Housing Urban and Rular Development Government Departments Closing in 6 days TDR #58448975

Tender For Repair Work And Electricity Related Work At Govt. M.S. College Bikaner (Ew)

Issued by Government Departments · Bikaner, Rajasthan
Tender Value
14.24 Lakhs
Estimated cost
Bid Submission
16 Nov 2026
6 days left
EMD
28480
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bikaner → Rajasthan
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair Work And Electricity Related Work At Govt. M.S. College Bikaner (Ew)

BOQ

Name of Work:- Repair work and electricity Related work at Govt. M.S. College Bikaner (EW)
Sl. No. Item Description
1Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required.
2Short point (up to 3 mtr.)
3Medium point (up to 6 mtr.)
4Long point (up to 10 mtr.)
5Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required.
6On board
7S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required.
820 mm
925 mm
10Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required.
112 x 2.5 sq. mm. + 1x1.5sqmm
122 x 4.0 sq. mm. + 1 x 2.5 sq. mm.
131 x 4.0 sq.mm
144 x 10.0 sq.mm
15Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required.
16Single pole MCB (With B / C curve tripping characteristics)
176 A to 32 A rating
18Double pole MCB (With B / C curve tripping characteristics)
1950/63 A rating
20Triple pole MCB (With B / C curve tripping characteristics)
2150/63 A rating
22Four pole MCB (With B / C curve tripping characteristics)
2350/63 A rating
24Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required.
25Metal door (single phase) IK-09 and IP-43 with Metal end box
268 Way
2712 Way
28Metal door (Three phase) IK-09 and IP-43 with Metal end box
296 Way (8 incomer + 18 Outgoing)
30Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for 3/4 pole MCCB and SP / TP MCB up to 63 Amps. as outgoing ,made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. complete with insulated 125/160/200/250 Amp. copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required.
31Double door IP-43 & IK-09 with Provision of Incomer MCCB up to 125 A Rating with Metal end box
326 Way
33P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required.
34P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required.
35Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required.
36Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required.
37Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required.
38Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required.
395 step fan regulator 2 Module
40Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required.
41Modular MCB 6 A to 32 A SP
42Providing & Fixing of following size cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect.
433 Module
4412 Module
45Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required.
463 Module
4710-12 Module
48SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:-
49(a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided
50(b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire.
51[c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra )
52(d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram.
53(e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging.
54(f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra )
55(g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out.
56(h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted)
57Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves.
58Electrolytic grade Aluminium bus bar 6010 grade
59Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.
60Three phase AMP + HZ + PF + KW + KVA + KVAR + KVARH+KWH+DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS Meter
61Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required .
62Ring type tape wound CT
63C T Class 1, Ratio 200/5 to 600/5, Burden 10 VA
64SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate.
654 pole MCCB With Thermal Magnetic release
66up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting,
67125 Amp , 25 kA, adjustable O/L & Fixed S/C setting,
68400 Amp , 35 kA, adjustable O/L & adjustable S/C setting,
69Providing & Fixing of bus bar chamber housed in sheet metal box Confirming to IEC-60439/ IS-8623 & IEC-60529/ IS-2147 made out from 1.6 mm thick powder coated CRCA sheet,degree of protection IP-31 front openable bus bar made out of aluminium or wrought aluminium alloy suitable for 200 amp. Capacity , bus bar fixed on porcelain/DMC insulators at approved spacing including making connections etc. as required.
70600 mm long , 4 strip
71Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size.
7210.0 Sq. mm
732 core
7435.0 Sq. mm
753.5 core
7670.0 Sq. mm
773.5 core
78120.0 Sq. mm
793.5 core
80Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth.
81Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size.
8210.0 Sq.mm
8316.0 Sq.mm
8425.0 Sq.mm
8570.0 Sq.mm
86120.0 Sq.mm
87P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra).
8850 mm
89SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :-
90(a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole
91(b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7
92© Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt
93(d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm.
94(e) Testing of earth resistance for value of 5 ohms or less as required.
95(f) Test certificates for confirming above standards from OEM is mandatory.
9617.2 mm thick and 3 Mtr. Long
97Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required.
9810 SWG G.I. ( Hot Dipped ) Wire
99Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra)
10065 mm dia.
101Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required.
1021200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 )
103SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required.
1041170mm(+/-10%) LED batten with min. lumen output 2200 lm , 20W
105Add 18% GST Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58448975
AUTHORITY Government Departments
TENDER VALUE 14.24 Lakhs
LAST DATE 16-11-2026
Authority
Authority Name Public Works Department
Work Description Tender for Repair Work And Electricity Related Work At Govt. M.S. College Bikaner (Ew)
Basic Detail
Tender No E NIT NO 41/2026-27 EE PWD ELECTRIC DIVISION BIKANER
Bidding Type Tender
Location
City Bikaner
State Rajasthan
Key Dates
Publish Date 09 Nov 2026
Submission Date 16 Nov 2026
Open Date 17 Nov 2026
Finance
Tender Value 14.24 Lakhs
Tender Fee 500
EMD 28480
Exemption Available
Document List
0f4a0267-c88c-486b-b3c3-678586a1bb18.html
BOQ_1074058.xls
Newtermandconditiion.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 09, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 16, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 6 days
Nov 17, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 7 days

Tender Documents

Download All (ZIP) ↓
html

0f4a0267-c88c-486b-b3c3-678586a1bb18.html

xls

BOQ_1074058.xls

pdf

Newtermandconditiion.pdf

pdf

Tendernotice_1.pdf

Disclaimer