Tender For Designing, Supply And Erection, Testing & Commissioning Of Two Numbers High Mast With Luminaires At Degree College Haroli Distt. Una (Hp)
Tender Value
19.99 Lakhs
Estimated cost
Bid Submission
17 Nov 2026
3 days left
EMD
40000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Una → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Designing, Supply And Erection, Testing & Commissioning Of Two Numbers High Mast With Luminaires At Degree College Haroli Distt. Una (Hp)
BOQ
| Sl. No. | Item Description |
| 1 | Designing, Supply, & erection, testing & commissioning of 20 mtr. High Mast with power tool based on the following parameters/ requirements of the Department. The power tool motorized of suitable rating. complete in all respects should be installed in the pole of reputed make ISI marked only. The structural design and drawings issued by the OEM shall be got vetted from NIT/ any Government institution before starting of this work and work shall be carried out as per structural drawings of steel and foundation issued by the High Mast OEM. Make: Valmount/ Surya/ Utkarsh/ Bajaj/ Ventura/ Jindal/ Phillips/ Transrail/ GE/ Crompton only. |
| 2 | A. High Mast Structure |
| 3 | Height of Mast: 20 m |
| 4 | Material of Construction: BS EN 10025 / IS 2062 |
| 5 | Thickness of Material – Top Section: 3 mm |
| 6 | Thickness of Material – Bottom Section: 4 mm |
| 7 | Cross Section of Mast: 20‑sided polygon |
| 8 | Length of Sections – Top Section: 10.30 m |
| 9 | Length of Sections – Bottom Section: 10.30 m |
| 10 | Base Diameter: 410 mm (Approx) |
| 11 | Top Diameter: 150 mm (Approx) |
| 12 | Type of Joints: Stress slip‑fit joints |
| 13 | Length of Overlap: 1.5 × diameter of insertion |
| 14 | Metal Protection: Hot‑dip galvanised (IS 4759 / IS 2629) |
| 15 | Galvanisation Thickness: Average 65 microns |
| 16 | Door Opening Size: 1200 mm × 300 mm |
| 17 | Door Locking Type: Close‑fitting door with Allen key locking; reinforced to avoid buckling |
| 18 | Lightning Protection Finial: GI single spike, 1200 mm |
| 19 | Base Plate Diameter: 570 mm |
| 20 | Base Plate Thickness: 30 mm |
| 21 | B. Dynamic Loading (Site Conditions) |
| 22 | Maximum Wind Speed (IS 875‑1987): 180 km/hr |
| 23 | Number of Foundation Bolts: 8 |
| 24 | PCD of Foundation Bolts: 490 mm |
| 25 | Diameter of Foundation Bolts: M30 |
| 26 | Length of Foundation Bolts: 850 mm |
| 27 | C. Lantern Carriage |
| 28 | Material: 40 NB ERW Class‑B MS Pipe |
| 29 | Lantern Carriage Ring Diameter: 600 mm (ID) |
| 30 | Construction: 6‑arm welded |
| 31 | Number of Joints: 2 segments |
| 32 | Load Capacity: 6 luminaires (Asymmetrical) |
| 33 | D. Winch |
| 34 | Number of Drums: Double drum |
| 35 | Gear Ratio: 50:1 |
| 36 | Capacity: SWL 750 kg |
| 37 | Operation: Motor & manual |
| 38 | Lubrication: Self‑lubricating, permanent oil bath |
| 39 | Lubricant Type: SAE‑90 / SAE‑140 |
| 40 | E. Stainless Steel Wire Rope |
| 41 | Grade: AISI 316 |
| 42 | Diameter: 6 mm |
| 43 | Construction: 7/19 |
| 44 | Number of Ropes: 3 nos (lantern carriage), 2 nos (winch) |
| 45 | Thimbles & Terminals: Provided |
| 46 | Breaking Load Capacity: 2350 kg per rope |
| 47 | F. Trailing Cable |
| 48 | Type: Flexible copper, 5‑core, 4 sq.mm |
| 49 | Material: EPR insulated, PCP/PVC sheathed |
| 50 | Make: IS‑approved |
| 51 | Circuits per Mast: 1 |
| 52 | G. Power Tool |
| 53 | Model: Integral |
| 54 | Capacity: 1.5 HP |
| 55 | Speed: Single speed |
| 56 | Reversible: Yes |
| 57 | Input Supply: 415 V |
| 58 | H. Aviation Light |
| 59 | Type: Low‑intensity twin type |
| 60 | Power Consumption: <18 W @ 230 V AC |
| 61 | Light Intensity: >10 candela @ 360° |
| 62 | Average Burning Hours: 100,000 hrs |
| 63 | IP Rating: IP65 |
| 64 | Body Material: Cast aluminium |
| 65 | Lamp: 300 super‑bright red LEDs per lamp |
| 66 | Dome: Red transparent polycarbonate |
| 67 | The foundation & erection work for the pole shall be carried out as mentioned below: (i) Excavation of pit of suitable size (ii) providing 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) PCC of suitable size at bottom of pit (iii) Providing bottom raft reinforcement with 16 mm dia. steel rods and suitable size and thickness ready mix M-20 grade RCC (iv) Providing top raft reinforcement with 10 mm dia. steel rods and suitable size and thickness ready mix M-20 grade RCC above bottom raft reinforcement. (v) Providing pedestal reinforcement with 6 mm and 12 mm dia. steel rods and ready mix M-20 grade, RCC of 1m above ground level.(vi) 6 mm thick, 1:3 (1 cement : 3 coarse sand) plastering work for finishing the pedestal.(vii) Refilling the pit with excavated earth including disposal of surplus earth as directed within a lead of 50 metres. .(viii) This work shall be carried out with special Tools and Plant such as suitable capacity excavator, crane for excavation, erection of pole, etc complete as required |
| 68 | Supplying, Installation, Testing & Commissioning of minimum 300 watt LED Flood Light on lantern carriage arrangement of the high mast, powder coated pressure die cast aluminium body (System lumen efficacy ≥120 lm/Watt) with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, lenses for beam angle 30 deg-120deg or as per the application and the project requirement, suitable tiltable fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C) Make: K-Lite, Phillips, Leksa, Jaquar, Panasonic, Surya, Wipro, LT, Crompton only. |
| 69 | Design, Manufacturing, supplying, fixing in position, testing and commissioning of out door type CPRI approved dust, damp, vermin & water proof, weather proof type cubical feeder pillar panel fabricated from 2mm thick CRCA sheet steel including locking arrangement complete with hinged and lockable doors , incomer MCCB, busbar, spreader links complete with interconnections copper crimping lugs, brass glands bonding to earth and painting, suitable for use at 415 volts, 3 phase 4 wire 50 Hz system . The panels fault withstanding capacity shall be of 25 MVA at 415 volts. All live accessories part shall be shrouded and all equipment shall be finger touch proof. It should be including all civil works (Feeder Pillar foundation) like excavation, PCC, bricks work, plastering, refilling, providing PVC sleeves in foundation etc. It should be erected in the 1:2:4 cement concrete platform of suitable dimensions 15cm high form ground level and 45 mm thick. The cubical pedestal shall be 15 cm from the top of cement concrete platform including epoxy painting of feeder pillar, interconnection, painting, bonding to the existing earth etc. etc complete as per specifications as required:A)INCOMING: 1 no. 63A, 415V, Ics=25kA, 4P MCCB with thermal magnetic trip unit, O/L, S/C & E/F protection.B) INSTRUMENTS WITH INCOMER: ● 1 no. Digital multifunction meter (V+A+Hz) with a set of cast resin CTs 200/5A. MCB BUS BARS-I : 100A TPN bus bars of aluminium alloy. ● 1 Set of ON / OFF indicating lamps ● 1 Set of RYB indicating lamps ● 1 Nos. Selector switch for lighting control to switch between between auto and manual mode. D) OUTGOING ● 4 nos. 32A 415V, 4P MCB of 10kA . 1 nos. 32A 415V, 4P MCB of 10kA with 40A 4P Contactor & Astronomical digital time switch to be mounted in feeder pillars for automatic switching On & OFF of street lights at sun set & sun rise or twilight (Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. ● 3 Nos. Contactor 18A/50A RATING for timer & reverse forward motion ● 3 Nos. Push Buttons for Forward, Reverse & Stop of 3 phase motor. Compartment for Outdoor Light Controller (OLC) insallation complete in all respect. ● Control SP MCB 6A 10KA ● 1 Set of SPD device of suitable rating. Make of Switchgear: LK/ ABB/ Legrand/ Schneider only |
| 70 | Supply and Laying of 10 Sq. mm x4 core PVC insulated and sheathed Armored Aluminum conductor cable PVC insulated and PVC sheathed armoured/ XLPE power cable & Served cable working voltage upto 1100 Volt. grade to be laid direct on surface as required. The job include the cost of making connections with suitable size of Al. Lugs/ thimbles, testing, commissioning from feeder pillar with the main building panel etc. as required to the entire satisfaction of Engineer in Charge. The cable should be of Polycab/ Finolex/ Havells make only. |
| 71 | Supply and Laying of 10 Sq. mm x4 core PVC insulated and sheathed Armored Aluminum conductor cable PVC insulated and PVC sheathed armoured/ XLPE power cable & Served cable working voltage upto 1100 Volt. grade to be laid in direct in ground including excavation and refilling the trench etc as required including making good of the surface as before starting the work including pavers, etc.. The job include the cost of making connections with suitable size of Al. Lugs/ thimbles, testing, commissioning with the main building panel etc. from feeder pillar to main panel of the building as required to the entire satisfaction of Engineer in Charge. The cable should be of Polycab/ Finolex/ Havells/ make only. |
| 72 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit as required 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Make: Polycab/ Havells Finolex or as approved by Engineer in Charge. |
| 73 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed heavy class PVC conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. Make: Polycab/ Finolex/Havells or as approved by Engineer in Charge. |
| 74 | Supplying and fixing true power make advanced earthing system having GI pipe 3 meter long 50 mm dia with terminal size 50x6 mm ,internal strip size 25x3 with 50 Kg compound including exvation of pit and refiling the same and making earthing pit cover 12 inch dia as required complete in all respect. Make :- True power, Earth plus, Ashloka as approved by Engineer-in-charge. |
| 75 | Extra for salt and charcoal for pipe electrode complete as required. |
| 76 | Providing and fixing 6 SWG G.I. wire dia. on surface or in recess for loop earthing as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 17, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 3 daysNov 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender