |
| 75 | Supplying & fixing air vessel made out of 250 mm dia,8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and painting with synthetic enamel paint of approved shade as required. |
| 76 | Supply, installation, testing & commissioning of flow switches with two no and two NC contacts with necessary nipply & other fittings, Flow switch shall be suitable for 150 dia. |
| 77 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : |
| 78 | Sub Head : C (Internal Hydrant) |
| 79 | Supply, erection and testing of ISI marked M.S. pipes (class B) and specials etc. (as per IS:1239) for above ground laying for hydrants system includeing transportation of materials upto the worksite, cuttings the pipes to required length, edge preparation, welding, fixing / erection of pipes including specials i.e. bends, tees, reducers, flanges expansion joints wherever required, washers, nuts, bolts etc. in proper position including all supports as per layout. |
| 80 | Supply, Installation, testing and commissioning of Fire Hydrant valve , bearing to IS:5290 marks, S.S. ,IS: 304 Grade, 63mm oblique instantaneous single out let, 75mm N.B. flanged inlet, brass spindles complete with PVC blank cap . G.I. chain etc. |
| 81 | supply, Installation, testing and commissioning of Branch pipe . S.S. short type with 63mm male instantaneous inlet, male threaded outlet fitted with 15mm, Bore nozzle,having IS: 903 |
| 82 | supply, Installation, testing and commissioning of Fire Hose,RRL hose jacketed with circular woven synthetic fibre,conforming to IS 636:88 63MM DIA.x 15mt. Long with SS 63mm 2 pair of male and female instantaneous coupling having IS :903 mark and duly S.S. wire wounded. The hose shall be rolled and hug to suitable M.S. support in the fire station. |
| 83 | supply, Installation, testing and commissioning of manual swing type Fire hose reel IS:884 comp. with heavy duty reel, 20 mm dia. X 30 mtr. Long 2- ply polyster yarn braided / rubber braided pressure hose with heavy duty nylon on/off jet/ spray nozzle, 25mm isolating valve and all other necessory. Please Enable Macros to View BoQ information |
| 84 | supply, Installation, testing and commissioning of manual swing type Fire hose reel IS:884 comp. with heavy duty reel, 20 mm dia. X 30 mtr. Long 2- ply polyster yarn braided / rubber braided pressure hose with heavy duty nylon on/off jet/ spray nozzle, 25mm isolating valve and all other necessory. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysNov 27, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender