Housing Urban and Rular Development Government Departments Closing in 18 days TDR #58432704

Tender For Construction Of 100 Beded Critical Care Block (Ccb) At Howrah District Hospital, Howrah--- Supply Installation Testing and Commissioning of Dg Set.

Issued by Government Departments · Howrah, West Bengal
Tender Value
1.05 Crore
Estimated cost
Bid Submission
30 Nov 2026
18 days left
EMD
2.11 Lakhs
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Howrah → West Bengal
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Construction Of 100 Beded Critical Care Block (Ccb) At Howrah District Hospital, Howrah--- Supply Installation Testing and Commissioning of Dg Set.

BOQ

Name of Work:- Construction of 100 beded Critical Care Block (CCB) at Howrah District Hospital, Howrah--- SITC of DG Set.
Sl. No. Item Description
1SITC of 1010 KVA ,415V,50Hz 3Phase Silent Diesel Generator Set incl full tank HSD oil,comprising of Engine,Alternator,separate AMF panel ,Base frame ,Fuel tank,Battery,CPCB-II approved Engine & Acoustic Enclosure having following specifications, Engine deration calculation require to submit from Engine Manufacturer Only. Engine should not derate at 50 deg C.:-
2Engine:-
3Engine Type: 4 Stroke Diesel Engine
4RPM:1500
5Rated Output:1180 BHP or Higher
6Duty: PRIME POWER
7Cooling: Coolant with radiator
8Cylinder: As per OEM Standard
9Aspiration: Turbo Charged
10Type of Governor: Electrnoic A1
11Fuel Tank Capacity: Minimum Capacity 990 Ltrs
12Fuel Consumption- at 50% rated load with Radiator or Fan: 116.1 Ltr/Hr (Maximum)
13Fuel Consumption- at 75% rated load with Radiator or Fan: 153.3 Ltr/Hr (Maximum)
14Fuel Consumption- at 100% rated load with Radiator or Fan: 203.8 Ltr/Hr (Maximum)
15Over Load Capacity: 10% Overload for one hourfor every 12 hours continuous running at Full load or better
16Engine instrument Panel:Consisting of starting switch with Key,Lube OilIndicator,water temperature Indicator, RPM indicator and Hour meter
17Safety Controls:Emergency Stop ,Low Lube Oil Pressure warings/Shutdown ,High Engine Water Temp warning/Shutdown,sensor failure Indicator,Engine over speed indicator,Battery Charging and Low barttery indicator
18Exhaust Silencer: Hospital Grade
19Starting System: 12V/24V starting system complete with starter motor, charging alternator with rectifier and Cut-out as per manufacturer standard
20Battery: Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak BATTERY WARNING.
21Alternator:-
22Rating:415V,3PH 50Hz,1010 KVA ,1500rpm, 0.8 PF
23Type: Brushless, Self Regulated, Excitation: As per OEM Standard
24Insulation: Calss H (Tempt. 150 deg. To 270 deg)
25Protection: screen-protected drip proof with Min IP-23 degree of protection
26RPM:1500
27Voltage Regulation: +/- 5% at full load
28Winding Connection: Star with Neutral (2/3 Pitch, Stator- Double layer & Rotor - Dynamically balanced)
29Total Harmonic distortion in output waveform: Less 5%
30AMF Panel:-
31Cubical type floor mounted AMF Panel made from 14 SWG Sheet Steel, duly pretreated,powder coated painted and aesthetically finished, suitable for controlling of 1010 KVA DG set having following specification/ features. Manufactured by the OEM/CPRI/Approved Panel builder.
32415V, 1600A ( Full load current) , 50KA, EDO type ACB with O/L, S/C, E/F protection and microprocessor based protection release , U/V release etc. (Master pact ) NW/ L&T (‘U power’ Series) / ABB Emax] - 2Sets
33ii) In Built By-Pass switch for rated capacity
34iii)on-delay timer for load change over
35iv)On delay timer for engine shut off
36Engine On-Off switch (Push button type), Emergency stop ,Remote Start/Stop Control. , Manual Run / Stop Control switch , Panel Lamp/ Lamp Test Control Switch
37vi)Battery charger completer with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine.
38vii)Minimum five number indicating lamps to indicate \\"mains ON\\" LOAD MAINS Set running \\"load on set\\" battery charger on\\"
39viii) Audio visual alarm for Low lubricating oil pressure, \\"High coolant temperature Start failure ,and DG over load.\\"
40ix)Mode selector for setting the panel on Auto/Man/ Test Mode.
41x)Microprocessor based relay with composite meter for digital display of following.
42a)Generator voltage/AC Mains voltage
43b)Generator Current in all phase
44c)Frequency
45d)Power Factor
46e)Indication for Alternator supply
47f) Running time indication number of hours of operation and service intervals ,service due indications
48The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15(fifteen) second from the instant of mains failure.
49Acoustic Enclosure:-
50The DG set should have integrated acoustic enclosure at the manufacturing state itself High quality acoustic must be certified as per CPCB-II norms.
51Base Frame-Rugged in construction fabricated out of ISMC Channel for mounting the engine, Alternator, Acoustic Enclosure etc. mounted on AVM pads and having provision for lifting Hook.
52INSTALLATION
53S&F MS angle iron structure made of (80x80x6)mm MS angle 50mm X 6mm MS flat , nut bolt etc to support 350mm dia MS pipe, chair for AMF panel etc. Incl painting and foundation if any as per GS. [For continuous vertical suppot of 1 set exhaust pipe along wall and vertical supports of horizontal run at suitable interval]
54S&F special type MS angle iron bracket support of 40x40x6 mm MS angle with flat iron clamp with nut bolts washers etcsuitable for 350mm dia (vertical run)
55Supply & Installation of exhaust pipe line (thickness 4mm) connection with MS black pipe, ISI approved, necessery flanges, nuts, bolts, washers, gasket incl. electrical welding where necessary
56400 mm (16\\") dia
57350 mm (14\\") dia
58S&F of 350mm/450mm MS heavy type reducing \\"T\\"/\\"Y\\" for 1010 KVA DG sets
59S&F 400mm MS heavy type long bend with suitable size and number MS plug incl sockets with short piece
60S&F 350mm MS heavy type long bend with suitable size and number MS plug incl sockets with short piece
61S&F rain protection canopy suitable for 400mm/350mm MS pipe.
62Painting of any steel/ iron surface with no. of coats of paints as given below with ready mixed painUprimer of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint.
631st coat of aluminium paint over one coat of RO priming
642nd coat of aluminium paint over 1st coat
65Wrapping the residue type exhaust silencer pipe for 1010 KVA DG
66Wrapping the Exhaust pipe line (400mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EiC.
67Wrapping the Exhaust pipe line (350mm dia) with Al. sheet high quality with necessary wire mesh & 50mm thick glass wool.as per direction of EiC.
68Hiring charges for scaffolding by bamboo, coir rope by square type arrangement for smooth working and lifting of MS black pipe for vertical installation including dismantling after completion of work.
69Supply, transporation & pouring of HSD fuel incl. loading and unloading in both side also making the transportation charge from pump station to Section office site.
70Supply & delivery of 500 ltrs. Capacity heavy gauge MS sheet barrel with MS angle made support stand.
71Supply & delivery of best quality oil hand pump with 1\\"(25.4mm) dia PVC flexible pipe (15' ft. approx.)
72Excavation of soil for installation of Earth Electrode and filling & ramming. For Soft Soil.
73Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.(For DG Body Earthing)
74Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.(For DG Neutral Earthing)
75Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
76Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
77Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
78Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
79Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
80Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
81Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.100 mm dia
82Supply and laying of following size copper Armoured control cable,after cutting floor/pavent/wall/and making holes incl. Embedding the cable at an average depth as 75mm and mending good the damages to original finish incl. Removing the rubbish as per direction of EIC.
8310 core 2.5sqmm
842 core 2.5sqmm
85Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :
8610 core 2.5Sqmm Copper Aurmoured cable
872 core 2.5Sqmm Coooer Aurmoured cable
88Finishing the end of the Cu armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials.
8910 core 2.5Sqmm Copper Aurmoured cable
902 core 2.5Sqmm Coooer Aurmoured cable
91Terms and Conditions
92Rate should be quoted inclusive of all applicable taxes and Duty etc.
93All materials, equipments & accessories must conform to relivent IS specifications. The DG set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
94Nacessary manufacturer's test certificate for Diesel Engine, Alternator etc. will have to submit in triplicate copy during delivery for the equipment.
95Copy of \\"Type Approval Certificate\\" and Certificate of \\"COP\\" must be produced at the time of delivery issued from component Authority (As per COP-II)
96Circuit Diagram for AMF panel must be submitted from the Manufacturer/OEM.
97The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is latter. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
98Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
99Rates are Inclusive of all taxes & duties as applicable Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58432704
AUTHORITY Government Departments
TENDER VALUE 1.05 Crore
LAST DATE 30-11-2026
Authority
Authority Name Public Works Department
Work Description Tender for Construction Of 100 Beded Critical Care Block (Ccb) At Howrah District Hospital, Howrah--- Supply Installation Testing and Commissioning of Dg Set.
Basic Detail
Tender No WBPWD/SEPEC/NIT-03/2026-2027
Bidding Type Tender
Location
City Howrah
State West Bengal
Key Dates
Publish Date 07 Nov 2026
Submission Date 30 Nov 2026
Open Date 02 Dec 2026
Finance
Tender Value 1.05 Crore
Tender Fee Ref. Documents
EMD 2.11 Lakhs
Exemption Not Available
Document List
2b3e50ef-297c-449a-94fc-52beeadc985c.html
BOQ_5204828.xls
Tendernotice_1.pdf
Tendernotice_2.pdf
Tendernotice_3.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 07, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 30, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 18 days
Dec 02, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 20 days

Tender Documents

Download All (ZIP) ↓
html

2b3e50ef-297c-449a-94fc-52beeadc985c.html

xls

BOQ_5204828.xls

pdf

Tendernotice_1.pdf

pdf

Tendernotice_2.pdf

pdf

Tendernotice_3.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender