Tender For Further Upgradation/ Enhancement Of The Work Supply, Installation, Testing And Commissioning Of Air Handling Units, Convectors, Radiators And Piping In The Main Hospital
Tender Value
97.84 Lakhs
Estimated cost
Bid Submission
16 Nov 2026
2 days left
EMD
1.96 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Srinagar → Jammu and Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Further Upgradation/ Enhancement Of The Work Supply, Installation, Testing And Commissioning Of Air Handling Units, Convectors, Radiators And Piping In The Main Hospital
BOQ
| Sl. No. | Item Description |
| 1 | Part ADisconnection, dismounting, dismantling of existing Air Handling Unit of Emergency OT by using skilled manpower, tools and tackles, chain pulley block & safety items etc. The old AHU shall be shifted to the place identified by site Engineer in the premised of SKIMS and handling over to condemnation /disposal department SKIMS Soura after obtaining proper receipt. The job includes cleaning of surfaces and places and removing unwanted and scrap items by using shifting trolley. |
| 2 | Fabrication, Supply, installation, testing and commissioning of 50 TR/20000 CFM capacity, draw through type air handling unit double skin with both chilled water and hot water coils, mixing chamber, heat recovery wheel (thermal wheel) and exhaust system meeting all the guidelines/standards for hospital with some of the detailed specification & requirements as per technical specifications as appended in annexure B : - |
| 3 | INSULATED CHILLED WATER PIPING (Nitrile rubber Insulation):Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastomeric nitrile rubber of minimum 45 Kg/ cum density, thermal conductivity 0.037 W/MK or better at 20 deg. mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589. |
| 4 | 80 mm dia. (32mm thickness insulation) |
| 5 | 65 mm dia. (32mm thickness insulation) |
| 6 | 50mm dia. (32mm thickness insulation) |
| 7 | Supplying, laying/ fixing, testing and commissioning of G.I. pipe Class “B” as per IS-1239 of following sizes: |
| 8 | 40mm diameter |
| 9 | 25 mm diameter |
| 10 | Supply, fixing, testing and commissioning of 3-Way Pressure Independent Control Valve (PICV) PN 1.6 including fittings, accessories etc. |
| 11 | Supplying, fixing, testing and commissioning of following valves, guages, strainers for condenser water circulation as per specification:Butterfly valve (Manual) with CI BODY SS Disc nitrile sheet & O-ring & PN 16 pressure rating as specified. |
| 12 | 80mm diameter |
| 13 | 65mm diameter |
| 14 | 50mm diameter |
| 15 | SITC of CI ball valve (threaded) with PN 1.6 ratings of following dia. The job also includes sealing materials, nuts/bolts wherever required, and all necessary accessories for proper installation. |
| 16 | 40mm diameter |
| 17 | 25mm diameter |
| 18 | SITC of Cast Iron Y-Strainer flanges end PN 1.6 rating of following sizes with allied jobs as per site requirements. |
| 19 | Providing and fixing in position the Bi-metal Dial thermometer Temperature Guage 4” Dail Size ½ “BSP (M) connection , SS case and SS Wetted parts completer as required. |
| 20 | Providing and fitting of Fully Stainless Steel Pressure Gauge ( Bourdon Beryllium copper , Socket SS316L, Case And Bazel SS304), 4” Dial Size, rugged Construction with EPDM Blowback, safety glass. Dail Size: 200mm , Range: 0-10 KG/CM², Dual display bar/Psi or Selectable |
| 21 | Providing & fitting of volume control dampers of 18 swg of opposed blade type of an approved type, lever operated and complete with suitable level links & quadrants, locking devices, which will permit the dampers to be adjusted and locked in any position. |
| 22 | Dismantling, shifting and reconnecting of existing Pipeline:The existing pipelines needs to be shifted/realigned to provide adequate clearance for AHU installation, and the pipelines shall be properly reconnected after the shifting work as per directions of the site Engineer |
| 23 | Dismantling of false ceiling including grids to facilitate the dismantling/dismounting of existing ducts and installation of new ducting. The Job includes cleaning and refitting of the false ceiling with necessary arrangements.The work shall also include repair/rectification of the existing aluminum grid framework, wherever required, and providing and fixing all necessary fasteners, fixtures, hooks, attachment rods, nuts, bolts and other accessories required for proper installation. The false ceiling shall be properly aligned, levelled, securely supported and finished to the satisfaction of the Engineer-in-Charge.Note: - The frame shall be fixed with the RCC slab by way of using attachment rods .Use of wire shall not be acceptable. |
| 24 | Supply, installation, testing and commissioning of 22/24 SWG (0.64/0.5 mm) Aluminum ducts complete with all accessories, straight & flanges with air tight joints for connecting of the ducts, all 90º elbow must be provided with double radius turning vanes, all rectangular duct taps should be made with shoe (45º) fittings i/c supports for hanging of ducts. The job also includes piercing of walls through which supply/return duct to be laid and finishing of same to the original décor. |
| 25 | Supply, Installation, Testing & Commissioning of flexible closed cell elastomeric foam Nitrile rubber duly laminated aluminum foil insulation over the Ducts. The job also includes applying thin film of adhesive on the back of the insulating material sheet and then on the metal surface and sealing of joints with 75 mm wide aluminum tape. |
| 26 | 32 mm |
| 27 | Supply, installation, testing and commissioning of 24/26 swg aluminum cladding over exposed Al Duct complete with all accessories. The job includes fixing of aluminum cladding over GI Duct using screw/fasteners. |
| 28 | Providing and fixing of suitable MS ISA, ISMC, flat bars as supports for HVAC Ductwork, including fabrication, cutting, drilling, welding, nuts, bolts, threaded rods, hangers, brackets and all accessories, complete with one coat of anti-corrosive primer. |
| 29 | Providing and laying in position specified grade of RCC including curing but excluding the cost of centering, shuttering, finishing and reinforcement .All works upto plinth level 1:1/2:3 (1 cement :1 ½ coarse sand : 3 graded stone aggregate 20 mm nominal size) |
| 30 | Form Work: Providing/laying of Shuttering/cantering including propping, strutting etc. |
| 31 | Steel reinforcement for RCC work including straightening, cutting, bending ,placing in position and binding all complete upto plinth level thermos-mechanically treated bars of grade Fe-500D or more |
| 32 | Providing and fitting Color coated CGI Roofing (24 SWG gauge). The job includes all tools and tackles such as bolts, hocks etc. required for successful completion of the job. |
| 33 | Providing and fitting of Ridge roof sheet/Ridge cap to be installed at the topmost apex where two sloping roof sections meet. The job includes all tools and tackles required for successful completion of the job. |
| 34 | Demolishing brick work in cement mortar manually/by mechanical means including stacking of serviceable material and disposal of unserviceable material |
| 35 | Providing and fitting of 20W, 220V outdoor type/Flood Light LED lights of different capacities of reputed make. The job also includes supplying and connection of single core 1.5 sqmm cables for LED lights. |
| 36 | Part BDisconnection, dismounting, dismantling of existing Air Handling Unit No. 04 at main AHU Room by using skilled manpower, tools and tackles, chain pulley block & safety items etc. The old AHU shall be shifted to the place identified by site Engineer in the premised of SKIMS and handling over to condemnation /disposal department SKIMS Soura after obtaining proper receipt. The job includes cleaning of surfaces and places and removing unwanted and scrap items by using shifting trolley. |
| 37 | Fabrication, Supply, installation, testing and commissioning of 30 TR/12,000 CFM capacity, draw through type air handling unit double skin with both chilled water and hot water coils, mixing chamber and exhaust system meeting all the guidelines/standards for hospital with some of the detailed specification & requirements as per the technical specifications as appended in anexure B |
| 38 | INSULATED CHILLED WATER PIPING (Nitrile rubber Insulation): Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastomeric nitrile rubber of minimum 45 Kg/ cum density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect.Note: The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS: 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589. |
| 39 | 80 mm dia. (32mm thickness insulation) |
| 40 | 65 mm dia. (32mm thickness insulation) |
| 41 | 50mm dia. (32mm thickness insulation) |
| 42 | Supplying, laying/ fixing, testing and commissioning of G.I. pipe Class “B” as per IS-1239 of following sizes: |
| 43 | 40mm diameter |
| 44 | 25 mm diameter |
| 45 | Supply, fixing, testing and commissioning of 3-Way Pressure Independent Control Valve (PICV) including fittings, accessories etc. |
| 46 | Supplying, fixing, testing and commissioning of following valves, guages, strainers for condenser water circulation as per specification:Butterfly valve (Manual) with CI BODY SS Disc nitrile sheet & O-ring & PN 16 pressure rating as specified. |
| 47 | 80mm diameter |
| 48 | 65mm diameter |
| 49 | 50mm diameter |
| 50 | SITC of CI ball valve (threaded) with PN 1.6 ratings of following dia. The job also includes sealing materials, nuts/bolts wherever required, and all necessary accessories for proper installation. |
| 51 | 40mm diameter |
| 52 | 25mm diameter |
| 53 | SITC of Cast Iron Y-Strainer flanged end PN 1.6 rating of following sizes with allied jobs as per site requirements. |
| 54 | Providing and fixing in position the Bi-metal Dial thermometer Temperature Guage 4” Dail Size ½ “BSP (M) connection , SS case and SS Wetted parts completer as required. |
| 55 | Providing and fitting of Fully Stainless Steel Pressure Gauge ( Bourdon Beryllium copper , Socket SS316L, Case And Bazel SS304), 4” Dial Size, rugged Construction with EPDM Blowback, safety glass. Dail Size: 200mm , Range: 0-10 KG/CM², Dual display bar/Psi or Selectable |
| 56 | Providing & fitting of volume control dampers of 18 swg of opposed blade type of an approved type, lever operated and complete with suitable level links & quadrants, locking devices, which will permit the dampers to be adjusted and locked in any position. |
| 57 | Supply, installation, testing and commissioning of 24 swg sheet metal ducts fabricated from galvanized steel sheets (GI) complete with all accessories, straight & smooth finished G.I flanges with air tight joints for connecting of the ducts, all 90º elbow must be provided with double radius turning vanes, all rectangular duct taps should be made with shoe (45º) fittings i/c supports for hanging of ducts and shall be in compliance as per SMACNA norms. |
| 58 | Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile Rubber insulation on existing duct after applying suitable adhesive for Nitrile Rubber. The joints shall be sealed with 50mm wide and 3 mm thick self-adhesive nitrile rubber tape insulation complete as per specifications and as required. |
| 59 | 32 mm |
| 60 | Supply, installation, testing and commissioning of 24/26 swg aluminum cladding over exposed GI Duct duly insulated with nitrile rubber complete with all accessories. The job includes fixing of aluminum cladding over GI Duct using screw/fasteners. |
| 61 | Providing and fixing suitable MS ISA, ISMC, flat bars as supports for HVAC Ductwork, including fabrication, cutting, drilling, welding, nuts, bolts, threaded rods, hangers, brackets and all accessories, complete with one coat of anti-corrosive primer. |
| 62 | Demolishing brick work in cement mortar manually/by mechanical means including stacking of serviceable material and disposal of unserviceable material |
| 63 | Supply installation testing and commissioning of inline duct fan. The fan motor shall be suitable for single phase 50 Hz AC supply. Inline fan shall incorporate axial flow fan with TEFC (IP44) motor. The capacity of the fan is given as under: |
| 64 | Air Qty. : 3000 cfmStatic pressure: 25mm or aboveMotor rating: as per OEM |
| 65 | Air Qty. : 6000 cfmStatic pressure: 25mm or aboveMotor rating: as per OEM |
| 66 | Providing, Installation, testing and commissioning of axial exhaust fans of following specifications• Capacity: 5000 CFM;• Fan type: Axial• Static Pressure: 25mm or above• Motor capacity: as per OEM• RPM = 1400; Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysNov 16, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender