Housing Urban and Rular Development Government Departments Closing in 11 days TDR #58446501

Tender For Construction Of Class 3 & 4 Employees Houses In New Rajindra Hospital At Patiala Punjab. (External Services Only)

Issued by Government Departments · Patiala, Punjab
Tender Value
1.12 Crore
Estimated cost
Bid Submission
23 Nov 2026
11 days left
EMD
2.25 Lakhs
Bank guarantee accepted
Document Fee
10000
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Patiala → Punjab
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Construction Of Class 3 & 4 Employees Houses In New Rajindra Hospital At Patiala Punjab. (External Services Only)

BOQ

Name of Work:- Construction of Class 3 & 4 Employees houses in New Rajindra Hospital at Patiala Punjab. (External Services only)
Sl. No. Item Description
1Cost of Campus Lighting SystemPVC INSULATED FR COPPER CONDUCTOR CABLES:Supply and erection of PVC insulated PVC sheathed (3 core) round flexible wire with copper conductor (FR) cable (ISI marked) confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:-Overall size 1.5sq.mm (48/0.20mm), 3Core
2XLPE INSULATED UN-ARMOURED CABLES (LOOSE):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:-Overall size 10sq.mm (4Core) Un-armoured (Loose)
3Overall size 16sq.mm (4Core) Un-armoured (Loose)
4GALVANIZED IRON PIPES AND G.I. EARTHINGEarthing earth rod 20 mm dia for providing earth connections upto line earth with G.I. Wire 8 S.W.G. (4mm dia.). The rod shall be tapered at one end and flatted on other end. The hole size 10mm dia shall be drilled on the flatened side for facilitating connection with G.I. wire and thimble etc. The rod shall be erected in ground upto complete length vertically:-GI Earth rod 20 mm dia., 3 mtr. Long
5GALVANIZED IRON PIPES AND G.I. EARTHINGSupply & erection of G.I. pipe (A-Class) as per IS:1239 (Part-I) 2004 including sockets, bends, inspection boxes, Steel hooks, GI saddle clamps and other petty materials etc., where necessary including painting as per PWD General Specifications:-Galvanized Iron Pipe 50mm dia. (A-class) Flushed
68 SWG COPPER EARTHING :Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 10.50 metre (34.44 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 9metre long
7MINIATURE CIRCUIT BREAKERS/ RCBO's/ RCCB's:MINIATURE CIRCUIT BREAKERS:Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- MCB Single Pole 6-32amp. (10kA, Curve-C)
8MCB Double Pole 40amp. (10kA, Curve-C)
9SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's:Supply and erection of sheet metal Double Door Distribution Boards IP 43-IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- SP&N Double Door Distribution Board 8 way each
10SHEET METAL BUS BAR CHAMBERS (COPPER STRIPS):Supply and erection of sheet metal bus-bar chamber (factory fabricated) duly powder coated on existing surface with required 4Nos. of tin plated copper bus-bar strips of suitable length and cross-sectional area mounted on DMC/ SMC moulds at sufficient distance, enclosure made of M.S. sheet 1.6mm thick with hinged cover and lock, fitted with dust excluding gaskets and secured with sufficient no. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/ rag bolts and nuts etc. complete with all accessories including connections with suitable size of thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge at site:-Bus Bar Chamber 63amp., 415volts Overall Dimensions (350mm x 450mm x 150mm) nominal
11MCCB's (FOR PANELS & SHEET ENCLOSURE):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-MCCB Four Pole 63/80/100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting (For Lighting Padestal)
12MS SHEET ENCLOSURE FOR MCCB's:Supply & Erection of indoor type MCCB enclosure of suitable size having provision for MCCB with extended rotary handle. The Enclosure shall be made from 14/16 SWG CRCA sheet, confirming to IS 8623/1977-82. The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The Enclosure door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. The Enclosure will be wall mounting type having provision for cable entry from bottom/top with cable glands etc. The sheet metal is sprayed with corrosion resistant etch primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work:- MS Sheet Enclosure having provision for MCCB 40-160Amp.with extended rotary handle (Approx. Size 500mm x 300mm x 200mm) (For Lighting Padestal)
13AUTOMATIC VOLTAGE STABLIZER, TIMER:TIMER:S/E of Microprocessor Based Street Light Controller with digital time switch daily programmed with stand by lithium battery with back up of 6 years with min. time between 2 switching operations is 1 minute, three pole power contactors 40A. with coil voltage 220-230V AC with 1 no. aux. contact NO, MCB 2 pole 40amp. (C-Curve, 10kA) & power wiring with single core PVC insulated FR cable 10 sq. mm and control wiring with PVC insulated FR cable 1 sq. mm, 1 no. two position selector switch to bypass timer and other accessories & petty material (din rail, 4 pole bakelite terminal strip 63A/ 440V AC, required nut bolts) should be fixed on bakelite sheet 6mm thick to be mounted in a IP54 surface/ flush mounting powder coated sheet metal (1.60mm thick) cabinet having size 450mm x 600mm x 150mm to switch ‘ON’ all the 3 phases & switch ‘OFF’ 3 phases pre-fixed timings complete in all respect as per satisfaction of Engineer-in-charge:-Street Light Controller (For Three Single Phase Circuits) with 3 Nos. Three Pole Power Contactors 40A, 1 no. aux. contactor 6 amp. (2NO+2NC) with coil voltage 220V AC, 3 Nos. MCB 2 Pole 40amp. (C-Curve,10kA) & petty material (Din rail, 2 Nos. 4 pole bakelite terminal strip 63A/ 440V AC, required nut bolts)
14GALVANIZED STEEL OCTAGONALPOLES FOR WIND VELOCITY OF 169 Km/ HOUR:Supply and Erection of Galvanized Steel Octagonal Pole (Sheet Thickness 3mm) with base plate designed to withstand wind speed 169 km/hour of suitable length Sheet Steel Confirming to IS 2062 : 2011 E350B0 (Yield Stress must be min 355Mpa and Tensile Strength min 470Mpa which is equivalent to BS- EN10025S355J or ASTM-572A GR-50) andthickness of Hot dip galvanization coating (70microns) conforming to IS:2629/ IS:2633/ IS:4759: BSEN-ISO-1461-1991OR ASTM A 123/A123M-02. The pole shall be in single piece hot dip galvanized and shall be tapered towards the top. The bottom section shall have openable slot with exterior surface door & shall have suitable locking arrangement for housing three phase four wire cable connection, Bakelite sheet, MCB, loop in and out arrangement for incoming/ outgoing cables. There shall be suitable arrangement for earthing. Rigid Base plate of suitable size and thickness shall be welded inside and outside at the bottom of pole with provision for fixing 4 foundation bolts. The Octagonal Pole shall be bolted on pre- cast foundation with a set of four foundation bolts of EN-8 Grade with thread portion hot dip galvanized for greater rigidity. The foundation shall be erected over cement concrete M20 withsteel of given size as per design of originalGalvanized Octagonal Pole Overall Length8 metre (Sheet thickness 3mm), Top dia.(A/F) 70mm and bottom dia. (A/F) 135mm, Foundation size below G/L 550mm x 550mm x 1500mm, 4Nos. Foundation Bolts size 20mm dia., Length≥750mm with Base Plate Dimensions 225mm x 225mm x 16mm Thick
15GALVANIZED OCTAGONAL POLEBRACKETS:Supply and erection of bracket for galvanized octagonal pole, the bracket should be fixed on the top of the pole having top outer dia. 70mm to 90mm (A/F) complete in all respect as approved by the Engineer-in-charge at site:Single arm bracket 1 metre long forgalvanized octagonal pole
16Single arm bracket 1.5 metre long forgalvanized octagonal pole
17LAYING OF UNDER GROUND CABLES, DISMANTALLING & ERECTION OF POLES AND CEMENT CONCRETE MUFFS:Supply and erection of SMC Junction Box (Glass Fibre reinforced polyester sheet moulding compound) confirm to IS:14772 (Recessed/ On surface), robustly constructed, safe & shock proof, rust & tamper proof of suitable inner & outer dimensions with ± 10% tolerance in size & hinged water tight cover with locking arrangement having 1No. terminal strip with 4Nos. terminals & 1No. Single pole MCB of required capacity fixed on din bar (Din Bar Provision for 2Nos. MCB's) complete in all respect as approved and desired by the Engineer In-Charge at site:-SMC Junction Box (Glass Fibre reinforced polyester sheet moulding compound) confirm to IS:14772, inner dimensions 140mm x 140mm x 95mm with hinged water tight cover with locking arrangement
18DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES:Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:-Double walled corrugated (DWC) HDPE pipe 50 / 38mm (outer/inner dia.)
19Double walled corrugated (DWC) HDPE pipe 63 / 51mm (outer/inner dia.)
20Supply and erection of heavy duty aluminium thimbles/lugs for cable end termination duly crimped including making necessary connections completely:- Aluminium thimble cable Core size 10 - 16sq.mm
21SHEET METAL CUBICAL PEDESTAL, TOWER STRUCTURES, HT & LT LINE ITEMS, MS CHANNELS, BRASS GLANDS, ALUMINIUM & COPPER THIMBLES:CUBICAL PEDESTAL:Supply and erection of Sheet metal cubical pedestal made from 50mmx50mmx6mm thick MS angle iron frame with 5 sides welded & covered with MS sheet 2mm thick & front side hinged with 4\\" hinges & locking system with single/ double door openable placed on MS strip of size 12.5mm x 2.5mm thick welded with MS sheet, 4Nos. legs of 50mmx50mmx6mm thick MS angle iron each of 600mm long with MS sheet 100mmx100mmx6mm thick at the bottom end of the legs. Front door welded x-sectionally with MS flat 25mmx5mm. The front side with MS sheet each 75mm wide & a bend of 75mm width outwards & inwards on all sides with tappered top 200mm high and pedestal with 4 Nos. supporting members each of MS flat 50mmx6mm thick according to cubical size duly welded & complete pedestal to be painted with 1 coat of red oxide & 2 coats of paint & bonding to the existing earth. The Pedestal platform should be filled with 1:2:4 cement concrete mixture and erected 150mm high from the top of the cement concrete platform. The job is to be completed as approved by Engineer-in-charge:-Cubical Size 1400mm high, 1200mm wide and 500mm deep with platform dimensions 1300mm x 600mm x 450mm
22Supply and Erection of LED Post top 40/45 watt Opal Diffuser Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED with wattage 1 to 5 Watt with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab.
23Supply and erection of LED Street Light 70/72 watt, Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED (with wattage 1 to 5 Watt) with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab.
24Supply and erection of LED Flood Light 120watt, Supply Voltage 140-270Volts AC supply, 50Hz ± 3% (including BIS Certified potted single diver with screen or laser printing logo LED driver) with pressure die cast or extruded aluminium housing with control gear (IP 66 protection), THD<10%, CRI minimum 70, High power LED with wattage 1 to 5 Watt with mandatory secondary lenses, toughened glass fitting, 4 KV SPD within driver and 10KV external SPD, Min IK07, efficacy of LED fixture minimum 120 lumens per watt, 5 year warranty including their drivers complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to Punjab Govt. vide Letter ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021. Besides this the lighting fixtures manufacturers should have in house NABL accredited lab.
25Pole Mounted Sub StationSupply, installation, testing and commissioning of 11KV/433V, 315KVA, Outdoor type pole mounted Distribution Transformer, Three Phase 50 Hz, Oil Immersed, Naturally Cooled ONAN, Core type Double wound with aluminium conductor conforming to IS:1180 (As amended upto date) Level-2 The max allowable total losses (includes no load and load losses)i) At 100% loading at rated volotage, frequency and at 75°C shall not exceed 2750 watts.ii) At 50% loading at rated voltage, frequency and at 75°C shall not exceed 955 watts.& IS: 2026 with first filling of Oil as per IS:335 compltete with connections on both sides (HT/LT side) as per satisfaction of Engineer Incharge at site. (a). Output Rating : KVA (b). No Load Voltage ratio at rated voltage & frequency: 11KV/ 0.433kV(c). Off Circuit Tap changer: +5% to -10% off circuit tapping in steps of 2.5%. (d). Vector group : Dyn11 (e). Ambient temperature: 50°C
26(f). Transformer shall be capable of operating continously at its normal rating without exceeding following temperature rises with the service conditions written in clause-3 of PSPCL order no POT-14072025i) 35°C in oil by thermometerii) 45°C in winding by resistance iii) Hot Spot temperature not to exceed 95°C(g). Magnetic Core: Prime grade of M4 or better (h). System Highest Voltage :- 12kV at the HV side (i). Terminations: Bushing on HV & LV Side(j). Insulation Level: ● H.V. Power Frequency (KV rms) : 28 kV ● H.V. Impulse withstand voltage (KV peak): 75 kVpThe Tranformers shall fitted with accesories like Rating and Diagram anodized aluminium plate, 2 Nos. Earthing terminals, 4 Nos. Lifting Lugs, Air Release hole with plug, Dehydrating Silica Gel Breather, Oil Level guage with minimum level marking, Conservator with Oil filling hole with cap & drain plug, Thermometer Pocket, Jacking Lugs, Bottom Drain cum filter valve, Top Filter Valve, 4Nos. Uni-directional rollers, Explosion vent with diaphragm, Fixed/ Detachable Radiator. Complete in all respect as approvede by Engineer-in-charge at site. Transformer warrantty (i.e 60 months from the date of commissioning or 66 months from the date of dispatch which ever is earlier) and All other specifications parameter should be as approved by PSPCL order no POT-14072025- (Technical Specification) Transformer should comply strictly to PSPCL specifications
27Supply and erection of pre-stressed cement concrete pole of suitable length with a given planting depth confirming to IS-1678/ 1960/1978 below ground level in excavated pit of suitable dimensions complete in all respect as approved by Engineer-in-charge at site:-PCC Pole Overall Length 11 metre, Planting depth 1.80 metre, W/L 363 kg
28HT & LT Line Items:Supply & erection of 11kV GO switch confirming to ISI specifications. The item includes supply and erection of operating pipe and handle arrangement of MS flat 50mm x 6mm and channels 75mm x 40mm sheet. The GO switch is to be fitted with locking arrangement so as it locks upward on 'ON' position and locks downward in 'OFF' position. The entire GO switch assembly/unit should be properly earthed and the job is to be completed as approved by Engineer-in-charge.
29MS CHANNELS/FLATS:Supply and erection of MS angle iron (Channel)/MS Flats of suitable size with cutting, bending, and necessary holes as desired by Engineer in charge at site:MS angle iron size 100mm x 50mm x 6mm thick
30MS flat iron size 50mm x 5mm thick
31MS flat iron size 25mm x 5mm thick
32G.I. EARTHING:Earthing with G.I. wire/ rope in G.I. pipe partly recessed and partly on surface complete with 150cm long 50mm dia. G.I. earth pipe (Cutting threads and 36 Nos. holes, 1cm dia. to make a mesh around the GI Pipe) with G.I. reducing socket including erection of the same, 4.50 metre (14.76 feet) below ground level with 20Kg. charcoal & salt mixture etc., up to 8 metre in length (including boring & refilling).
33Earthing with 7/12 S.W.G. (7/2.80mm dia.)G.I. rope in 20mm dia G.I. pipe with G.I. reducing socket 50mm x 20mm (upto 8Metre in length)
34LT PANELS & MCCB's (MOULDED CASECIRCUIT BREAKERS):LT PANELS:Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55).Fabrication:- Panel shall be made from 14/16 SWG CRCA sheet, conforming to IS 8623/1977-82. The sheet metal used for the fabrication of control panel will be 2mm for load bearing member’s door and fittings plates etc. the partitions and other non load bearing members will be fabricated out of1.6mm sheet, the sheet will be of mild steel CRCA type. The base channel will be made out of 75 x 40 x 5mm rolled channel.The door should be double folded without edge and the gasket should be ‘S’ type puffed neutral rubber gasket for long life. The hinges of the door should be bolted type with double hole arrangement. The panel door lock should be quick openable type spring loaded. There should not be any special tool or key to open the lock. Minimum depth 400mm / wide 300 mm for busbar/ Cable ally at the front of the panel. The panel will be free standing floor mounting type having provision for cable entry from bottom/top with cable glands etc.
35The fabrication should be such that all the memberi.e. vertical/horizontal should be detachable typei.e. total bolted. In case of any changes required at site. it should be possible then and their self without any cutting or welding. The fabrication of the panel in 3B construction fully compartmentalized type i.e. bus bar chamber as well as the cable chamber should be totally isolated from the feeder chamber. Where there crossing of the wire or bus links. It should have proper rubber gourmets or non-hygroscopic material. No live part should be in visible condition.
36Painting:- The sheet metal is sprayed withcorrosion resistant etch Primer. The finishing treatment shall be applicable with air drying paint (7/9 tank Powder coated process should present in company pemises) after necessary putty work .Busbars:-The panel shall be provided with TPN aluminium busbar of suitable size according to the size of MCCB's. Busbar shall be of high conductivity (53% to 58%) E91-E Grade aluminium (1A/Sq.mm). All Busbar will be air insulated with codified in Red, Yellow, Blue & Black as per standard for cable termination with the help of extended busbar only with proper adjustable cable supports. The main busbar would be supported upon non-hygroscopic SMC/DMC supports.
37Metering:-The panel shall be completed withdigital metering unit (with selector switches, voltmeter & ammeter) epoxy insulator, gasket, PVC sleeves, CT's & L.E.D. type indicator etc.Manufacturer of Panel should be CPRI Approved (Approval not older then 5 years) & ISO certified (Manufacturer workshop as per ISO 9001: 2015 standard) The Concerned contractor shall be approved the detailed drawing of panel with complete specification from the Engineer in charge at site.Detail of capacities of MCCB's to be installed in the cubical panel Enclosure (Excluding the cost of MCCB's) as per following:-LT Panel enclosure having space for 1No. Incomer MCCB 630Amp. and 6Nos. outgoing MCCB's 40amp. to 250amp. (Option: MCCB 200-250amp.= 2 No. and MCCB's 40-100amp.= 4 Nos.) according to the requirement at site (Approx. size 1475 x1800 x 400mm)
38MCCB's (FOR PANELS & SHEET ENCLOSURE):Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:-MCCB Four Pole 63/80/100 amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
39MCCB Four Pole 250amp., 415volts, ≥36kA Fixed Magnetic and Adjustable Thermal Setting
40MCCB Four Pole 630amp., 415volts, ≥36kA Microprocessor Based Adjustable Thermaland Magnetic Setting
41CABLE TRAY:Supply and erection of MS perforated cable tray (MS Sheet thickness 2mm) with DA gray paint on the existing surface with the help of MS angle iron support (to be painted with approved paint) of size 50mm x 50mm x 6mm thick to be fixed with fastners/ nut & bolts etc., complete in all respect as desired by the Engineer-in-charge and as per PWD General Specifications:-Cable Tray Size 450mm x 50mm x 50mm (2mm thick)
42COPPER EARTHING (Upto 14 metre in Length):Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 10.50 metre (34.44 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 14metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 9metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:-Earthing with 25mm x 3mm Copper Tape (upto 14Metre in Length)
43Earthing with 25 mm X 5 mm copper Tape (upto 14 metre in length)
44COPPER EARTHING STRIP (As Additional Length):Fixing additional Length of earthing with Copper Tape (On Surface/Flushed) with petty material as required etc.:-Additional Length 25mm x 3mm thick Copper Tape
45Additional Length 25 mm X 5 mm thick copper Tape
46STAY SETS:Supply and erection of Stay Set consisiting of 19/20mm dia.of suitable length G.I. stay rod duly threaded upto 300mm at one end and shaped on the other end. MS plate size 30cm x 30cm x 6mm with 20mm dia. hole drilled in the centre of the plate G.I. stay wire size 7/10 SWG, G.I. thimble for stay binding, Egg/Strain insulator, MS elbow made out of 16mm plain sheet and a 20cm long piece of 50mm x 50mm x 6mm angle iron made to the shape as approved by Engineer-in-charge. Stay set complete shall be fixed to the pole by providing suitable size full clamps made out 50mm x 6mm size MS flat with required number of nut and bolts 16mm dia. on one end and shall be embedded on the other end. The stay plate shall be covered with cement concrete having total volume of the concrete not less that 0.042Cum. The job shall include excavation of pit and back filling and after pouring concrete with excavated soil etc. as approved/desired by the the Engineer-in- charge:-Stay Set consisiting of 19/20mm dia., 2.4 metre Long G.I. Stay Rod
47XLPE INSULATED HT CABLES:XLPE INSULATED HT ARMOURED CABLES (UNDERGROUND):Supply & laying of Circular Aluminium Conductor screened with extruded semiconducting compound, XLPE insulated, insulation screened with extruded semiconducting combination in combination with copper tape (0.3KA for 1sec.) cores laid up, FR PVC inner sheathed, galvanized steel strip armoured and overall FR PVC sheathed cable confirming to IS:7098 (Part-2), 2011 working voltage 11KV(E) grade to be laid1.50 meter below ground level including excavation, sand cushioning, covering with sand & First class bricks and back filling the trench etc., of the required size:-HT Cable Overall size 35sq.mm (3Core)
48S/E of Heat shrinkable cable end termination/ Straight through joint kit for 11 KVA /6.6 KV (E) XLPE Cables as approved & desired by Enginer in charge:-Heat Shrinkable End Termination for cable size 35 sq. mm, 3Core (Indoor Type)
49XLPE INSULATED ARMOURED CABLES (UNDERGROUND):Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS:7098 (Part-1)1988 to be laid 1metre below ground level including excavation, sand cushioning, covering with sand & First Class bricks and back filling the trench etc., of the required size as per PWD General Specifications:-Overall size 16sq.mm (4 Core) Armoured (Underground)
50Overall size 240 sq.mm (3½ Core) Armoured (Underground)
51Cultural cess @1 % Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58446501
AUTHORITY Government Departments
TENDER VALUE 1.12 Crore
LAST DATE 23-11-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction Of Class 3 & 4 Employees Houses In New Rajindra Hospital At Patiala Punjab. (External Services Only)
Basic Detail
Tender No Tender Notice 22 Dated 6/11/2026
Bidding Type Tender
Location
City Patiala
State Punjab
Key Dates
Publish Date 07 Nov 2026
Submission Date 23 Nov 2026
Open Date 23 Nov 2026
Finance
Tender Value 1.12 Crore
Tender Fee 10000
EMD 2.25 Lakhs
Exemption Available
Document List
83d2a313-1398-4632-85ff-0c74457308e4.html
BOQ_365848.xls
sbd.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 23, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 11 days
Nov 23, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 11 days

Tender Documents

Download All (ZIP) ↓
html

83d2a313-1398-4632-85ff-0c74457308e4.html

xls

BOQ_365848.xls

pdf

sbd.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender