Tender For Construction Of Multi-Storey Buildings In Rukmani Vihar Residential Scheme, Vrindavan, Janpad Mathura.
Tender Value
75.93 Crore
Estimated cost
Bid Submission
05 Dec 2026
17 days left
EMD
1.51 Crore
Bank guarantee accepted
Document Fee
5900
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mathura → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Construction Of Multi-Storey Buildings In Rukmani Vihar Residential Scheme, Vrindavan, Janpad Mathura.
BOQ
| Sl. No. | Item Description |
| 1 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.All kinds of soil |
| 2 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. 1.50 LVL. TO 3.00 MTR. |
| 3 | 3.00 LVL. TO 4.50 MTR. |
| 4 | 4.50LVL. TO 6.00 MTR. |
| 5 | 6.00 LVL. TO 7.50 MTR. |
| 6 | 7.50 LVL. TO 9.00 MTR. |
| 7 | 9.00 LVL. TO 10.50 MTR. |
| 8 | 10.50 LVL. TO 12.00 MTR. |
| 9 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 10 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 11 | Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement:2 coarse sand) to match the existing floor. |
| 12 | Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall & rodding etc. complete:With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration |
| 13 | Providing, supplying, erecting, fixing and maintaining heavy-duty steel shoring arrangement for supporting RCC girders, including MS/H-frame staging, adjustable steel props/screw jacks, horizontal and diagonal bracing members, base plates, U-heads, clamps, bolts and other required accessories; including cutting, welding, fabrication, erection, alignment, leveling, plumbing, necessary strengthening, shifting/handling, dismantling and removal after completion of the work, complete with all materials, labour, tools & plants, consumables, safety arrangements, scaffolding/supports and incidental works, as required for safe and stable support of the girder during construction, all complete as per approved drawings, structural requirements and Engineer-in-Charge's instructions. |
| 14 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Footing |
| 15 | Wall at basement 2 |
| 16 | Wall at basement 1 |
| 17 | Column Padestal to upto plinth |
| 18 | Slab 2 |
| 19 | Beam 2 |
| 20 | Slab 1 |
| 21 | Beam 2 |
| 22 | Column M-30 |
| 23 | Lintal |
| 24 | 6th Floor |
| 25 | 7th Floor |
| 26 | 8th Floor |
| 27 | 9th Floor |
| 28 | 10th Floor |
| 29 | 11th Floor |
| 30 | 12th Floor |
| 31 | 13th Floor |
| 32 | 14th Floor |
| 33 | 15th Floor |
| 34 | 6th Floor |
| 35 | 7th Floor |
| 36 | 8th Floor |
| 37 | 9th Floor |
| 38 | 10th Floor |
| 39 | 11th Floor |
| 40 | 12th Floor |
| 41 | 13th Floor |
| 42 | 14th Floor |
| 43 | 15th Floor |
| 44 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 45 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 46 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 47 | Extra for brick work / AAC block masonry / Tile brick masonry in superstructure above floor V level, for each four floors or part thereof by mechanical means. |
| 48 | 7th Floor |
| 49 | 8th Floor |
| 50 | 9th Floor |
| 51 | 10th Floor |
| 52 | 11th Floor |
| 53 | 12th Floor |
| 54 | 13th Floor |
| 55 | 14th Floor |
| 56 | 15th Floor |
| 57 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 58 | Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry. |
| 59 | Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means. 6th Floor |
| 60 | 7th Floor |
| 61 | 8th Floor |
| 62 | 9th Floor |
| 63 | 10th Floor |
| 64 | 11th Floor |
| 65 | 12th Floor |
| 66 | 13th Floor |
| 67 | 14th Floor |
| 68 | 15th Floor |
| 69 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 70 | 15 mm cement plaster on rough side of single or half brick wall of mix : 1:4 (1 cement: 4 coarse sand). |
| 71 | Extra for plastering exterior walls of height more than 10 mtr from ground level for every additional height of 3 mtr or part thereof 3rd floor |
| 72 | 4th floor |
| 73 | 5th floor |
| 74 | 6th floor |
| 75 | 7th floor |
| 76 | 8th floor |
| 77 | 9th floor |
| 78 | 10th floor |
| 79 | 11th floor |
| 80 | 12th floor |
| 81 | 13th floor |
| 82 | 14th floor |
| 83 | 15th floor |
| 84 | 15 mm cement plaster on rough side of single or half brick wall of mix:1:6 (1 cement: 6 coarse sand) |
| 85 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 86 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab of colour Black, Cherry/Ruby Red or equivalent (FLOORING) |
| 87 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. (Skirting) |
| 88 | Providing and laying Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quickset tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including |
| 89 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). Size of Tile 600x600 mm |
| 90 | Providing and fixing 1st quality ceramic glazed floor tiles conforming to IS : 15622 (thickness to be specified by the manufacturer) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge in skirting, risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 (1 cement: 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade complete. |
| 91 | Providing & fixing ISI marked flush door shutters conforming IS: 2202 decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters (a) 30mm thick including ISI marked stainless steel butt hinges with necessary screws. Both side laminated. (i) Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. (Part I) 1.5 mm thick (ii)Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). (a) Single leaf |
| 92 | (b) Double leaf |
| 93 | Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square |
| 94 | Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Clerestory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength |
| 95 | Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid decorative type flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/ wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant. |
| 96 | Providing and fixing T-iron frames for doors, windows and ventilators of mild steel Tee-sections, joints mitred and welded, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer. Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block 15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) |
| 97 | Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, |
| 98 | Providing & fixing Float glass panes 5.0 mm thick glass panes (weight not lessthan 12.50 kg/sqm). |
| 99 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications :Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of Special primer applied @ 0.75 ltr /10 sqm |
| 100 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm)over and including priming coat of exterior primer applied @2.20kg/10 sqm |
| 101 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 102 | Providing and fixing 150 mm bright finished floor brass door stopper with rubber cushion, necessary brass screws etc. to suit shutter thickness complete. |
| 103 | Providing and fixing Stainless steel 304 grade sliding door bolts, of 16mmx250mm solid rod with required nuts, screws, keeper, etc. all item to s.s. 304 grade only and supplied along with material test certificate. (OZ-ALD-01(16x250mm) |
| 104 | Providing and fixing Stainless steel 304 grade tower bolts (barrel and plate type) with required nuts, screws, keeper, etc. all item to s.s. 304 grade only and supplied along with material test certificate. (a) 300 mm x 10mm -(OZ-TB-S-12\\" ) |
| 105 | (b) 250 mm x 10mm (OZ-TB-S-10\\" ) |
| 106 | Providing and fixing Stainless steel 304 grade handles with plate fixed with S.S. screws,etc. complete of size 10mm 125mm all item to s.s. 304 grade only and supplied along with material test certificate. (ODG-11-10x125) |
| 107 | Providing & fixing EN:1154 Certified 500000 cycle tested door closer made of Aluminium Diecasted body having UL stamping sutable for 80kg with double speed adjustment with necessary accessories and screws etc. Complete. (NSK-680) |
| 108 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to |
| 109 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge. |
| 110 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 111 | Providing and filling sunken portion of toilet/ bathroom floors with AAC blocks of approved size and destiny, including supply , transportation, loading/unloading , stacking,cutting,dressing laying packing of AAC block in required configuration, including cement based adhesive/ mortar, labour, tools & plants , wastage, sundries and all incidental works, complete as per approved drawings and instruction of Engineer-in-charge |
| 112 | Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of:(i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS : 2645 in recommended proportions including rounding off junction of vertical and horizontal surface.(ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area.(iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm). |
| 113 | Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying:(a) after surface preparation, first layer of slurry of cement @ 0.488 kg/ sqm mixed with water proofing cement compound @ 0.253 kg/sqm.(b) laying second layer of Fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm.(c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around.(d) fourth and final layer of brick tiling with cement mortar (which will be paid for separately. For the purpose of measurement the entire treated surface will be measured. |
| 114 | Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/sqm) suitable for mounting 120 minutes Fire Rated Glazed Door Shutters. The frame shall be filled with mineral wool Insulation having density minimum 96Kg/sqm . The frame will have a provision of G.I. anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with factory made template for SS ball bearing hinges of Size 100x89x3mm for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire resistant primer or powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- Charge . (Cost of SS ball bearing hinges is excluded). |
| 115 | Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 minutes Fire rating conforming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved by Engineer-in-Charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/sqm) duly filled mineral wool insulation having density minimum 96 kg/cum and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat of approved fire resistant primer or powder coating not less than 30 micron etc all complete as per direction of Engineer-in-Charge (panelling to be paid for seperately). |
| 116 | Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/sqm) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c , including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and as per direction of Engineer-in-Charge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredited labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm. |
| 117 | Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete. |
| 118 | Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. |
| 119 | Providing and fixing false ceiling at all heights including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre,with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer’s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : |
| 120 | Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. |
| 121 | P/F of GRC Jali |
| 122 | Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specificationsand directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately). |
| 123 | Providing and laying high Tensile tiles on pavement area. |
| 124 | Providing and laying integral cement based treatment for water proofingon the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conformingto IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge :Using rough Kota stone |
| 125 | Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mmthick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge :Using rough Kota stone |
| 126 | Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Onlyweight of grill to be measured for payment). |
| 127 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 128 | P/F Polycarbonate sheetabove Ramp area |
| 129 | Centering and shuttering including strutting, propping etc. and removal of form for: Foundations, footings, bases of columns, etc. for mass concrete |
| 130 | Suspended floors, roofs, landings, balconies and access platform with water proof ply 12 mm thick |
| 131 | Lintels, beams, plinth beams, girders, bressumers and cantilevers with water proof ply 12 mm thick |
| 132 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 133 | Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 134 | Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landings, beams and balconies(Plan area to be measured) |
| 135 | Providing and fixing double scaffolding system (cup lock type) on the exterior side, up to seven story height made with 40 mm dia M.S. tube 1.5 m centre to centre, horizontal & vertical tubes joining with cup & lock system with M.S. tubes, M.S. tube challies, M.S. clamps and M.S. staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for the required duration as approved and removing it there after. The scaffolding system shall be stiffened with bracings,runners, connection with the building etc wherever required for inspection of work at required locations with essential safety features for the workmen etc. complete as per directions and approval of Engineer-in-charge. The elevational area of the scaffolding shall be measured for payment purpose. The payment will be made once irrespective of duration of scaffolding. |
| 136 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 137 | Excavating, supplying, stacking and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in foundation trenches, plinth, sides of foundation etc. complete for all lift. |
| 138 | Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete. |
| 139 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 140 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor: With Chlorpyriphos/Lindane E.C. 20% with 1% concentration |
| 141 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.All works upto plinth levelConcrete of M25 grade with minimum cement content of 330 kg /cum |
| 142 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level Concrete of M25 grade with minimum cement content of 330 kg /cum Lintel Band |
| 143 | Slabs |
| 144 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 145 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 146 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 12.5mm nominal size derived from natural sources) |
| 147 | Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per square metre on damp proof course after cleaning the surface with brushes and finally with a piece of cloth lightly soaked in kerosene oil. |
| 148 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 ( 1 cement : 4 coarse sand) |
| 149 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level & above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 150 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 151 | Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured). |
| 152 | Mild steel or iron workSteel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 153 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 154 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 155 | Providing and fixing angle iron frames for doors, windows and ventilators of mild steel Angle sections of size 35x35x5 mm, joints mitred and welded by angle iron 35x35x5 mm or 35x 5 mm flat pieces to the existing T-iron frame or to the wall with dash fastener, including fixing of necessary butt hinges and screws and applying a priming coat of approved steel primer, all complete as per the direction of Engineer-In-charge. |
| 156 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with 4.0 mm thick glass panes |
| 157 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 158 | 15 mm cement plaster on rough side of single or half brick wall of mix 1:6 (1 cement: 6 coarse sand) |
| 159 | 15 mm cement plaster in single coat on plinth 1 cement: 4 course sand in plinth. |
| 160 | Add for plaster groove in plastered surface or moulding to R.C.C. projections. |
| 161 | Making drip course in sun shade or facia as per direction of Engineer incharge including supply of all materials, labour T & P etc for proper completion of the work. |
| 162 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate |
| 163 | Providing and laying Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, ANSI: A 118.4 ET, EN12004/ISO 13007: C2TE in average 6 mm thickness, including grouting of joints |
| 164 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints Size of Tile 600x600 mm |
| 165 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade : New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) |
| 166 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 167 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 168 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @ 0.80 ltr/10 sqm of approved brand and manufacture |
| 169 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture |
| 170 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. |
| 171 | Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :300x16 mm |
| 172 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : |
| 173 | Providing and fixing Stainless Steel handles, approved quality & make with necessary screws etc all complete. : 125 mm. |
| 174 | PLUMBING WORKS |
| 175 | ELECTRICAL WORKS |
| 176 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in charge |
| 177 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 178 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. All works upto plinth level. |
| 179 | All works above plinth level upto floor V level. |
| 180 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 181 | Centering and shuttering including strutting, propping etc. and removal of form for. Foundations, footings, bases of columns, etc. for massconcrete |
| 182 | Lintels, beams, plinth beams, girders, bressumers andcantilevers |
| 183 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 184 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more |
| 185 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in Cement mortar 1:6 (1 cement : 6 coarse sand |
| 186 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 187 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 188 | Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work |
| 189 | 12 mm cement plaster in single coat on fair side of single or half brick wall for interior plastering up to floor two level including brick wall for interior plastering upto floor two level including internal rounded angles chamfers, and / or rounded angles not exceeding 80 mm in girth and finished even and smooth No. extra for mixing any additive. (1)1 cement : 6 coarse sand |
| 190 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm)over and including priming coat of exterior primer applied @2.20kg/10 sqm |
| 191 | Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in charge |
| 192 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 193 | R.c.c. work with cement approved coarse sand and 2 cm. (3/4\\") guage approved stone ballast in the proportion 1:1.5 :3,(1 cement :4.5 aggregate) in lintels As in item 3 above but in R.C.C. Raft fou stone ballast. (Using 1:1.5:3 Mixndation and footing with approved |
| 194 | As in item 3 above but in R.C.C. BEAMS in1:1.5:3having strength not less than M20 UPTO PLINTH |
| 195 | ABOVE PLINTH |
| 196 | As in item 3 above but in R.C.C. columns in1:1.5:3having strength not less than M20 |
| 197 | Mild steel or iron in plain work such as reinforced concrete or reinforced, brick work (when not included in anover all rates ) wrought to required shape |
| 198 | Class 150 brick work in 1:6 cement & coarse sand of 2.25 fine ness modulus mortar in foundation and plinth including supply of all materials , labour and tools and plants etc.required for proper completion of the work. |
| 199 | Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.Cement mortar 1:4 (1 cement :4 coarse sand) |
| 200 | Finishing walls with textured exterior paint of required shade :New work (Two or more coats applied @ 3.28 ltr/10 sqm)over and including priming coat of exterior primer applied @2.20kg/10 sqm |
| 201 | Providing and fixing 18 mm thick gang saw cut, mirror polished,premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing of edges to give high gloss finish etc. complete at all levels. Area of slab over 0.50 sqm |
| 202 | Add cost of Stainless Steel Words write on Entrance Gate. |
| 203 | Providing and fixing stone jali 40 mm thick throughout in cement mortar 1:3 (1 cement : 3 coarse sand), including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment, matching the stone shade, jali slab without any chamfers etc.White sand stone |
| 204 | Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 205 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 206 | Foundations, footings, bases of columns, etc. for mass concrete. |
| 207 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets,gates and similar works |
| 208 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitableshade with ordinary paint of approved brand and manufacture |
| 209 | COST OF ELECTRICAL WORKS |
| 210 | Excavation in foundations in ordinary soil (Loam clay or sand) including lift upto 1.5 m (5 fts.) and lead upto 30 mt. (100 fts.) & including filling, watering and ramming of excavated earth into the trenches or into the space between the building and the sides of foundation trenches or into the plinth and removal and disposal of surplus earth as directed by the Engineer-Incharges upto a distance of 30mt. (100 fts) from the foundation trenches. |
| 211 | Prepration and consolidation of sub grade with power road roller of 8 to12 tonne capacity after excavating earth to an average of 22.5 cm depth , dressing to camber and consolidating with road roller including making good undulations etc. and re-rolling the sub grade and disposal of surplus earth with lead up to 50 meters. |
| 212 | Construction of granular sub base by providing close graded material conforming to specifications , mixing in mechanical mix plant at OMC , carriage of mixed material by ippers to work site, For all leads & lifts , spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density , complete as per specification and directions of engineering - charge With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25 |
| 213 | Construction of granular sub base by providing close graded material conforming to specifications , mixing in mechanical mix plant at OMC , carriage of mixed material by ippers to work site, For all leads & lifts , spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density , complete as per specification and directions of engineering - charge with material conforming to grade III (size range 26.5mm to 0.075 mm ) having CBR value 20. |
| 214 | Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80 mm thick C.C. paver block of M-35 grade with approved colour design and pattern. |
| 215 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 216 | Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil from Lvl. 1.5 Mt.m to 3.0 Mt |
| 217 | from Lvl. 3.0 Mt.m to 4.50 Mt |
| 218 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 219 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 and for all lift. |
| 220 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. Concrete of M30 grade with minimum cement content of 330 kg /cum All works upto plinth level |
| 221 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete.Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of thespecified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement.Concrete of M25 grade with minimum cement content of 330 kg /cumAll works above plinth level |
| 222 | Add for using extra cement in the items of design mix over and above the specified cement content therein. |
| 223 | Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete |
| 224 | Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc. |
| 225 | Suspended floors, roofs, landings, balconies and access platform |
| 226 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 227 | Edges of slabs and breaks in floors and wallsUnder 20 cm wide |
| 228 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 229 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:4 (1 cement : 4 coarse sand) |
| 230 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 ( 1 cement : 6 coarse sand) |
| 231 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:4 ( 1 cement : 4 coarse sand) |
| 232 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works |
| 233 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws |
| 234 | Providing & fixing glass panes with putty and glazing clips in steel doors, windows, clerestory windows, all complete with :4.0 mm thick glass panes |
| 235 | Providing and fixing ISI marked oxidised M.S. sliding door bolts with nuts and screws etc. complete (Copper oxidised as per IS 1378)300X16 mm |
| 236 | Providing and fixing ISI marked oxidised M.S. tower bolt black finish, (Barrel type) with necessary screws etc. complete (Copper oxidised as per IS 1378) |
| 237 | 150x10 mm |
| 238 | Providing and fixing Stainless Steel handles, approved quality & make with necessary screws etc all complete. : 125 mm. |
| 239 | 12 mm cement plaster finished with a floating coat of neat cement of mix :1:4 (1 cement: 4 fine sand) |
| 240 | 12 mm cement plaster of mix 1:6 (1 cement: 6 coarse sand) |
| 241 | 15 mm cement plaster on rough side of single or half brick wall of mix 1:6 (1 cement: 6 coarse sand) |
| 242 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test.“All above operations to be done in order and as directed and specified by the Engineer-in-Charge : With average thickness of 120 mm and minimum thickness at khurra as 65 mm. |
| 243 | Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gram/litre, of approved manufacturer and of required shade and colour all complete to achieve even shade and colour : New work (two or more coats) over and including water thinnable priming coat with cement primer having VOC content less than 50 gram/litre |
| 244 | Finishing walls with water proofing cement paint of required shade : New work (Two or more coats applied @ 3.84 kg/10 sqm) |
| 245 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications : Painting wood work with Deluxe Multi Surface Paint of required shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under coat of primer applied @0.75 ltr/10 sqm of approved brand and manufacture |
| 246 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate |
| 247 | Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for under ground structures as directed by Engineer-in-Charge and consisting of : (i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound conforming to IS:2645 in the recommended proportion over the leveling course (leveling course to be paid separately). Joints sealed and grouted with cement slurry mixed with water proofing compound. (ii) 2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in recommended proportions. (iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer. Using rough kota stone. |
| 248 | Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge Using rough kota stone. |
| 249 | Supplying and fixing C.I. cover without frame for manholes : 560 mm diameter C.I. cover (heavy duty) the weight of the cover to be not less than 108 kg |
| 250 | Providing M.S. foot rests including fixing in manholes with 20x20x10 cm cement concrete blocks 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) as per standard design : With 20x20 mm square bar |
| 251 | ELECTRICAL WORKS As Per Datail Attached |
| 252 | Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.All kinds of soil 0.00 LVL. TO 1.50 MTR. |
| 253 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) |
| 254 | Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. |
| 255 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 256 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 257 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. Thermo-Mechanically Treated bars of grade Fe-500D or more. |
| 258 | 15 mm cement plaster on rough side of single or half brick wall of mix:1:6 (1 cement: 6 coarse sand) |
| 259 | 12 mm cement plaster of mix :1:6 (1 cement: 6 coarse sand) |
| 260 | Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. (FLOORING) |
| 261 | Providing and laying integral cement based treatment for water proofingon the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conformingto IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge :Using rough Kota stone |
| 262 | Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mmthick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge :Using rough Kota stone |
| 263 | Centering and shuttering including strutting, propping etc. and removal of form for: Walls (any thickness) including attached pilasters,butteresses, plinth and string courses etc. |
| 264 | SUB HEAD-I-SANITARY INSTALLATIONSProviding and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS: 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: W.C. pan with ISI marked white solid plastic seat and lid |
| 265 | Providing and fixing Jaquar Make Hand Shower (Health Faucet) with 8mm Dia,1.2 Meter Long Flexible Tube & Wall Hook of quality and make as approved by Engineer - in - charge. |
| 266 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer |
| 267 | Providing and fixing CP Brass 31mm size Bottle Trap of approved quality & make and as per the direction of Engineer-in-charge. |
| 268 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms. |
| 269 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. |
| 270 | Providing, fixing, testing and commissioning of C.P. brass angle valve with C.P. wall flange, Nut and Washer etc. complete as required. 15 mm nominal bore |
| 271 | Providing and fixing uplasticised PVC connection pipe with brass unions 15 mm nominal bore |
| 272 | Supply, storage and fixing in position of Bath and Shower Arrangement with Wall mixer complete as required and shown on Wall mixer with provision for overhead shower and telephone shower drawings/specifications Shower Head Shower arm with wall flange 100 mm diameter |
| 273 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. Providing & fixing toilet paper holde rC.P. brass ' |
| 274 | 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not lessthan 190 gms. |
| 275 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 276 | Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40 mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever Size 600x450x200mm |
| 277 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 15mm nominal bore |
| 278 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15mm nominal bore |
| 279 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge.Concealed work, including cutting chases and making good the walls etc.For Internal Toile 15 mm nominal outer dia Pipes |
| 280 | 20 mm nominal outer dia Pipes |
| 281 | 25 mm nominal outer dia Pipes |
| 282 | 32 mm nominal outer dia Pipes |
| 283 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall 25 mm nominal bore |
| 284 | 32 mm nominal bore |
| 285 | 40mm nominal dia Pipes |
| 286 | 50 mm nominal dia Pipes |
| 287 | Providing, supplying, laying, jointing, testing and commissioning of unplasticized Polyvinyl Chloride (uPVC) Soil, Waste & Waste Water drainage pipes of specified diameter, Type-B, conforming to IS 13592, with all required matching uPVC fittings conforming to IS 14735, including bends, tees, junctions, reducers, couplers, traps, clamps/supports, solvent cement joints and all necessary accessories, complete as per approved drawings, specifications and manufacturer’s recommendations, including testing and commissioning, complete in all respects. 75mm dia pipe |
| 288 | 110 mm dia pipe |
| 289 | 160mm dia pipe |
| 290 | Supply, installation , testing & commissioning of male/ female screwed end full way lever operated forged brass ball valve(PN 16) of brass body with brass ball & teflon seat tested to a pressure 24 Kg / sqcm with (threaded joints) complete as required. 15 mm nominal bore |
| 291 | 20 mm nominal bore |
| 292 | 25 mm nominal bore |
| 293 | 32 mm nominal bore. |
| 294 | 40 mm nominal bore |
| 295 | Supply, installation , testing & commissioning of gun metal vertical non return valve conforming to IS 778 of approved quality (screwed end) including union, nipple, fixing on pipe complete as required.(PN 16) 50 mm nominal bore |
| 296 | 65 mm nominal bore |
| 297 | Supply, Installation, Testing and commissioning of slim seal type C.I. Butterfly valve confirming to IS 13592 (Body : Grey Cast Iron, shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) of approved make with PN 16 rating flange dimensions shall be confirming to IS 6392, washer, nuts & bolts. Rated to temperature of 85 Deg C and tested to a pressure not less than 24 Kg/Sq.cm. 50 mm nominal bore |
| 298 | 65 mm nominal bore |
| 299 | 80 mm nominal bore |
| 300 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS :13592 Type B, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm dia (for rain water) |
| 301 | 160 mm dia (for rain water) |
| 302 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type B, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. Single Push Fit Coupler 110 mm dia |
| 303 | 160 mm dia |
| 304 | Single tee with door 160x110x110 mm |
| 305 | Plain bend 87.5 deg 110 mm dia |
| 306 | 160 mm dia |
| 307 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm dia |
| 308 | 160 mm dia |
| 309 | Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete. |
| 310 | Providing and fixing on wall face unplasticised - PVC moulded fittings/accessories for unplasticised Rigid PVC pipes including jointing with seal ring leaving 10 mm gap for thermal expansion. Bend without door (45°) 110mm |
| 311 | 160mm |
| 312 | Bend without door (87.5°) 110mm |
| 313 | 160mm |
| 314 | Y' Fitting without door 110mm |
| 315 | 160mm |
| 316 | Clean Out Plug (COP) 110 mm |
| 317 | 160mm |
| 318 | Reduced 'Y' Fitting without door 110mm x 75mm |
| 319 | 160mm x 110mm |
| 320 | Tee with door 160mm x 110mm |
| 321 | Vent Cowl 110mm |
| 322 | Providing, fixing, jointing and testing , of PVC Multi Floor Trap without jali of minimum 50 mm water seal, making necessary cutting in slab or floors and making good including supports with cement concrete 1:3:6 complete as approved by Engineer-in-Charge. 110mm x 75mm x 50mm/40mm (Toilet) |
| 323 | Providing, fixing, jointing and testing , of PVC Nahani Trap without jali of minimum 50 mm water seal, making necessary cutting in slab or floors and making good including supports with cement concrete 1:3:6 complete as approved by Engineer-in-Charge. 110mm x 75mm (Toilet & Kitchen) |
| 324 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains, including dressing of sides and ramming of bottoms, lifting, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 325 | Excavating trenches of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottoms, depth upto 2.0 M including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cms in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia. Metre |
| 326 | Sewage & Storm water Pipes:Providing and laying non pressure NP2 class (medium duty) R.C.C. pipes conforming to IS 458 with collars jointed with stiff mixture cement mortar in the proportion of 1:2 (1 cement: 2 fine sand) including testing of joints etc. complete. (all round and upto haunching shall be paid separately) 200 mm dia. R.C.C. pipe |
| 327 | 250 mm dia R.C.C. pipe |
| 328 | 300 mm dia R.C.C. pipe |
| 329 | Providing and laying cement concrete 1:5:10 mix (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) all round for pipes including bed concrete as per approved drawing and specification. 200 mm diameter |
| 330 | 250 mm diameter |
| 331 | 300 mm diameter |
| 332 | Providing and laying cement concrete 1:5:10 mix (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) upto haunches for pipes including bed concrete as per approved drawing and specification. 200 mm dia pipe |
| 333 | 250 mm dia pipe |
| 334 | 300 mm dia pipe |
| 335 | Construction of road gully chamber of the following sizes in brick work with bricks of class 75 in cement mortar 1 : 5 (1 cement : 5 find sand) necessary foundation concrete(1 : 4 : 8). Inside & outside plastering 12 mm thick with cement mortar 1 : 3 with a floating a coat of neat cement. Including the RCC top slab for fixing the grating including necessary excavation, dewatering, refilling, watering, ramming, removing, the surplus excavated material and making good the same complete as required. Cost shall be inclusive of providing, DI grating with frame.Internal size 450 x 450 x 600 mm deep; DI Grating with frame 450 x 450 mm |
| 336 | Providing and fixing stoneware gully trap of the following sizes in brick masonary chamber of standard design with first class bricks and trap to be set in cement concrete 1:2:4, both side 12mm thick plastering with floating coat of neat cement. Making necessary connections & providing water tight D.I. cover with frame of 300mm x 300mm internal size. The weight of cover & frame not be less than 8 kg as per standard design. Including necessary excavation, dewatering, refilling, watering, ramming and removing the surplus excavated material and making good the same complete as required. With Sewer bricks with 150 x 100mm size `P' trap |
| 337 | Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand) RCC top slab with 1:2:4 mix ( 1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) and outside plastering finished with a floating coat of neat cement making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per approved drawing and specification. Inside size 90x80 cms and 60 cms deep including CI cover/grating with frame (Light duty) 610x455mm internal diamesions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg) with FPS bricks. Manhole to be constructed With Sewer bricks |
| 338 | Inside size 120x90 cms and 90 cms deep including CI cover/grating with frame (Light duty) 610x455mm internal diamesions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg) with FPS bricks. Manhole to be constructed With Sewer bricks |
| 339 | Extra for depth for manholes: size 90x80 cm Manhole to be constructed With Sewer bricks |
| 340 | size 120x90 cm Manhole to be constructed With Sewer bricks |
| 341 | Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated on 12mm dia steel bar having minimun cross section as 23 mm x 25 mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and heaving manufacture\\"s permanent identification mark to be visible even after fixing \\" incluting fixing in manholes with 30x20x15 cm cement concrete block 1:3:6: (1 cement :3 coarse sand :6 graded stone aggregate 20mm nominal size )complete as per design. |
| 342 | Providing and executing reverse bore of rain water recharging comprising of rain water harvesting pit as per the the plumbing site plan drawing complete with PVC (6kg/cm2 )200 mm dia slotted pipe having having 3mm slot adequate size of bore filled with 3-6mm gravels,compete with bail plug at bottom. The reverse bore shall be upto 300mm above water level and the execution of some shall be in accordance RWH detailed sketch and conservation manual of CPWD .Govt. of India . The cost shall be inclusive of all necessary excavation in all kind of soils, refilling and disposal of surplus earth with in the site or away from site as directed with out any extra cost including required nos. 750 x 750 mm, Medium Duty, Wt : 125 kg, Ductile Iron cover with frame for Filter chamber. Filter Media shall be comprising of 300 mm thick 50-150 mm boulders, 300 mm thick 5-10 mm gravel and 300 mm thick coarse sand at the bottom of Pit below in 300 mm thick layer at the bottom of Filter chamber, below effective depth. All three layers shall be separated by G.I Wire Mesh screen of appropriate size. Size- 3X3X 2.5 mtr. water depth WD |
| 343 | Constructing Disiltling chamber/Oil Trap of brick work with bricks of class 75 with cement mortar 1:5 (1 cement:5 fine sand) plastering internal face with cement mortar 1:3 (1 cement: 3 fine sand and rough plaster on outer face with a floating coat of neat cement. R.C.C top slab with medium duty CI manhole cover and frame of 600 mm dia. The weight of cover to be not less than 58 kg & frame not be less than 58 kg as per standard design. Including excavation, dewatering, refilling, watering, ramming and removing the surplus excavated material complete as required. (All sizes are clear internal sizes). Depth shall be as per actual site condition and invert level. Size 1500 x 1000 x 1000 mm water depth (Total Depth shall be as per invert level of site) |
| 344 | Supply, installation , testing & commissioning Single/multistage monoblock pumping set with stainless steel CI stage casing and SS-304 impellers with stainless steel shaft and suction & discharge casing as per IEC standards , connected to TEFC ventilated induction motor of 2 pole, 2900 RPM, suitable for 400/440 Volts, 3 phase, 50 Hz A.C. supply with pressure gauge and with gunmetal isolation valves, vibration elimination pads etc. complete with base and frame, nuts and bolts.All valves, RCC foundations and foundation bolts shall be paid seperately under relevant heads as per requirement and as per instructions . The vender shall submit performance curve and technical data sheet to the consultant prior to installation. The head versus discharge curve shall be on the rising side. including termination of cables on motor. Head 20 M |
| 345 | Terrace Hydro-Pneumatic Water Supply Pumping SystemProviding, installing, testing and commissioning of automatic variable speed hydro-pneumatic water supply pumping system comprising 2 Nos. vertical multistage centrifugal pumps (1 Working + 1 Standby), each having a capacity of 2.0 LPS at 20 m Total Dynamic Head, complete with SS 304 impellers, diffusers, pump shaft and all wetted parts, mechanical seal, cast iron or stainless steel pump casing as per manufacturer's standard, directly coupled to IE3 energy-efficient TEFC squirrel cage induction motor suitable for 415 V ±10%, 3 Phase, 50 Hz AC supply. |
| 346 | Submersiable Centrifugal Non-clog Drainage Pump - Supply, installation, testing and commissioning of continuous duty submersible centrifugal non-clogging drainage/sewage pumps complete with 3 phase motor with all necessary protection and mechanical seal etc. complete with all ancillaries including float type level controllers, electrical control panels fabricated from 14 gauge CRCA sheet volt meter ammeter with selector switch, TPMCB, 5 VA CL : CTs, phase indicating lamps protected by 2 amp SP MCB, DOL starter, necessary wiring, cable alleys, earthing, interlocking, starter with Automatic float type level controller, providion of high level alarm, sequence timer, potential free contact to starter for connection to BAS, both pumps may run simultaneously at pre determind level. Location : Drainage Sump Pump Room |
| 347 | upplying, installing, testing and commissioning of electrically operated 2-way Solenoid Valve for water line at tank inlet for automatic filling/level control, of approved make, normally closed (NC) / normally open (NO) as required, suitable for potable water service, complete with valve body (brass/SS as specified), coil suitable for 230V AC, IP65 coil enclosure, minimum working pressure suitable for system, including strainer (where required), isolating valve before and after, unions/flanges, required fittings, support/clamps, wiring from local JB/level controller to solenoid coil, termination, testing, commissioning and making good, complete in all respects as per specifications and directions of Engineer-in-Charge. Size: _ mm (typically 25/32/40/50 mm). |
| 348 | PUMP CONTROLMinimum 4 level Multi level indicators with magnetic type sensor probes complete |
| 349 | Associated civil work for STP including foundation of pumps & equipment, M S structural work etc. is included in this scope Supply of all required Civil & Mechanical/Electrical shop drawings to be prepared by the contractor and approved by Project Manager.Contractor shall include all electrical mechanical items as required to operate the system automatically/ manually and also include in his rates level controller, electrical wiring cables earthing main control panel and connection to be various equipment’s, other accessories complete as required. Only main power supply with the earthing to be STP main control panel shall be provided by the owner through other agencies. STPshould follow all the concern Indian CPCB and Local norms and to be got approved from statuatory authority.Bypass arrangement shall be provided as shown in the drawings such that equalization tank pump can be used to pumpout sewage to external manhole incase of maintenance of STP. |
| 350 | Providing and fixing water closet squatting pan (Indian type W.C. pan) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS: 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests |
| 351 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer . |
| 352 | Providing and fixing HEP Nahni-trap of Indian make HCI 100x75mm 4 Kg |
| 353 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Semi rigid pipe32 mm dia |
| 354 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Rectangular shape 453x357 mm |
| 355 | Providing and fixing soil, waste and vent pipes :100 mm dia Centrifuggally cast iron(spun) socket & spigot (s&s)pipe as per IS 3989 |
| 356 | Centrifuggally cast iron(spun) socket & spigot (s&s)pipe as per IS 3989 |
| 357 | Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 ( 1 cement : 2 fine sand) in S.C.I./ C.I. Pipes : 75 mm dia pipe |
| 358 | 100 mm dia pipe |
| 359 | Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size),including cost of cutting holes and making good the walls etc. : For 100mm dia pipe |
| 360 | For 75 mm dia pipe |
| 361 | Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100 mm dia |
| 362 | Sand cast iron S&S as per IS - 3989 |
| 363 | Providing and fixing plain bend of required degree: 100 mm dia |
| 364 | Sand cast iron S&S as per IS - 3989 75 mm dia |
| 365 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. 100x100x100 mm |
| 366 | Sand cast iron S&S as per IS - 3989 75x75x75 mm |
| 367 | Providing and fixing single equal plain junction of required degree : 100x100x100 mm |
| 368 | Sand cast iron S&S as per IS - 3989 |
| 369 | Providing and fixing single unequal plain junction of required degree : 100x100x75 mm |
| 370 | Providing and fixing single equal plain invert branch of required degree : 100x100x100 mm Sand cast iron S&S as per IS - 3989 |
| 371 | Sand cast iron S&S as per IS - 3989 |
| 372 | Providing and fixing sand cast iron S&S off sets as per IS: 1729 114 mm off sets With 75 mm dia pipe |
| 373 | With 100 mm dia pipe |
| 374 | Providing and fixing terminal guard : 100 mm Sand cast iron S&S as per IS - 3989 75 mm |
| 375 | Sand cast iron S&S as per IS - 3989 |
| 376 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : 100 mm inlet and 100 mm outlet Sand cast iron S&S as per IS - 3989 |
| 377 | Sand cast iron S&S as per IS - 3989 |
| 378 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall 20 mm nominal dia Pipes |
| 379 | BRASS FITTINGSProviding and fixing brass bib cock of approved quality : 15 mm nominal bore |
| 380 | Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : 20 mm nominal bore |
| 381 | Providing and fixing rectangular high density polyethylene water storage loft tank with cover, conforming to ISI : 12701, colour of opaque white or as approved by Engineer-in-charge. The rate includes making necessary holes for inlet, outlet & over flow pipes. The base support Including fittings & fixtures for tank shall be paid separately |
| 382 | Transportation Charges of drilling equipment including assembly and other material as required. |
| 383 | Drilling of 675 mm. dia by rotary machine |
| 384 | Supply & laying of 350 mm. dia housing pipe (8 mm. thick) |
| 385 | Supply & laying of 200 mm. dia blind pipe (8 mm. thick) |
| 386 | Supply & laying of 200 mm. dia slotted pipe (8 mm. thick) |
| 387 | Supply & fixing of 350 mm. dia Socket |
| 388 | Supply & fixing of 200 mm. dia Socket |
| 389 | Supply & fixing of 200 mm. dia Bail plug |
| 390 | Supply & fixing of 350 mm. dia well cap |
| 391 | Supply & fixing of 350x200 mm. dia reducer. |
| 392 | Supply & fixing of 350 mm. dia housing clamp |
| 393 | Supply & Filling of pee gravel 2 mm. 4 mm. in side of bore after lower and development as required as per direction of E/I. |
| 394 | Development by air compressor including Transportation. |
| 395 | Development by O.P. Unit including Transportation. |
| 396 | Supply of submersible pump suitable for tube well capable of pumping clear and cold water free from chemical and directly coupled with electric moter operating of 415 volt suitable for 3 phase 50 cycle A.C. Supply of following duty condition: A - Discharge of water in LPM 860 Approx size of discharge outlet in 80 mm. B - Total Head of pump set 45 m. |
| 397 | Supply and fixing of finolex or equivalent ISI marked submersible copper cable of size 2x3x2.5 sq. mm. |
| 398 | Supply of control panel cubical type wall mounted vermin proof with internal wiring duly enameled painted and mechanically finished having L&T of qul. Male switch fuse unit with HRC fuses, Ameter, Boltmeter, Selector switch, phase indicating lamp with bulbs, instrument fuses, power capcitor single phase preventor etc. complete set with supply of Jyoti or eq. Air break Star- Delta motro starter suitable for above submersible pump set. |
| 399 | Supply of 80mm dia M.S. column pipe of class 'C' both and socketed with heavy sockets in 3/6 meter length and one end flanged complete with interlocking arrangements. |
| 400 | Supply of 80mm dia M.S. column pipe clamps with nut, bolts, packing etc. |
| 401 | Supply of 80mm dia C.I. double flanged ISI mark reflex valve of updadhya or equ. Make. |
| 402 | Supply of 80mm dia C.I. double flanged ISI mark sluice valve with hand wheel of upadhya or equ. Make. |
| 403 | Supply of C.I. double flanged bend of 80mm dia i/c cost of material and labour. |
| 404 | Supply of 80mm dia C.I. tee heavy quality i/c cost of material. |
| 405 | Supply of Guru/Fibing or equivalent make pressure gauge. |
| 406 | Erection & commissioning of pumping plants complete along with electric wiring. |
| 407 | Supply of steel wire rope of 1/2\\" size |
| 408 | S/B of 600mm x 600 mm x 6.0 mm G.I. plate vertically for earthing with its top at least 3 metres below ground level complete with 20mm dia G.I. pipe and funnel for watering and one earthing lead on one no. 8 to 10 SWG GI wite in 15mm dia G.I. pipe up to switch board (from appron to switch board the cost of G.I. , pipe and G.I. wire will be extra) 30 cm square C.I. frame with hinged cover masonry housing alternate layers of charcoal. coke and salt at least 150mm thick alround etc. as per directions of E/I complete in all respects as per drawing. |
| 409 | S/F of one number 8 to 6 SWG G.I. wire in 15mm dia G.I. Pipe for earthing, laid in ground or in wall duly concealed includingn the cost of cement, sand labour. T&P other material required for proper completion of the work as directed at site. |
| 410 | S/F of aluminium conductor PVC insulated armoured, served, sheathed cable 1100 volts grade at a depth of 750mm below ground level over a cushion of 75mm thick sand alround and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by E/I complete in all respects The armoring of the cable shall be properly connected with the earth conductor by clamps etc. 16 sqmm x 4 core |
| 411 | SUPPLYING INSTALLATION TESTING AND COMISSIONING OF SITTING BENCHES CURVED BENCH |
| 412 | CURVED BENCH WITH BACK REST |
| 413 | SUPPLYING INSTALLATION TESTING AND COMISSIONING OF OPEN GYM EQUIPMENTS ELIPTICAL CROSS TRAINER MACHINE |
| 414 | AIR WALKER / SKI WALKER |
| 415 | ROWING EXERCISE MACHINE |
| 416 | ARM SHOULDER EXERCISER TWO PEOPLE WHEEL MACHINE |
| 417 | TWO PEOPLE SITTING PUSHING AND PULLING EXERCISER MACHINE |
| 418 | DUAL AB BOARD MACHINE |
| 419 | BODY SHAPER |
| 420 | BICYCLE |
| 421 | SUPPLYING INSTALLATION TESTING AND COMISSIONING OF CHILDREN'S PLAY MULTI PLAY EQUIPMENTS INTEGRATED STRUCTURAL SYSTEMS CONTAINING A COMBINATION OF SLIDES, TUNNELS,CLIMBING LADDERS AND TOWERS UNDER ARCHITECTURAL CANOPY ROOFS |
| 422 | HEAVY DUTY STANDALONE MOTION EQUIPMENT BUILT WITH REINFORCED GROUND ANCHORING FRAMEWORKS TO ENDURE CONTINUOUS USAGE |
| 423 | FRP DOUBLE SEA SAW FEATURES HEAVY DUTY MILD STEEL STRUCTURAL FRAMING PAIRED WITH MODELED ANTI SLIP FRP SADDLE SEATS, RUBBER SAFETY BUMPERS, AND STEEL HAND GRIPS SUPPORTING UPTO 80 KG PER PERSON |
| 424 | FRP DUAL SEGREGATION SETUP WITH 'USE ME' LABELLED WASTE DUSTBINS ENGINEERED FOR PUBLIC PARKS AND PLAYGROUND ENVIRONMENTS, MANUFACTURED FROM ISOPTHALIC GELCOAT AND UV STABILIZED FIBERGLASS REINFORCED POLYSTER RESIN OF CAPACITY 120 LITRE (60 LITRESX2) |
| 425 | Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil. |
| 426 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) |
| 427 | Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand) |
| 428 | Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. 20 mm cement plaster. |
| 429 | Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement. 20 mm cement plaster. |
| 430 | Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate |
| 431 | Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100 mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick, 100 mm wide MS sheet duly painted over priming coat, reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc including cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge. |
| 432 | Supply, installation, testing and commissioning of AMCA Certified Tube Axial Smoke Exhaust Fan for basement ventilation and smoke management system, suitable for operation under normal ventilation and emergency smoke extraction mode in accordance with NBC 2016 (Part 4 – Fire & Life Safety) and latest amendments. The fan shall be of heavy-duty tube axial type comprising an aerodynamically designed steel casing with epoxy powder coated finish, high efficiency adjustable pitch cast aluminium aerofoil impeller, dynamically balanced as per ISO 21940, directly coupled to a high efficiency IE3 squirrel cage induction motor, suitable for 415 V ±10%, 3 Phase, 50 Hz AC supply, with IP55 protection, Class H insulation, and suitable for VFD operation. Basement-1: Tube Axial Smoke Fan (12500 CFM at 30mm static) |
| 433 | Basement-2: Tube Axial Smoke Fan (11500 CFM at 30mm static) |
| 434 | Basement-2: Tube Axial Fresh Air Fan(15200) CFM |
| 435 | 14000CFM/30 mm LIFT WELL Pressurization |
| 436 | 12500CFM/30 mm STAIRCASE Pressurization |
| 437 | Supply, Installation, Testing and Commissioning of Ductless Ventilation System / Jet Fans as per the specifications and layouts, suitable for Normal Ventilation and Smoke Extraction Application in case of emergency i.e. 250 to 300 Deg C for 2 Hrs operation. Each fan shall be complete with motor and impeller. The complete fan shall be certified as tested for 300 Deg C for 2 hours operation. The Motor shall be suitable for operation on 415±10% Volts, 50 Hz, 3 Phase AC power supply. (For Car Parking of Basement) |
| 438 | Supply, Installation, Testing and Commissioning of CO-Sensors at Basement Floor Car Parking |
| 439 | Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. Thickness 0.80 mm Sheet |
| 440 | Thickness 0.63 mm Sheet |
| 441 | Supply, Installation, Testing and Commissioning of GI volume control dampers complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. |
| 442 | Supply, installation, testing & balancing of factory made Bird screen made out of galvanized steel mesh in 20G having diamond pattern with GSS flanges and necessary cross bracings suitable for Fresh/ Exhaust air fans on terrace, complete as per specification & approved shop drawings. |
| 443 | Supply, Installation, Testing and Commissioning of flexible canvass cloth connection at oulet of each Ducted Indoor Unit with zipper to facilitate temperature measurement |
| 444 | Charges for Core Cutting / making opeing and repairing of walls for passing the Supply Air Ducting upto 0.50 Sqm size |
| 445 | Supplying, installation, testing & commissioning of addressable fire control module complete as required. |
| 446 | Providing & fixing of supports Consisting of Tie rods, Clamps, anchor bolts, angles for supporting the ductings complete as required including all labour T&P. |
| 447 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. Group C |
| 448 | Wiring for twin control light point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 449 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 450 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 451 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 452 | 4 X 10 sq. mm + 2 X 6 sq. mm earth wire |
| 453 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25mm |
| 454 | 32 mm |
| 455 | Supplying and fixing of following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 Amps switch |
| 456 | 3 pin 5/6 Amp socket outlet |
| 457 | 15/16 A switch |
| 458 | Telephone socket outlet |
| 459 | TV antenna socket outlet |
| 460 | Bell push |
| 461 | RJ- Data socket |
| 462 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 463 | Supplying and fixing of following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 module (100mmx 75mm) |
| 464 | 6 module (200mmx 75mm) |
| 465 | 8 module (125mmx 125mm) |
| 466 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 467 | Supplying and fixing suitable size GI box with modular plate and cover in front on wall or floor, including providing and fixing 3 pin 5/6 & 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 468 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, \\"C\\" curve including connections, painting etc. as required. |
| 469 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required |
| 470 | Supply and fixing of LED Tube Light with heavy duty Metal Box type Tube Light fitting 1x22 watt suitable for upto 1x 22 watt LED Polycarbonate tube light complete Including tube suitable for both surface & suspended complete in all respect |
| 471 | Supply and fixing of IP 20, Front Lit, Mid Power SMD type LED Light, recess Surface mounting round 18 Watt to 20 Watt, Cut out Min 150 mm, Height Min 40 min LED Down Lighter having Powder coated die cast aluminium housing with heat sink, High purity/transmisivity. UV Stabilized Non yellowish, diffuser/Reflector for uniform light distribution, detachable driver set, suitable for 24 Hr Continuous Operation, Complete in All respect. |
| 472 | Supply & fixing of water tight-oblong 10 watt LED Bulkhead luminaire having pressure die cast housing with driver set confirming, to IP65 and above protection, IK 08, High purity/transmisivity UV Stabilized Non yellowish diffuser/ for uniform light distribution, detachable driver set, open and short circuit protection, suitable for 24 Hr Continuous Operation, Complete in All respect, conipelete in all respec |
| 473 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor , unarmoured telephone cable in the existing surface/recessed steel /pvc conduit as required. 2 Pair |
| 474 | Supply, laying, testing and commissioning of 10 Pair x 0.5 sq.mm annealed solid copper conductor, PVC insulated, PVC sheathed, jelly-filled, armoured/unarmoured telephone cable conforming to TEC/BSNL specifications, suitable for indoor/outdoor installation, complete with excavation, sand cushioning, protective covering, warning tape, termination, ferruling, identification, testing and commissioning, complete as required. |
| 475 | Supply, laying, testing and commissioning of 20 Pair x 0.5 sq.mm annealed solid copper conductor, PVC insulated, PVC sheathed, jelly-filled, armoured/unarmoured telephone cable conforming to TEC/BSNL specifications, suitable for indoor/outdoor installation, complete with excavation, sand cushioning, protective covering, warning tape, termination, ferruling, identification, testing and commissioning, complete as required. |
| 476 | Supply, laying, testing and commissioning of 100 Pair x 0.5 sq.mm annealed solid copper conductor, PVC insulated, PVC sheathed, jelly-filled, armoured/unarmoured telephone cable conforming to TEC/BSNL specifications, suitable for indoor/outdoor installation, complete with excavation, sand cushioning, protective covering, warning tape, termination, ferruling, identification, testing and commissioning, complete as required. |
| 477 | Supplying and drawing co-axial TV cable RG-Grade , 0.7 mm solid copper conductor pe insulated shielded with fine tinned copper braid and protected with pvc sheath in the exsisting surface /reccessed steel /pvc conduit as required. |
| 478 | Supply, installation, testing and commissioning of Telephone Tag Block comprising 10-pair/20-pair/50-pair/100-pair Krone type IDC modules (as required), complete with back mounting frame, disconnection and test facility, jumper wires, identification labels, earthing arrangement, termination accessories and all necessary hardware. The tag block shall be suitable for terminating and cross-connecting telephone/data cables, mounted inside a powder-coated CRCA sheet steel enclosure with lockable hinged door, complete in all respects as required at site. |
| 479 | Supply, installation, testing and commissioning of passive TV signal splitter (2-way/4-way/8-way, as required) suitable for 5–1000 MHz (or higher) frequency range, die-cast zinc alloy housing with F-type connectors, low insertion loss, high isolation between ports, 75-ohm impedance, compatible with MATV/CATV systems, complete with mounting accessories, connectors, patch cords, earthing, and all necessary hardware for proper installation and commissioning, complete in all respects as required at site. Makes: Triax, Televes, Johansson, Spaun, Commscope or approved equivalent |
| 480 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/lsolator) 8way(4 +24),Doubledoor |
| 481 | 4way(4 +12),Doubledoor |
| 482 | Supply and fixing following way, single pole and neutral, sheet steel, MCB distribution board,240 v, on surface/recess,complete with tinned copper bus bar,neutral bus bar,earth bar,din bar,interconnection, powder painted including earthing etc. as required 6way, Double door |
| 483 | 12way, Double door |
| 484 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole |
| 485 | Supplying and fixing following rating, Four pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required |
| 486 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB),having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. As required. 25amps |
| 487 | 40amps |
| 488 | 63amps |
| 489 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray With perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. susp enders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 490 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 491 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 492 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 493 | 600 mm width X 62.5mm depth X 2.0 mm thickness |
| 494 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"bends\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 100 mm width X 50 mm depth X 1.6 mm thickness |
| 495 | 150 mm width X 50 mm depth X 1.6 mm thickness |
| 496 | 300 mm width X 62.5 mm depth X 2.0 mm thickness |
| 497 | 450 mm width X 62.5 mm depth X 2.0 mm thickness |
| 498 | 600 mm width X 62.5mm depth X 2.0 mm thickness |
| 499 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray \\"Tee\\" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 500 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 501 | Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness |
| 502 | 300 mm width X 50 mm depth X 1.6 mm thickness |
| 503 | Supply, installation, testing and commissioning of LED Aviation Obstruction Light (Low/Medium Intensity, as required) complete with die-cast aluminium housing, UV-stabilized polycarbonate lens, IP66 protection, high-intensity red LEDs with minimum 100,000 hours life, integral constant-current driver, surge protection, photocell for automatic dusk-to-dawn operation, flashing/steady burn operation as specified, suitable for 230V AC, 50Hz supply, complete with mounting bracket/base plate, GI hardware, junction box, earthing, wiring up to nearest junction box, and all accessories required for complete installation in accordance with DGCA, ICAO Annex 14 and applicable BIS/IEC standards. |
| 504 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 505 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 506 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 507 | Supply & fixing of following sizes of medium class PVC conduit along with accessories in surface / recessed including cutting the wall & making good the same in case of recessed conduit as required. 25mm |
| 508 | Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 Amps switch |
| 509 | 3 pin 5/6 Amp socket outlet |
| 510 | Telephone socket outlet |
| 511 | TV antenna socket outlet |
| 512 | Supplying and fixing of Stepped type 2 module electronic fan regulator on the existing modular plate & switch box including connections but excluding modular plate etc. as required. |
| 513 | Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. |
| 514 | Supplying and fixing of following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 1or 2 module (75mmx 75mm) |
| 515 | 8 module (125mmx 125mm) |
| 516 | Supplying & fixing 5 amps to 32 amps rating 240/415 volts, 10 kA, \\"C\\" curve Miniature Circuit Breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole |
| 517 | Supply & fixing of single pole blanking plate in the existing MCB DB complete etc. as required |
| 518 | Supplying & Fixing of following rating double pole (single phase and neutral) 240 volts, Residual Current Circuit Breaker (RCCB), having a sensitivity current upto 30 milli-amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 Amps |
| 519 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 520 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connection etc. as required. |
| 521 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 522 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 523 | Installation, Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 524 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 525 | Supply Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 526 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/6 A modular switch, connections etc. as required. |
| 527 | Earthing with G.I. earth plate 600 mm X 600 mm X 6mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 528 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc.with charcoal/ coke and salt as required. |
| 529 | Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 530 | Supply and laying of 25mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm) |
| 531 | LED Batten light (System lumen efficacy ≥120 <135 Im/Watt) Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS: 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P. F.≥0.95, IP20, CRI ≥80, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 Im/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). |
| 532 | Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum) |
| 533 | (A) Supplying Installation , testing and commissioning of electric driven Main Fire Pump suitable for automatic operation and consisting of following , complete in all respects , as required: (B) Horizontal type ,centrifugal pump of cast iron body & bronze impeller with stainless steel shaft , mechanical seal conforming to IS 1520. |
| 534 | 2280 lpm at 88m Head |
| 535 | 180 lpm at 88m Head |
| 536 | Poviding laying , testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/3589 i/c fitting like elbow, tees, flanges,tapers, nuts bolts , gaskets etc. in ground including welding excavations & providing cement concrete blocks as supports , anticorrosive tratment with coltar / asphalt tape as pr IS 10221, refilling the trench etc. of following sizes complete as required. 80 mm dia |
| 537 | 150 mm dia |
| 538 | Poviding laying , testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including welding ,fitting like elbow, tees, flanges,tapers, nuts bolts , gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint required shade complete as required : 25 mm dia |
| 539 | 32 mm dia |
| 540 | 40 mm dia |
| 541 | 50 mm dia |
| 542 | 65 mm dia |
| 543 | 80 mm dia |
| 544 | 100 mm dia |
| 545 | 150 mm dia |
| 546 | Supplying & fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Tpe- A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel |
| 547 | Supplying & fixing single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel , ISI marked conforming to IS 5290 (Tpe- A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel |
| 548 | Supply and Installation weather proof lockable cabinet of size not less than 900X600X450 mtr made out of 20gauge MS (as per BOQ) powder coated sheet of fully welded construction with hinged double front door partially glazed (3 mm glass panel).with locking arrangement, stove enamelled fire red paint (shade No. 536 of IS:5) including necessary locking arrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade. (External Cabinet). |
| 549 | Supplying ,fixing,testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with ns, bolts, washers,gaskets conforming ti IS 13095 of following sizes as required : 80mm dia |
| 550 | 100 mm dia |
| 551 | 150 mm dia |
| 552 | Supplying, installing, testing, and commissioning of Rising Spindle OS&Y Type Valves, PN16, Flanged type, Fully encapsulated EPDM Ductile Iron Wedge Disc, Stainless Steel Stem, Fusion Bond Epoxy Coated Interior and Exterior Surfaces, with required flanges, nuts, bolts, and gaskets, etc. complete. UL Listed and FM Approved. 80 mm dia |
| 553 | 100 mm dia |
| 554 | 150 mm dia |
| 555 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to educe pressure at the outlet to the level of 3.5kg/cm2 complete as required : |
| 556 | Providing , intalllation, testing and commissioning of non - return valve of following sizes conforming to IS : 5312 complete with rubber gasket, GI bolts, nuts, washers etc. as required: 80 mm dia |
| 557 | 100 mm dia |
| 558 | 150 mm dia |
| 559 | Providing , intalllation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stailnless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 100 mm dia |
| 560 | 150 mm dia |
| 561 | 200 mm dia |
| 562 | Providing, fixing, testing & commissioning of: installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as requir 80 mm dia |
| 563 | 100 mm dia |
| 564 | 150 mm dia |
| 565 | Providing, fixing, testing & commissioning of resilient rubber bellows single arch vibration eliminators suitable for raw water up to 45 deg. C temperature, working pressure 8.5 Kg/cm2 and test pressure 14 Kg/cm2 to provide relief from stresses at pipe flanges. It should be complete as per manufacturer's specifications & as 80 mm dia |
| 566 | 100 mm dia |
| 567 | 150 mm dia |
| 568 | Providing fixing, testing & commissioning of installation control valve of cost iron body , brass/bronze working parts comprising of water motor alarm , bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates , pressure gauges, emergency releases , stainer, pressure switch, cock valve complete with drain valve and bypass , test control box, ball valves, MS pipe of required size, flanges,orifice plate, gasket etc of following sizes as required : 150 mm dia |
| 569 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Stainless Steel (Grade 304) |
| 570 | Supplying and fixing first - aid Hose Reel with MS construction spray painted in post office red, conforming ti IS 884 complete with the following as required :20 mm nominal internal dia water hose thermoplastic (Textile reinforced ) type-2 as per IS: 12585 30 m |
| 571 | Supplying and fixing 63 mm dia, gun metal short branch pipe with 20 mm nominal internal diameter size nozzle confoming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304) |
| 572 | Supplying and fixing of fire brigade connection of cat iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way -100 mm dia M.S. Pipe |
| 573 | 2 way -100 NB M.S. Pipe |
| 574 | Providing fixing, testing & commissioning of 15 mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler |
| 575 | Upright Sprinkler |
| 576 | Horizontal side wall spirinkler |
| 577 | Providing and fixing of pressure switch in M.S. pipe line including connection etc. as required : |
| 578 | Providing and fixing flow switch in following sizes pipe including connection etc. as required : 100 mm dia |
| 579 | 150mm dia |
| 580 | Supplying , installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer , nipple, 2 side bracket, stockbar of following sizes complete as required. 1200 mm dia |
| 581 | Providing installation , testing & commissioning of welectric release trim assembly for deluge wall with two way solelnoid valve ,weather proof operation on 24 volts DC supply complete as required. |
| 582 | Providing and fixing standard fire mans axe with heavy duty insulated rubber handle. |
| 583 | Supply and fixing of CO2 type Fire extinguisher 4.5kg. Capacity (ISI Marked is :15683)Complete with initial Charge and wall Bracked along with supply of all materials and labour for proper completion of work. |
| 584 | Supply and fixing of fire extinguisher, ABC Type 6.00 kg. capacity (ISI Marked IS : 15683 & TAC approved) complete with initial charge and wall bracket, along with supply of all materials and labour for proper completion of work. |
| 585 | Providing of FHC Door made of 16 gauge MS Sheet with frame of size 105x70mm complete door and frame assembly including all hardwares (Concealed Flush handle,Allen Key Lock, MS Hinges, 5mm Thick Float glass) & accesories . The door to be painted with fire resistance paint. The scope shall also include the painting of the frame with the same paint as the shutter or complete as per direction of Engineer-in-charge.(Approx. size of door: 900mm Wide & 1500mm Height) |
| 586 | Providing and fixing Fire related signages printed on photoluminescent U1000 aluminium sheet of 1.0 mm (+-10%) containing Lumigen II as base chemical, covered under UV stablized coating and of appropriate size including fixing on wall, door, ceiling etc. with proper clamps, hangers, cleats, anchor fasteners etc. complete in all respects as directed by Engineer-in-charge. |
| 587 | Supply, installation, testing,& Commisioning of 50 kg water pressure type extinguisher . |
| 588 | Providing and fixing dial type SS pressure gauge with isolation cock and copper pipe on main header Dial diameter 100 mm calibration 0-14 / sq. cm.It should be complete as per manufacturer's specifications & as directed by Engineer- in-charge. |
| 589 | SITC of Indoor type hose cabinet hose cabinets fabricated from 16 g M.S sheet with full glass door and locking arrangement,suitabletoaccommodate 2 nos. 15 m long hoses and 1-no. branch pipe. the cabinet shall be painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and shall be suitably mounted on a raised masonry platform as required. exact size & shape shall be as per site conditions and prior approval. |
| 590 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5 % V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System) and shall be complete with all accessories. The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specification |
| 591 | Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed temperature thermistor complete with base as required. |
| 592 | Supplying, installation, testing & commissioning of intelligen analog addressable photothermal(smoke) detector complete with mounting base complete as required. |
| 593 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 594 | Supplying, installation, testing & commissioning of addressable fire control module complete as required |
| 595 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 596 | Supplying, installation, testing & commissioning of fault isolator complete with base as required. |
| 597 | SITC of Intelligent Addressable, Supervised Monitor Module monitoring Potential-free, Normally Open Dry Contact input. The Monitor Module shall have operating temperature range from 0°C to 70°C and a humidity tolerance of up to 93% RH, Non-Condensing with weatherproof enclosure |
| 598 | Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required. |
| 599 | Supplying, installation, testing & commissioning of 6 zone, voice alarm controller with USB, MP4 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required |
| 600 | Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required. |
| 601 | Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required. |
| 602 | Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and inter connections etc. as required. speaker cable Two pair, 2-core, 1.5 sqmm |
| 603 | Supplying and fixing 25 mm dia MS flexible pipe with PVC coating along with all ancillaries and accessories like coupler etc. as required. |
| 604 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. |
| 605 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required |
| 606 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 607 | Supply & fixing of following sizes of medium class PVC conduit along with accessories in surface / recessed including cutting the wall & making good the same in case of recessed conduit as required. |
| 608 | Supplying and fixing of following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 Amps switch |
| 609 | 15/16 Amp switch |
| 610 | 3 pin 5/6 Amp socket outlet |
| 611 | Supplying & fixing 5 amps to 32 amps rating 240/415 volts, 10 kA, \\"C\\" curve Miniature Circuit Breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 612 | Supply & fixing of single pole blanking plate in the existing MCB DB complete etc. as required |
| 613 | Supplying & Fixing of following rating double pole (single phase and neutral) 240 volts, Residual Current Circuit Breaker (RCCB), having a sensitivity current upto 30 milli-amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 614 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 Amp modular socket outlet and 5/6 A modular switch, connection etc. as required. |
| 615 | Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. |
| 616 | Supplying and fixing brass batten/ angle holder including connection etc. as required. |
| 617 | Installation, Testing, Commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required. |
| 618 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored) |
| 619 | Supply Installation, Testing and Commissioning of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep |
| 620 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/6 A modular switch, connections etc. as required. |
| 621 | Earthing with G.I. earth plate 600 mm X 600 mm X 6mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 622 | Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 623 | Supply and laying of 25mm x 5mm copper strip at 0.50 meter below ground as strip earth electrode including connection / terminating with nut ,bolt spring washer etc. jointing shall be done by overlaping and with 2 sets of brass nut bolt&spring washer spaced at 50mm) |
| 624 | Supply, installation, testing and commissioning of 12 kV, 3-way extensible Ring Main Unit (RMU) suitable for 11 kV, 3-phase, 50 Hz distribution system, metal enclosed, factory assembled, indoor/outdoor type, IP54 or higher protection, with one (1) 630 A Load Break Switch (LBS) incoming feeder and two (2) 630 A Vacuum Circuit Breaker (VCB) outgoing feeders, rated 630 A continuous current, 21 kA for 3 seconds short-time withstand current, 52.5 kA peak withstand current, 28 kV power-frequency withstand voltage (1 min) and 75 kV lightning impulse withstand voltage, conforming to IEC 62271-200/100/102, IS/IEC standards and CEA Regulations. The RMU shall be suitable for future extensibility and complete with SF₆ sealed-for-life gas tank or solid insulated technology, maintenance-free switching mechanism, mechanical ON/OFF/EARTH position indication, padlocking facility, interlocks, mimic diagram, cable test points, voltage presence indicating system (VPIS), fault passage indicator (where specified), local control, spring-operated mechanism, anti-reflex handle, and cable termination compartment suitable for XLPE cables. |
| 625 | Supply, installation, testing and commissioning of 630 kVA, 11/0.433 kV, outdoor type, oil immersed, naturally cooled (ONAN), copper wound distribution transformer with conservator tank, 3-phase, 50 Hz, Dyn11 vector group, conforming to IS 1180 (Part 1): 2026, BIS certified and BEE Star Rated as applicable. The transformer shall be complete with conservator fitted with magnetic oil level gauge (MOG), silica gel breather, Buchholz relay, pressure relief device (PRD), off-circuit tap changer (±5% in 2.5% steps), HV & LV porcelain bushings, thermometer pocket, oil temperature indicator (OTI), drain and filter valves, air release plug, sampling valve, marshalling box, bi-directional rollers, lifting lugs, cable boxes, two independent earthing terminals, rating and diagram plate, mineral insulating oil and all standard accessories. The item shall include factory routine tests, site testing, commissioning and submission of all test certificates complete as required. |
| 626 | Supply, installation, testing and commissioning of 250 kVA, 11/0.433 kV, outdoor type, oil immersed, naturally cooled (ONAN), copper wound distribution transformer with conservator tank, 3-phase, 50 Hz, Dyn11 vector group, conforming to IS 1180 (Part 1): 2026, BIS certified and BEE Star Rated as applicable. The transformer shall be complete with conservator fitted with magnetic oil level gauge (MOG), silica gel breather, Buchholz relay, pressure relief device (PRD), off-circuit tap changer (±5% in steps of 2.5%), HV & LV porcelain bushings, thermometer pocket, oil temperature indicator (OTI), drain and filter valves, air release plug, sampling valve, marshalling box, bi-directional rollers, lifting lugs, cable boxes, two independent earthing terminals, rating and diagram plate, mineral insulating oil, and all standard accessories. The item shall include factory routine tests as per IS 1180 and IS/IEC 60076, site testing, commissioning, submission of all routine test certificates, foundation bolts, first filling of transformer oil, and all labour, tools, tackles and materials required for complete installation, complete in all respects as required. |
| 627 | Providing and constructing RCC/PCC for RMU & TRANSFORMER foundation/plinth of approved dimensions, minimum 300 mm above finished ground level or above the highest flood level, whichever is higher, including excavation, PCC, RCC, reinforcement, shuttering, cable trenches, sleeves, embedded channels, waterproofing and finishing, complete as per approved OEM foundation drawing. |
| 628 | Supply and Laying of 3 core stranded Aluminium Conductor XLPE (Cross linked polyethylene) insulated PVC bedded, galvanized flat steel strip armoured cables confirming to I.S. 7098 (Part II with latest amendments) 11 KV grade at a depth of 900 mm below ground level over a cushion of 100mm thick fine rever sand all around and protected with well burnt bricks on sides and on top put across as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 185 sqmm 3 core |
| 629 | Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVCsheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 630 | Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 185 sqmm |
| 631 | Supplying, installation, testing and commissioning of factory-assembled, silent-type diesel engine generating set of 380 kVA prime rating at 0.8 power factor, 415 V, 3-phase, 4-wire, 50 Hz and 1500 rpm, suitable for individual and parallel operation, comprising turbocharged and after-cooled, water-cooled diesel engine with electronic governor conforming to ISO 8528 Class G3 performance; brushless alternator with PMG excitation, digital AVR with three-phase RMS sensing, two-thirds pitch winding, Class-H insulation with temperature rise limited to Class-F, minimum IP23 protection, star-connected winding with neutral brought out, low sub-transient reactance and suitability for nonlinear loads comprising chiller VFDs, lift drives, UPS systems and LED lighting. The net output after considering ambient-temperature, altitude, auxiliary-power and nonlinear-load derating shall not be less than 750 kVA. The DG set shall comply with applicable IS/IEC standards and the latest CPCB emission and noise regulations, complete with common base frame, anti-vibration mountings, engine-mounted radiator suitable for 50°C ambient, starting batteries, automatic battery charger, fuel filters, air filters, lubricating-oil filters and all standard accessories. |
| 632 | Supply, installation, testing and commissioning of floor-mounted, front-operated, compartmentalized, automatic DG Synchronizing and Load Sharing Panel suitable for synchronizing, paralleling, automatic load sharing and load management of 2 Nos. 380 kVA, 415 V, 3-phase, 4-wire, 50 Hz DG sets, fabricated from minimum 2.0 mm thick CRCA sheet steel, powder-coated, minimum IP54 protection, complete with 1250 A TPN high-conductivity electrolytic aluminium busbars of adequate short-circuit withstand capacity, suitably rated neutral and earth busbars, cable alleys, gland plates, internal wiring, control terminals, space heaters, illumination, engraved labels and all accessories. Panel shall be designed and type-tested in accordance with IEC/IS 61439, complete as required. |
| 633 | Supply and Laying of Aluminium Conductor PVC insulated armoured served sheathed cables 1100V grade at a depth of 750mm below ground level over a cushion of 75mm thick sand all around and protected with burnt bricks on sides and on top as directed by Engineer in Charge complete in all respect including excavation and refilling. The armouring of the cable shall be properly connected with the earth conductor by clamps 6 sq. mm 2 core etc. |
| 634 | 10 sq. mm 2 core |
| 635 | 25 sq. mm 3.5 core |
| 636 | 35 sq. mm 3.5 core |
| 637 | 50 sq. mm 3.5 core |
| 638 | 95 sq. mm 3.5 core |
| 639 | 120 sq. mm 3.5 core |
| 640 | 185 sq. mm 3.5 core |
| 641 | 240 sq. mm 3.5 core |
| 642 | 300sq. mm 3.5 core |
| 643 | 400 sq. mm 3.5 core |
| 644 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kv grade as required. 6 sq. mm 2 core |
| 645 | 10 sq. mm 2 core |
| 646 | 25 sq. mm 3.5 core |
| 647 | 35 sq. mm 3.5 core |
| 648 | 50 sq. mm 3.5 core |
| 649 | 95 sq. mm 3.5 core |
| 650 | 120 sq. mm 3.5 core |
| 651 | 185 sq. mm 3.5 core |
| 652 | 240 sq. mm 3.5 core |
| 653 | 300sq. mm 3.5 core |
| 654 | 400 sq. mm 3.5 core |
| 655 | Design, fabrication, supply, installation, testing, and commissioning of floor-mounted, front-access, modular LT power distribution panel, suitable for 433 V, 3-phase, 4-wire, 50 Hz system, rated for 1250A, fully compartmentalized, IP54 rated, fabricated from 2.0 mm CRCA sheet steel, powder-coated (RAL7035), conforming to IEC 61439, complete in all respects with Aluminum busbar system rated for 1600A at 40°C, short-circuit withstand of 50 kA for 1 sec, including: |
| 656 | Supply, installation, testing and commissioning of floor-mounted, indoor/outdoor, IP54, cubicle type, powder-coated CRCA sheet steel LT Meter Distribution Panel suitable for 415 V, 3-phase, 4-wire, 50 Hz AC supply, fabricated from minimum 2.0 mm thick CRCA sheet with 3 mm gland plate, complete with aluminium busbars of suitable rating, neutral and earth busbars, cable alley, interconnections, danger notice, engraved labels, hardware, base frame, and all accessories as required. |
| 657 | Supply, installation, testing, and commissioning (SITC) of the Main Common Panel fabricated strictly as per IEC 61439 standards. The scope includes factory testing, packing, transport, transit insurance, unloading at site, and shifting to the electrical room. The contractor is responsible for civil foundation anchoring, module coupling, and internal torque-tightening of busbars using torque wrenches.Testing and Commissioning Scope specifically includes: Insulation Resistance (Megger) tests, High Voltage (HV) die-electric tests, and busbar contact resistance tests. All Numerical Protection Relays must undergo Secondary Injection Testing using calibrated relay test kits to verify and calibrate IDMT curves, Overcurrent/Earth Fault pick-up values, and time-dial settings. Testing of Master Trip Relay (86) and Trip Circuit Supervision (74) logic must be practically simulated. Final commissioning includes functional handshake testing, provision of as-built single-line diagrams (SLD), relay setting charts, and obtaining final statutory clearance from the Electrical Inspectorate.\\"* |
| 658 | Supplying, installation ,testing and commissioning of LT switchgear panels(Common panel) suitable for 433 V. 3 phase. 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. |
| 659 | Supplying, installation ,testing and commissioning of LT switchgear panels(Common panel) suitable for 433 V. 3 phase. 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. |
| 660 | 1 No. of 630 AMP, 4-Pole MCCB with microprocessor-based electronic trip unit (LSIG) having adjustable Long Time, Short Time, Instantaneous and Ground Fault protection, ON, OFF & TRIP status indication, shunt trip, under-voltage release, control MCB, suitable for receiving supply from an external 300A Automatic Transfer Switch (ATS), complete with all accessories, cable entry provisions and spreader links as required. |
| 661 | Design, Supply, Installation, Testing & Commissioning of 150 kVAR APFC Panel, floor mounted, IP42, CRCA construction, powder coated with Aluminum busbars and sectionalized chambers. Digital Microprocessor-based APFC Controller with 12/14 step operation, auto/manual mode and THD blocking functionality. |
| 662 | BASEMENT PANEL- |
| 663 | Supplying & Installation, testing and commissioning of STP panel of the following cubicle type indoor mounting Powder coated, modular compartmentalized IP 42, dead front, dust and vermin proof, floor mounting 2 mm thick sheet steel clad switchboard suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level of 35 MVA at 415 volts. (50 kA) with indication lamps; accessories etc. as required and complete with following incoming and outgoing switchgears with protection and metering and etc. as per specification and schematic diagram. |
| 664 | Supplying & Installation, testing and commissioning of Plumbing panel of the following cubicle type indoor mounting Powder coated, modular compartmentalized IP 42, dead front, dust and vermin proof, floor mounting 2 mm thick sheet steel clad switchboard suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to withstand a symmetrical fault level of 35 MVA at 415 volts. (50 kA) with indication lamps; accessories etc. as required and complete with following incoming and outgoing switchgears with protection and metering and etc. as per specification and schematic diagram with |
| 665 | Supply, Installation, Testing and Commissioning (SITC) of floor mounted, indoor type, free-standing PLC/DDC based Terrace Pressurization Control Panel fabricated from 2.0 mm thick CRCA sheet steel, powder coated finish, IP-54 degree of protection, complete with suitably rated incomer MCCB with adjustable Thermal Magnetic/Electronic release, aluminium/copper busbars of adequate capacity, outgoing MPCBs/MCCBs, contactors, control relays, PLC/DDC controller, 24 V DC SMPS, colour HMI, digital multifunction meter with Class 1.0 CTs, voltmeter, ammeter, phase indication lamps, terminal blocks, control transformer, internal FRLS copper wiring, cable alleys, gland plates, space heater with thermostat, cooling fan, earthing terminals and all accessories required for satisfactory operation. |
| 666 | Supply, Installation, Testing and Commissioning (SITC) of floor-mounted, indoor type, free-standing PLC based Basement Ventilation Control Panel fabricated from 2.0 mm thick CRCA sheet steel, powder coated, IP-54 protection, complete with suitably rated aluminium, incomer MCCB of required rating with adjustable Thermal Magnetic/Electronic release, outgoing MCCBs/MCBs, contactors, MPCBs, control transformers, PLC (Siemens S7-1200/Schneider M221/Allen Bradley Micro 850 or approved equivalent), colour HMI, 24 V DC SMPS, interposing relays, timers, terminal blocks, internal FRLS copper wiring, engraved labels, gland plates, earthing terminals, space heaters with thermostat, cooling fan and all accessories required for satisfactory operation. |
| 667 | Fabrication, supply, Insallation testing & commissioning of Electrical FIRE Panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required : |
| 668 | Supply installing testing & commissioning of out door type street light feeder pillar (Distribution Panel) compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated complete as required with following incomming & outgoing as per detail below. |
| 669 | Supply and fixing of 6 mtr. G.I. Octagonal pole of approved make (top dia 70 mm, Bottom dia 130 mm & Base plate 12 mm thick) having 3 mm, thickness with double arm bracket length of 1 mtr. length in 1:2:4 RCC foundation bolt including the cost of foundation, excavation & back filling and Required T & P complete in all respect. |
| 670 | Supply and fixing of LED Street light Fitting with mandatory driver set, having, die cast aluminium body with loughend glass UV stabilized PC Cover and lenses suitable for 45 Watt. to 50 Wart, Confirming to IP. 66, and IK07, and above, protection having Company LOGO Engraved complete in all respect including Labour |
| 671 | Supply, installation, testing and commissioning of complete Automatic Boom Barrier and RFID-based Vehicle Access Control System, suitable for vehicular entry/exit control, comprising 6.0 metre boom barrier with painted galvanized steel weatherproof housing, 24 V DC geared motor, inbuilt electronic control unit, manual release arrangement, boom opening/closing time not exceeding 4–5 seconds, suitable for 230 V AC, 50 Hz supply, approximately 350 W power consumption, minimum 100 cycles/hour duty and minimum IP44 protection, complete with boom arm, balancing mechanism, foundation/base plate, mounting hardware and boom support/rest stand. |
| 672 | Earthing with G.I. earth pipe 4.5 Meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
| 673 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 674 | Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm) |
| 675 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required. |
| 676 | Supply and laying of 25mm x 5mm G.I. strip from earth electrode directly in the ground as required complete in all respect. |
| 677 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required. |
| 678 | Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as required. |
| 679 | Jointing copper/G.I. tape (with another copper/GI tape, base of the finial or any other metallic object) by riveting/ nut bolting/ sweating and soldering etc as required. |
| 680 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run) |
| 681 | Fixing of copper/ G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run) |
| 682 | Supply, laying, testing and commissioning of Green colour FRLSH insulated copper Protective Earth (PE) conductor of __ sq.mm size, stranded, 1100 V grade, conforming to IS 694, complete with terminations using tinned copper lugs, glands, ferrules, clamps, identification and continuity testing, laid in existing/proposed conduit, cable tray or trunking, complete as required. |
| 683 | Supply, installation, testing and commissioning of Main Earthing Terminal (MET) comprising a high-conductivity electrolytic copper earth bar of minimum 50 mm × 6 mm (or size as indicated in drawings), complete with minimum 12 Nos. tinned copper termination studs of M10 size with brass nuts, bolts, spring washers and flat washers, mounted on non-hygroscopic insulated supports within a powder-coated CRCA sheet steel enclosure having transparent hinged cover with lock and key. The MET shall be provided with engraved identification labels for incoming earth from earth grid, transformer body earth, neutral earth, DG earth, lightning protection earth, panel earth, cable tray earth, equipment earth, structural steel earth, UPS earth, IPS earth and spare terminals. The earth bar shall be complete with all fixing accessories, gland plate, earthing symbol, danger notice, interconnecting links, testing, continuity measurement and commissioning, in accordance with IS 3043, IEC 60364, CEA Regulations and NBC, complete in all respects as required. |
| 684 | Supply, installation, testing and commissioning of Floor Supplementary Earth Bus Bar (SEBB) comprising high-conductivity electrolytic copper bus bar of minimum size 25 mm × 6 mm (or as specified in drawings), complete with minimum 8 Nos. tinned copper M8/M10 termination studs with brass nuts, bolts, flat and spring washers, mounted on DMC/SMC insulated supports inside a powder-coated CRCA sheet steel enclosure with hinged lockable door. The bus bar shall be connected to the Main Earthing Terminal (MET) through an insulated copper PE conductor of specified size and shall provide dedicated termination points for panel earth, cable tray earth, equipment earth, DB earth, conduit earth, metallic piping bonding and other protective equipotential bonding conductors. The item shall include all fixing accessories, identification labels, danger notice, glands, lugs, ferrules, continuity testing and commissioning, complete in all respects in accordance with IS 3043, IEC 60364, CEA Regulations and NBC. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 05, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysDec 07, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 19 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender