Tender For Repairs / Maintenance / Servicing Of Lt Supply Distribution System, Mccbs, Panel And Panel Accessories, Trunking Bus Bar System, Lt Underground Cables And Other Connected Works Under Age E/M-Ii In Ge (Central) Khadki.
Tender Overview
Project Description
Tender for Repairs / Maintenance / Servicing Of Lt Supply Distribution System, Mccbs, Panel And Panel Accessories, Trunking Bus Bar System, Lt Underground Cables And Other Connected Works Under Age E/M-Ii In Ge (Central) Khadki.
BOQ
| Sl. No. | Item Description |
| 1 | Supply, Laying, jointing and testing LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable , laid in trenches/ducts or fixed to poles/walls including cable gland of suitable sizes and aluminium lugs for connection complete including taking down old unsv existing size of cable all as specified and directed of following size: |
| 2 | 25 Sqmm 4 core |
| 3 | 50 Sqmm 3.5 core |
| 4 | 70 Sqmm 3.5 core |
| 5 | 120 Sqmm 3.50 core |
| 6 | 185 Sqmm 3.50 core |
| 7 | 240 Sqmm 3.50 core |
| 8 | 400 Sqmm 3.50 coreNote for Item No 1.01 to 1.07:- (i) During earth work for laying of cable, any damage to the existing services will be made serviceable without any extra cost within 24 hrs. (ii) Contractor should visit the site before quoting the rate for understanding the scope of work. (ii) contractor should provide the safety belt and all accessories for laying cable in cable tray or wall upto height of 15 Mtr. |
| 9 | Supply and fix tubing 'light grade' galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete all as specified and as directed including taking down of the following bores :- |
| 10 | 50 mm bore |
| 11 | 40 mm bore |
| 12 | Material and labour for cutting through existing bituminous road/PCC/floor/Stone block Tank road along cross section of the road as per required breadth and depth for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finishes complete all as specified. NOTE :- Contractor should visit the site before quoting the rate & GI Pipe will be measured and paid seperately in respective item. |
| 13 | Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in hard / dense soil complete all as specified and as directed. |
| 14 | Material and labour for laying double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to IS 16205 & 14930 (Part-I and II) for protection of underground cable of size 160 mm outer dia with all fittings such as clamps, coupler etc. laid in trenches/roads/nallah or fixed along wall/ poles or laid under floor (including cutting floor/road and making to match with existing adjouning surface etc. for cable protection all as specified and as directed. (excavatoin and earth work measured and paid separately) |
| 15 | Description as per item No 05 above but of size 120 mm OD |
| 16 | Description all as per item No 05 above but of size 63 mm OD |
| 17 | Description all as per item No 05 above but of size 40 mm OD |
| 18 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thick complete all as specified and as directed. |
| 19 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed. |
| 20 | Supply and fixing MCCB 63 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 21 | Supply and fixing MCCB 100 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 22 | Supply and fixing MCCB 160 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 23 | Supply and fixing MCCB 200 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 24 | Supply and fixing MCCB 250 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 25 | Supply and fixing MCCB 320 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 36 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 26 | Supply and fixing MCCB 400 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 36 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed |
| 27 | Supply and fixing MCCB 630 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 50 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 28 | Supply and fixing MCCB 800 Amp 4 pole, 415 Volts, 50 Hz, breaking capacity 50 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 29 | Supply and fixing MCCB 63 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 30 | Supply and fixing MCCB 100 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 31 | Supply and fixing MCCB 160 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 32 | Supply and fixing MCCB 200 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 33 | Supply and fixing MCCB 250 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 25 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 34 | Supply and fixing MCCB 320 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 36 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 35 | Supply and fixing MCCB 400 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 36 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. |
| 36 | Supply and fixing MCCB 630 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 50 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. Please Enable Macros to View BoQ information |
| 37 | Supply and fixing MCCB 630 Amp 3 pole, 415 Volts, 50 Hz, breaking capacity 50 KA, with thermal magnetic protection unit, Ics = 100% Icu, four optimum frame, thermal adjustable 0.8 to 1In, Magnetic Adjustable 5 to 10 In, including suitable size of separator, thimble including all required accessories as per requirement at site including taking down old unsv existing size of MCCB complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender