Tender For Repair/Maintenance Of Lt Panels, Lt Ug Cable And Certain Allied Connected Works At Metcalfe House And Jcb Lab Area Under Ge (I) R&D Delhi
Tender Value
44 Lakhs
Estimated cost
Bid Submission
28 Nov 2026
15 days left
EMD
88000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repair/Maintenance Of Lt Panels, Lt Ug Cable And Certain Allied Connected Works At Metcalfe House And Jcb Lab Area Under Ge (I) R&D Delhi
BOQ
| Sl. No. | Item Description |
| 1 | M&L for painting of LT Panel Indoor/Outdoor type with spray gun with two coats of synthetic enamel heat resistant smoke grey paint including preparation of old painted surfaces/removing/scraping old faded/rust/ cemented material of surface of complete LT panel in and including writing of incoming and out going feeder name and other word (size of word and colours directed by EIC), complete all as specified and directed. |
| 2 | M&L for replacement old rusted MS base frame of any size and type at various locations as directed and fabrication and fixing new base frame of Angle iron/ Channel/Flat/Plate/Rod for LT Panel complete with MS ClAs, Nuts, Bolts, Washers and necessary fixing arrangements duly painted with two coat of black synthetic enamel paint over a coat of zinc chromate primer in and including complete all as specified and directed. |
| 3 | M&L for welding, cutting, rusted sheet LT panel of any size and any type including, replacement of front and back cover and top cover duly fabricated made of CRCA steel sheet of size not less than 3.15mm thick, matching with existing including replacement of hinges and locking devices complete all as specified and directed by Engineer-in-Charge. |
| 4 | S&F in replacement of aluminium bus bar with colour coded heat sink sleeves supported on SMC type grip supports of rating 400A uniformly rated complete all as specified and directed. |
| 5 | S&F in replacement of aluminium bus bar with colour coded heat sink sleeves supported on SMC type grip supports of rating 800A uniformly rated complete all as specified and directed. |
| 6 | S&F in replacement of aluminium bus bar with colour coded heat sink sleeves supported on SMC type grip supports of rating 1500A uniformly rated complete all as specified and directed. |
| 7 | S&F in replacement of DMC/SMC LT insulator of appropriate size with existing one complete all as specified and directed by Engineer-in-Charge |
| 8 | M&L for disconnecting LT electric supply after taking proper shut-down and cleaning, servicing, lubrication and repairing of ACB 800A, cleaning and lubrication of mechanical operation mechanism, contacts, calibration and setting of all safety coils, cleaning and tightening of all electric and control wiring connections and nuts, bolts etc.including necessary spare parts and testing complete all as specified and directed. |
| 9 | All as per item No 8 above but ACB of capacity 1000A to 2000A |
| 10 | S&F in replacement of ACB with pre-fabricated factory made tested with suitable retrofitting kit solution for New ACBs, 4 Pole, 800A to 1000A, Ics=Icu=Icw= 65kA (RMS) for 1 Sec, Electrical (manual fixed type), front operated Air Circuit Breaker suitable for 415V, 3-Phase, 50Hz AC supply system, Ics=Icu=Icw= for 1 Sec , complete with microprocessor based protection release with LCD 4 Line display and adustable over current, adjustable short-circuit, adjustable earth-fault, instantaneous protection and over temperature protection feature, the breaker shall have minimum breaking capacity of 65KA (RMS Symmetrical) in-built thermal memory complete all as specified and directed. |
| 11 | S&F in replacement of ACB with pre-fabricated factory made tested with suitable retrofitting kit solution for New ACBs, 4 Pole, 800 to 1000, Ics=Icu=Icw= 65kA (RMS) for 1 Sec, Electrical (Manual draw out type), front operated Air Circuit Breaker suitable for 415V, 3-Phase, 50Hz AC supply system, Ics=Icu=Icw= for 1 Sec , complete with microprocessor based protection release with LCD 4 Line display and adjustable over current , adjustable short-circuit, adjustable earth-fault, instantaneous protection and over temperature protection feature, the breaker shall have minimum breaking capacity of 65kA (RMS Symmetrical) in-built thermal memory complete all as specified and directed. |
| 12 | S&F in replacement of ACB with pre-fabricated factory made tested with suitable retrofitting kit solution for New ACBs, 4 Pole, 1250A to 2000A, Ics=Icu=Icw= 65kA (RMS) for 1 Sec, Electrical Manual /draw out type), front operated Air Circuit Breaker suitable for 415V, 3-Phase, 50Hz AC supply system, Ics=Icu=Icw= for 1 Sec, complete with microprocessor based protection release with LCD 4 Line display and adjustable over current, adjustable short-circuit, adjustable earth-fault, instantaneous protection and over temperature protection feature, the breaker shall have minimum breaking capacity of 65kA (RMS Symmetrical) in-built thermal memory complete all as specified and directed. |
| 13 | Disconnecting, taking out old unserviceable joints and Supplying, Fixing, Jointing and testing for provision of straight through joints, heat shrinkable epoxy tube with epoxy jointing materials suitable for XLPE, LT Cable 1100V grade, for size 16 to 50 sqmm 3.5 Core complete all as specified and directed. |
| 14 | All as per item Ser No 13 above but size 120 Sqmm to 185 Sqmm 3.5 core. |
| 15 | All as per item Ser No 13 above but size 240 Sqmm to 300 Sqmm 3.5 core. |
| 16 | All as per item Ser No 13 above but size 400 Sqmm to 630 Sqmm 3.5 core. |
| 17 | Disconnecting and Taking out old unserviceable joints and Supplying, Fixing, Jointing and testing for provision of indoor termination joint Kits, heat shrinkable epoxy tube with epoxy jointing materials suitable for XLPE, LT Cable 1100V grade indoor , for size 95sqmm to 185 sqmm 3.5 Core complete all as specified and directed. |
| 18 | All as per item Ser No 17 above but size 240 Sqmm to 300 Sqmm 3.5 core. |
| 19 | All as per item Ser No 17 above but size 400 Sqmm to 630 Sqmm 3.5 core. |
| 20 | S&F in replacement of 3 Pole MCCB, 100A, 50 Hz, 415V with thermal magnetic release based,100% ICS=100% ICU = 25KA, with handle and phase barriers both sides complete all as specified and directed. |
| 21 | S&F in replacement of MCCB of cap 3 Pole 125A, with thermal magnetic release based,100% ICS=100% ICU = 25 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 22 | S&F in replacement of MCCB of cap 3 Pole 160A, with, thermal magnetic release based,100% ICS=100% ICU = 25 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 23 | S&F in replacement of 4 Pole MCCB,100A, 50 Hz, 415V with thermal magnetic release based,100% ICS=100% ICU = 25KA, with handle and phase barriers both sides complete all as specified and directed. |
| 24 | S&F in replacement of MCCB of cap 4 Pole 125A, with thermal magnetic release based,100% ICS=100% ICU = 25 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 25 | S&F in replacement of 4 Pole MCCB, 160A, 50 Hz, 415V thermal magnetic release based, based,100% ICS=100% ICU = 25 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 26 | S&F in replacement of 4 Pole MCCB, 250A, 50 Hz, 415V with microprocessor release based, 100% ICS=100% ICU = 36 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 27 | S&F in replacement of 4 Pole MCCB, 400A, 50 Hz, 415V with microprocessor release based, 100% ICS=100% ICU = 50 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 28 | S&F in replacement of 4 Pole MCCB, 630A, 50 Hz, 415V with microprocessor release based, 100% ICS=100% ICU = 65 KA, with handle and phase barriers both sides complete all as specified and directed. |
| 29 | S&F digital Multifunctional meter as per matching to existing including all accessories and wiring complete all as specified and directed. |
| 30 | S&F in replacment power factor meter digital type for frequency range (45-65 Hz) as per matching to existing one including all accessories and wiring complete all as specified and as directed. |
| 31 | S&F in replacement three phase overcurrent earth fault relay MC-61 as per matching to existing one including all accessories and wiring complete all as specified and as directed. |
| 32 | S&L in replacement of LT cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V grade with stranded aluminium conductor of size 16 sqmm 4.0 core including testing complete all as specified and directed. |
| 33 | All as per item No 32 above but of cable 25 Sqmm 3.5 core |
| 34 | All as per item No 32 above but of cable 35 Sqmm 3.5 core |
| 35 | All as per item No 32 above but of cable 50 Sqmm 3.5 core |
| 36 | All as per item No 32 above but of cable 70 Sqmm 3.5 core |
| 37 | All as per item No 32 above but of cable 95 Sqmm 3.5 core |
| 38 | All as per item No 32 above but of cable 120 Sqmm 3.5 core |
| 39 | All as per item No 32 above but of cable 240 Sqmm 3.5 core |
| 40 | All as per item No 32 above but of cable 300 Sqmm 3.5 core |
| 41 | All as per item No 32 above but of cable 400 Sqmm 3.5 core |
| 42 | Excavation in trenches in soft/loose soil not exceeding 1.5m depth and not exceeding 1.5m in width for laying of LT cables including for taking out and relaying of LT Cables complete all as specified and directed. |
| 43 | All as per item No 42 above but excavation in hard/dense soil. |
| 44 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick as in soft/loose soil complete all as specified and directed. |
| 45 | Removing surplus soil to a distance not exceeding 50m and depositing where directed at a level and not exceeding 1.5m above the starting point complete all as specified and directed. |
| 46 | S&L dry fine sand for cushioning of underground cable laid in trenches/duct complete all as specified and directed |
| 47 | M&L for PCC cover size 250 x 150 x 40mm for cable, protection of cable laid in trenches complete all as specified and directed |
| 48 | M&L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including supply and laying of GI pipe of 100mm diameter light grade complete all as specified and directed by Engineer-in-Charge |
| 49 | Supply and laying in replacement of GI pipe medium grade of 150mm diameter laid in trenches for protection of UG cable complete |
| 50 | All as per item No 49 but GI pipe 100mm diameter complete |
| 51 | All as per item No 49 but GI pipe 50mm diameter complete |
| 52 | Supply and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 09m long. Poles shall be coated with two coats of black bituminous paint throughout internally, and externally up to the planting depth. The remaining portion of the exterior shall be painted with one coat of red oxide primer including taking down old unserviceable pole complete all as specified and directed . |
| 53 | S&F Junction box SMC KIOSK box water proof IP-54 of size 300mm x 225mm x 100mm including fixing of terminal connector 100A 4 pole suitable for in and out connection of 3 core 2.5sqmm cable fixed to termination box to light fittings complete all as specified and directed. |
| 54 | M&L in replacement of wiring with multistranded copper conductor of size 2.5 sqmm 3 Core FRLSH matching with existing size/type including proper laying with the help of locking device complete all as specified and directed by Engineer-in-Charge. |
| 55 | M&L for PCC (1:2:4) type B-1 (using 20mm graded stone aggregates) for repairing of LT pole foundation etc including filling in road cuts/ hard standing/ Bitumen etc all as specified and directed. |
| 56 | M&L for PCC (1:3:6) type C-1 (using 20mm graded stone aggregates) for LT pole foundation etc including filling in road cuts/ hard standing/ Bitumen etc all as specified and directed. |
| 57 | M&L for PCC (1:4:8) type D-2 (using 40mm graded stone aggregates) for repairing of LT pole foundation all as specified and directed. |
| 58 | M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.5m deep below normal ground level) with top edge of plate not less than 1.5m below normal ground level, connecting to the Galvanised iron earth lead 32mm x 6mm size, by means of bolts, nuts, check nuts and washers of galvanised iron protected by provision of GI medium grade pipe 40mm bore upto test point including provision of concrete pit in PCC (1:2:4) type B-1 (using 20mm graded stone aggregates) with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weigth not less than 4 Kg/Sqm) and frame of angle iron 25mm x 25mm x 6mm with lugs 02 Nos and with 6mm diameter MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75m long placed on top edge of earth plate, common salt and charcoal filling, test point made out of 40mm x 8mm FI with fixing arrangement, funnel, wire mesh and excavation/earth work in hard dence soil, returning filling in and removal of surplus soil to a distance not exceednig 50m, all as per Electric Plate No 3 of SSR 2010 Part-I and connecting to earth test point, all as specified and directed. |
| 59 | Earth continuity conductor passing through PVC Conduit of size 25mm main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25 x 4mm galvanised iron strip complete all as specified and directed by Engineer-in-Charge. |
| 60 | Disconnecting of electric supply and Servicing of any make and type of APFC Panel and its minor/major parts by cleaning, checking and all setting of relays, contactor, removing dust particle from the Panel, checking spring mechanism, tightening of all nut and bolts of entire Panel and checking all control wiring of entire system testing on load complete all as specifed and directed. |
| 61 | S&F in replacement of APFC relay for 10 KVAR, 10 Stages complete all as specified and directed. |
| 62 | S&F in replacement of A/M Switch complete all as specified and directed. |
| 63 | S&F in replacement of LED type Indicating lamp type of voltage AC/DC set of RYB, as per matching to existing. |
| 64 | S&F in replacement of Capacitor Bank MPP-H, 05 KVAR capacity rated 440V AC, 3ø, 50Hz, Delta connection, Round type complete all as specified and directed. |
| 65 | S&F in replacement of Capacitor Bank MPP-H, 10 KVAR capacity rated 440V AC, 3ø, 50Hz, Delta connection, Round type complete all as specified and directed. |
| 66 | S&F in replacement of capacitor duty, contactor MO C 5 complete all as specified and directed. |
| 67 | S&F in replacement of capacitor duty contactor MO C 12.5 complete all as specified and directed. |
| 68 | S&F in replacement of capacitor duty contactor MO C 25 complete all as specified and directed. |
| 69 | S&F in replacement of capacitor duty contactor MO C 50 complete all as specified and directed. |
| 70 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning indoor panel fabricated out of 3.15mm thick CRCA sheet steel provided of size 3m x 2m x 1m with hinged detachable lockable door at front and back, floor mounted free standing totally enclosed indoor cubicle extensible, compartmentalized, front operational, hinged lockable doors,dust and vermin proof CPRI approved IP-65, suitable reinforcement by pressed sheet steel angle, channels, T section or flat wherever necessary. Cable gland plate shall be provided at the bottom of the panel. Panel enclosure shall be treated with all anti-corrosive process before powder coating as per specification with approved shade. 2 Nos earthing terminals shall be provided for all distribution panel. Panel shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided and 1800A capacity extensible aluminium bus bars of high conductivity for three phase supply, DMC/ SMC bus bar supports, bottom base channel of MS section not less than 70mm x 65mm x 6mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm Approval shall be obtained for each panel in the form of shop drawing before fabrication. The panel(s) shall have the switch gears metering instrument and accessories as specified and directed.Incoming : ACB 4 Pole 1250A with microprocessor release based, 100% ICS=100% ICU = 65 kA-01 NoOutgoing :(a) MCCB 630A 4 pole with microprocessor release based, 100% ICS=100% ICU = 65 kA-02 Nos(b ) MCCB 500A with microprocessor release based, ICS=100% ICU = 50 kA - 02 Nos(c) MCCB 250A with microprocessor release based, ICS=100% ICU =36 kA : 02 Nos(d) MCCB 160A with microprocessor release based, ICS=100% ICU = 25 kA : 02 Nos(e) Wiring and Metering(f) Set of RYB phase LED indicating lamps - 01 set of three(g) Multi function meter with backlit LCD display with RS 485 communication port - 1 Set complete all as specified and directed. |
| 71 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning indoor panel fabricated out of 3.15mm thick CRCA sheet steel provided of size 1.6m x 1.5m x 1.5m with hinged detachable lockable door at front and back, floor mounted free standing totally enclosed indoor cubicle extensible, compartmentalized, front operational, hinged lockable doors,dust and vermin proof CPRI approved IP-65, suitable reinforcement by pressed sheet steel angle, channels, T section or flat wherever necessary. Cable gland plate shall be provided at the bottom of the panel. before powder coating as per specification with approved shade. 2 Nos earthing terminals shall be provided for all distribution panel. Panel shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided and 1200A capacity extensible aluminium bus bars of high conductivity for three phase supply, DMC/ SMC bus bar supports, bottom base channel of MS section not less than 70mm x 65mm x 6mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm Approval shall be obtained for each panel in the form of shop drawing before fabrication. The panel(s) shall have the switch gears metering instrument and accessories as specified and directed.Incoming:(a) MCCB 400A 4 pole with microprocessor release based,100% ICS= 100% ICU = 65 kA-02 NosOutgoing:(b) MCCB 250A with microprocessor release based,100% ICS= 100% ICU = 50 kA - 01 Nos(c) MCCB 100A Thermal magnetic release 100% ICS= 100% ICU = 36 kA : 04 Nos(d) wiring and Metering(e) Set of RYB phase LED indicating lamps - 01 set of three(f) Multi function meter with backlit LCD display with RS 485 communication port- 1 Set complete all as specified and directed. |
| 72 | Design, fabrication, assembling, wiring, supply , installation, testing and commissioning outdoor panel fabricated out of 3.15mm thick CRCA sheet steel provided of size 1.6m x 1.5m x 0.5m with hinged detachable lockable door at front and back, floor mounted free standing totally enclosed indoor cubicle extensible, compartmentalized, front operational, hinged lockable doors,dust and vermin proof CPRI approved IP-65, suitable reinforcement by pressed sheet steel angle, channels, T section or flat wherever necessary. Cable gland plate shall be provided at the bottom of the panel. Panel enclosure shall be treated with all anti-corrosive process powder coating as per specification with approved shade. 2 Nos earthing terminals shall be provided for all distribution panel. Panel shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided and 1200 A capacity extensible aluminium bus bars of high conductivity for three phase supply, DMC/ SMC bus bar supports, bottom base channel of MS section not less than 70mm x 65mm x 6mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm, Approval shall be obtained for each panel in the form of shop drawing before fabrication. The panel(s) shall have the switch gears metering instrument and accessories as specified and directed. Incoming :(a) MCCB FP 630A with microprocessor release based,100% ICS=100% ICU= 50 kA -1 NosOutgoing :(b) MCCB FP 250A with microprocessor release based, 100% ICS=100% ICU= 36 kA -2 Nos(c) MCCB FP 160A with microprocessor release based, 100% ICS=100% ICU= 25 kA -2 Nos(d) MCCB FP 100A with thermal magnetic release based,100% ICS=100% ICU= 25 kA -1 Nos(e) Metering, LED indicating lamps(f) Set of RYB phase LED indicating lamps - 01 set of three(g) Multi function meter with backlit LCD display with RS 485 communication port- 1 Set complete all as specified and directed. |
| 73 | Design, fabrication, assembling, wiring, supply, installation, testing and commissioning outdoor panel fabricated out of 3.15mm thick CRCA sheet steel provided of size 1.27m x 1m x 1m x .5m with hinged detachable locked door at front and back, floor mounted free standing totally enclosed indoor cubicle extensible,compartmentlized, front operational, hinged lockable doors,dust and vermin proof CPRI approved IP-65, suitable reinforcement by pressed sheet steel angle, channels, T section or flat wherever necessary. Cable gland plate shall be provided at the bottom of the panel. Panel enclosure shall be treated with all anti-corrosive process (7 tank process) before powder coating as per specification with approved shade. 2 Nos earthing terminals shall be provided for all distribution panel. Panel shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided and 600 A capacity extensible aluminium bus bars of high conductivity for three phase supply, DMC/ SMC bus bar supports, bottom base channel of MS section not less than 70mm x 65mm x 6mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm, Approval shall be obtained for each panel in the form of shop drawing before fabrication. The panel(s) shall have the switch gears metering instrument and accessories as specified and directed.Incoming: (a) MCCB FP 250A with microprocessor release based, 100% ICS=100% ICU = 36 kA -1 NosOutgoing:(a) MCCB FP 160A with release based,100% ICS=100% ICU = 25 kA -3 Nos(b) Metering, LED indicating lamps(c) Set of RYB phase LED indicating lamps - 01 set of three(d) Multi function meter with backlit LCD display with RS 485 communication port - 1 Set complete all as specified and directed. |
| 74 | Design, fabrication, assembling, wiring, supply , installation, testing and commissioning outdoor panel fabricated out of 3.15mm thick CRCA sheet steel provided of size 2.8 x 1.5 x 1 with hinged detachable lockable door at front and back, floor mounted free standing totally enclosed indoor cubicle extensible,compartmentalized, front operational, hinged lockable doors,dust and vermin proof CPRI approved IP-65, suitable reinforcement by pressed sheet steel angle, channels, T section or flat wherever necessary. Cable gland plate shall be provided at the bottom of the panel. Panel enclosure shall be treated before powder coating as per specification with approved shade. 2 Nos earthing terminals shall be provided for all distribution panel. Panel shall be suitable for 415V, 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be provided and 1200A capacity extensible aluminium bus bars of high conductivity for three phase supply, DMC/ SMC bus bar supports, bottom base channel of MS section not less than 70mm x 65mm x 6mm thick, entire panel shall have a common copper earth bar of size 25mm x 5mm, Approval shall be obtained for each panel in the form of shop drawing before fabrication. The panel(s) shall have the switch gears metering instrument and accessories as specified.Incoming:(a) ACB FP 800A with microprocessor release based, ICS=100% ICU = 65 KA - 03 Nos with coupler 4 pole match as per exiting.Outgoing:(b) MCCB FP 630A with release based,100% ICS=100% ICU = 50 KA -02 Nos(c) MCCB FP 400A with release based, ICS=100% ICU = 50 KA -1 Nos(d) Metering, LED iindicating lamps.(e) Set of RYB phase LED indicating lamps - 01 set of three(f) Multi function meter with backlit LCD display with Rs 485 comunication port - 1 Set complete all as specified and directed. |
| 75 | S&F of Aluminium thimble of size 35 sqmm for terminal end of cable complete all as specified and directed. |
| 76 | S&F of Aluminium thimble of size 50 sqmm for terminal end of cable complete all as specified and directed. |
| 77 | S&F of Aluminium thimble of size 70 sqmm for terminal end of cable complete all as specified and directed. |
| 78 | S&F of Aluminium thimble of size 95 sqmm for terminal end of cable complete all as specified and directed. |
| 79 | S&F of Aluminium thimble of size 120 sqmm for terminal end of cable complete all as specified and directed. |
| 80 | S&F of Aluminium thimble of size 150 sqmm for terminal end of cable complete all as specified and directed. |
| 81 | S&F of Aluminium thimble of size 185 sqmm for terminal end of cable complete all as specified and directed. |
| 82 | S&F of Aluminium thimble of size 240 sqmm for terminal end of cable complete all as specified and directed. |
| 83 | S&F of Aluminium thimble of size 300 sqmm for terminal end of cable complete all as specified and directed. |
| 84 | S&F of Aluminium thimble of size 400 sqmm for terminal end of cable complete all as specified and directed. |
| 85 | S&F in replacement motor for spring charging of ACB/ VCB. Complete all as specified and directed |
| 86 | S&F in replacement of charging gear assembly/ ACB VCB.Complete all as specified and directed |
| 87 | S&F in replacement of rack in out gear assembly Complete all as specified and directed |
| 88 | S&F in replacement of triping coil ACB/ VCB Complete all as specified and directed |
| 89 | S&F in replacement of cooling coil. Complete all as specified and directed |
| 90 | S&F earth pit chamber alongwith cover of Polymer, FRP Pit Cover of heavy high grade polypropelene for high stress and starin level of size 225x300x195 mm complete all as specified and directed. |
| 91 | Supply and laying in replacement GI pipe mideum grade in replacement of 40mm diameter laid in trenches for protection of UG cable complete all as specified and directed. |
| 92 | M&L for brining cable testing Van (fault locator ) dedecting location of the fault in HT 11 KV /1.1 KV UG cable any complete all as specified and directed . |
| 93 | M&L 10mm thick rendering in CM (1:6) on fair faces of new or old brick works or concrete work finished even and smooth without using extra cement complete all as specified and directed. |
| 94 | M&L 5mm thick rendering in CM (1:3) on ceiling new or old brick works or concrete work finished even and smooth without using extra cement complete all as specified and directed. |
| 95 | M&L 5mm thick rendering in CM (1:4) on ceiling new or old brick works or concrete work finished even and smooth without using extra cement complete all as specified and as directed. |
| 96 | M&L preparation of newly plastered surfaces of walls and applying two coats of oil bound distemper (white or tinted) over two coat of wall care putty (Avg 1mm thick) complete all as specified and directed. |
| 97 | M&L for Complete removal of existing treatment from internal plastered or unplastered surfaces of walls and applying two coats of oil bound distemper on walls over and including two coat of wall care putty (Avg 1mm thick) on scrapped/uneven surfaces of any description to match with the existing surfaces before application of paint etc complete all as specified and directed |
| 98 | S&F Pre-painted galvanume aluminium zinc coating GI based corrugated steel sheet 0.50mm thick of an colour having tensile strength of 550 MPa as in roof covering/cladding to wall, fixed with self tapping screws as specified and directed. |
| 99 | Excavating in post holes soft/loose soil (or similr holes) not exceeding 0.5 cum getting out returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cum watering and removing surplus soil to a distance not exceeding 50m and making good surfaces complete all as specified and directed. |
| 100 | M&L for applying one coat of cement base paint on walls/ security wall including prepration of old decorated surface with brooming down smoke soot, moulds efforescent salt etc complete all as specified and directed |
| 101 | M&L Hardcore of gauge not exceeding 63mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and directed. |
| 102 | M&L for cleaning of duct size (600 x 400) and removing of old unsv LT cable any size deposite to MES store and Cost including filling of river sand after cleaning of Duct compelete all as specified and directed . |
| 103 | S&F sheet upto 6mm thick for cable pit duct/trench cover with chequered plate including handles and angle iron 10mm thick complete all as specified and directed Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 28, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 15 daysDec 05, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 22 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender