Tender For Construction Of 100 Beded Critical Care Block (Ccb) At Howrah District Hospital, Howrah--- Supply Installation Testing and Commissioning of Dg Set.
Tender Value
1.05 Crore
Estimated cost
Bid Submission
30 Nov 2026
18 days left
EMD
2.11 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Howrah → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Construction Of 100 Beded Critical Care Block (Ccb) At Howrah District Hospital, Howrah--- Supply Installation Testing and Commissioning of Dg Set.
BOQ
| Sl. No. | Item Description |
| 1 | SITC of 1010 KVA ,415V,50Hz 3Phase Silent Diesel Generator Set incl full tank HSD oil,comprising of Engine,Alternator,separate AMF panel ,Base frame ,Fuel tank,Battery,CPCB-II approved Engine & Acoustic Enclosure having following specifications, Engine deration calculation require to submit from Engine Manufacturer Only. Engine should not derate at 50 deg C.:- |
| 2 | Engine:- |
| 3 | Engine Type: 4 Stroke Diesel Engine |
| 4 | RPM:1500 |
| 5 | Rated Output:1180 BHP or Higher |
| 6 | Duty: PRIME POWER |
| 7 | Cooling: Coolant with radiator |
| 8 | Cylinder: As per OEM Standard |
| 9 | Aspiration: Turbo Charged |
| 10 | Type of Governor: Electrnoic A1 |
| 11 | Fuel Tank Capacity: Minimum Capacity 990 Ltrs |
| 12 | Fuel Consumption- at 50% rated load with Radiator or Fan: 116.1 Ltr/Hr (Maximum) |
| 13 | Fuel Consumption- at 75% rated load with Radiator or Fan: 153.3 Ltr/Hr (Maximum) |
| 14 | Fuel Consumption- at 100% rated load with Radiator or Fan: 203.8 Ltr/Hr (Maximum) |
| 15 | Over Load Capacity: 10% Overload for one hourfor every 12 hours continuous running at Full load or better |
| 16 | Engine instrument Panel:Consisting of starting switch with Key,Lube OilIndicator,water temperature Indicator, RPM indicator and Hour meter |
| 17 | Safety Controls:Emergency Stop ,Low Lube Oil Pressure warings/Shutdown ,High Engine Water Temp warning/Shutdown,sensor failure Indicator,Engine over speed indicator,Battery Charging and Low barttery indicator |
| 18 | Exhaust Silencer: Hospital Grade |
| 19 | Starting System: 12V/24V starting system complete with starter motor, charging alternator with rectifier and Cut-out as per manufacturer standard |
| 20 | Battery: Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak BATTERY WARNING. |
| 21 | Alternator:- |
| 22 | Rating:415V,3PH 50Hz,1010 KVA ,1500rpm, 0.8 PF |
| 23 | Type: Brushless, Self Regulated, Excitation: As per OEM Standard |
| 24 | Insulation: Calss H (Tempt. 150 deg. To 270 deg) |
| 25 | Protection: screen-protected drip proof with Min IP-23 degree of protection |
| 26 | RPM:1500 |
| 27 | Voltage Regulation: +/- 5% at full load |
| 28 | Winding Connection: Star with Neutral (2/3 Pitch, Stator- Double layer & Rotor - Dynamically balanced) |
| 29 | Total Harmonic distortion in output waveform: Less 5% |
| 30 | AMF Panel:- |
| 31 | Cubical type floor mounted AMF Panel made from 14 SWG Sheet Steel, duly pretreated,powder coated painted and aesthetically finished, suitable for controlling of 1010 KVA DG set having following specification/ features. Manufactured by the OEM/CPRI/Approved Panel builder. |
| 32 | 415V, 1600A ( Full load current) , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. (Master pact ) NW/ L&T (‘U power’ Series) / ABB Emax] - 2Sets |
| 33 | ii) In Built By-Pass switch for rated capacity |
| 34 | iii)on-delay timer for load change over |
| 35 | iv)On delay timer for engine shut off |
| 36 | Engine On-Off switch (Push button type), Emergency stop ,Remote Start/Stop Control. , Manual Run / Stop Control switch , Panel Lamp/ Lamp Test Control Switch |
| 37 | vi)Battery charger completer with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine. |
| 38 | vii)Minimum five number indicating lamps to indicate \\"mains ON\\" LOAD MAINS Set running \\"load on set\\" battery charger on\\" |
| 39 | viii) Audio visual alarm for Low lubricating oil pressure, \\"High coolant temperature Start failure ,and DG over load.\\" |
| 40 | ix)Mode selector for setting the panel on Auto/Man/ Test Mode. |
| 41 | x)Microprocessor based relay with composite meter for digital display of following. |
| 42 | a)Generator voltage/AC Mains voltage |
| 43 | b)Generator Current in all phase |
| 44 | c)Frequency |
| 45 | d)Power Factor |
| 46 | e)Indication for Alternator supply |
| 47 | f) Running time indication number of hours of operation and service intervals ,service due indications |
| 48 | The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15(fifteen) second from the instant of mains failure. |
| 49 | Acoustic Enclosure:- |
| 50 | The DG set should have integrated acoustic enclosure at the manufacturing state itself High quality acoustic must be certified as per CPCB-II norms. |
| 51 | Base Frame-Rugged in construction fabricated out of ISMC Channel for mounting the engine, Alternator, Acoustic Enclosure etc. mounted on AVM pads and having provision for lifting Hook. |
| 52 | INSTALLATION |
| 53 | S&F MS angle iron structure made of (80x80x6)mm MS angle 50mm X 6mm MS flat , nut bolt etc to support 350mm dia MS pipe, chair for AMF panel etc. Incl painting and foundation if any as per GS. [For continuous vertical suppot of 1 set exhaust pipe along wall and vertical supports of horizontal run at suitable interval] |
| 54 | S&F special type MS angle iron bracket support of 40x40x6 mm MS angle with flat iron clamp with nut bolts washers etcsuitable for 350mm dia (vertical run) |
| 55 | Supply & Installation of exhaust pipe line (thickness 4mm) connection with MS black pipe, ISI approved, necessery flanges, nuts, bolts, washers, gasket incl. electrical welding where necessary |
| 56 | 400 mm (16\\") dia |
| 57 | 350 mm (14\\") dia |
| 58 | S&F of 350mm/450mm MS heavy type reducing \\"T\\"/\\"Y\\" for 1010 KVA DG sets |
| 59 | S&F 400mm MS heavy type long bend with suitable size and number MS plug incl sockets with short piece |
| 60 | S&F 350mm MS heavy type long bend with suitable size and number MS plug incl sockets with short piece |
| 61 | S&F rain protection canopy suitable for 400mm/350mm MS pipe. |
| 62 | Painting of any steel/ iron surface with no. of coats of paints as given below with ready mixed painUprimer of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint. |
| 63 | 1st coat of aluminium paint over one coat of RO priming |
| 64 | 2nd coat of aluminium paint over 1st coat |
| 65 | Wrapping the residue type exhaust silencer pipe for 1010 KVA DG |
| 66 | Wrapping the Exhaust pipe line (400mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EiC. |
| 67 | Wrapping the Exhaust pipe line (350mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EiC. |
| 68 | Hiring charges for scaffolding by bamboo, coir rope by square type arrangement for smooth working and lifting of MS black pipe for vertical installation including dismantling after completion of work. |
| 69 | Supply, transporation & pouring of HSD fuel incl. loading and unloading in both side also making the transportation charge from pump station to Section office site. |
| 70 | Supply & delivery of 500 ltrs. Capacity heavy gauge MS sheet barrel with MS angle made support stand. |
| 71 | Supply & delivery of best quality oil hand pump with 1\\"(25.4mm) dia PVC flexible pipe (15' ft. approx.) |
| 72 | Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil. |
| 73 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.(For DG Body Earthing) |
| 74 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.(For DG Neutral Earthing) |
| 75 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 76 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
| 77 | Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required. |
| 78 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 79 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 80 | Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required |
| 81 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.100 mm dia |
| 82 | Supply and laying of following size copper Armoured control cable,after cutting floor/pavent/wall/and making holes incl. Embedding the cable at an average depth as 75mm and mending good the damages to original finish incl. Removing the rubbish as per direction of EIC. |
| 83 | 10 core 2.5sqmm |
| 84 | 2 core 2.5sqmm |
| 85 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : |
| 86 | 10 core 2.5Sqmm Copper Aurmoured cable |
| 87 | 2 core 2.5Sqmm Coooer Aurmoured cable |
| 88 | Finishing the end of the Cu armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials. |
| 89 | 10 core 2.5Sqmm Copper Aurmoured cable |
| 90 | 2 core 2.5Sqmm Coooer Aurmoured cable |
| 91 | Terms and Conditions |
| 92 | Rate should be quoted inclusive of all applicable taxes and Duty etc. |
| 93 | All materials, equipments & accessories must conform to relivent IS specifications. The DG set to be supplied must be from the authorized OEM of the respective Engine Manufacturer. |
| 94 | Nacessary manufacturer's test certificate for Diesel Engine, Alternator etc. will have to submit in triplicate copy during delivery for the equipment. |
| 95 | Copy of \\"Type Approval Certificate\\" and Certificate of \\"COP\\" must be produced at the time of delivery issued from component Authority (As per COP-II) |
| 96 | Circuit Diagram for AMF panel must be submitted from the Manufacturer/OEM. |
| 97 | The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is latter. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. |
| 98 | Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. |
| 99 | Rates are Inclusive of all taxes & duties as applicable Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 07, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 30, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 18 daysDec 02, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 20 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender