Tender For Camc Of Different Capacity Ups & Servo Stabilizers, Dg Sets , Substation, At Sms Hospital Jaipur
Tender Value
1.73 Crore
Estimated cost
Bid Submission
19 Nov 2026
12 days left
EMD
3.47 Lakhs
Bank guarantee accepted
Document Fee
2000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Camc Of Different Capacity Ups & Servo Stabilizers, Dg Sets , Substation, At Sms Hospital Jaipur
BOQ
| Sl. No. | Item Description |
| 1 | All in all Comprehensive annual maintenance and repair contract for On line UPS of following Capacity ( Excluding Replacement of Batteries ) |
| 2 | 600 VA UPS |
| 3 | 1 KVA UPS |
| 4 | 2 KVA UPS |
| 5 | 3 KVA UPS |
| 6 | 5/6 KVA UPS |
| 7 | 10 KVA UPS |
| 8 | 30KVA UPS |
| 9 | All in all comprehensive maintenance including servicing , replacement of fuel - filter, coolant , lubricating oil etc of Diesel Generating set including auto mains failure (AMF) panel , change over switch , earthing etc as per OEM guidelines and maintenance manual complete in all respet. (Excluding replacement of batteries as and when required.) |
| 10 | 15 KVA |
| 11 | 50 KVA |
| 12 | 62.5 KVA |
| 13 | 63 KVA |
| 14 | 125 KVA |
| 15 | 200 KVA |
| 16 | 250 KVA |
| 17 | 320 KVA |
| 18 | 380 KVA |
| 19 | 500 KVA |
| 20 | All in all comprehensive maintenance of 11/0.415 KV or 33/0.415 KV Distribution sub station including 11 KV circuit Breaker , Transformer and its complete accessories , Auto transfer switch ,repairing of LT/HT cables with terminations, LT panel with complete accessories , Sub station Earthings etc with maintaining of Log Books complete in all respect but excluding of transformer oil as and when required. |
| 21 | 22780 KVAx12 month=273360 kva |
| 22 | All in all comprehensive maintenance of Automatic power factor correction panel including repair / replacement of defective componenets to maintain the power factor as per Discom's permissible limit and without any penalty or surcharge. |
| 23 | Up to 125 KVAR APFC Panels |
| 24 | Above 125 kvar APFC Panels |
| 25 | Providing Manpower through Contracting agency for Supervision / Execution / Operation of various Electromechanical Installations. (one shift of 8 working Hrs per day ) on basis of minimum wages + VDA order Dt. 28.03.2025 Ministry of Labour and Employement Govt. of India |
| 26 | Engineer with B.Tech and1 Yrs, experience ,/Diploma Engineer with 3 Yrs. Experience in relevant field |
| 27 | Wireman, Electrician, Welder, Lineman, AC Mechanic, Fireman, , Supervisor, ELV technician or equivalent professional with ITI or Equivalent course and Experience of 2 years in relevant field ) |
| 28 | Technical Helper Having basic Knowledge of E&M Services |
| 29 | Replacement of Existing Battery with 12V VRLA Lead Acid Sealed maintenance free (SMF) batteries of following capacity with Warranty of 2 years (The old battery shall be retained by contractor) |
| 30 | 12V 9 AH |
| 31 | 12V 12 AH |
| 32 | 12V 18 AH |
| 33 | 12V 26 AH |
| 34 | 12V 28 AH |
| 35 | 12V 34 AH |
| 36 | 12V 42 AH |
| 37 | 12V 150 AH |
| 38 | 12V 185 AH |
| 39 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , one coat of primer & two coat of enamel paint etc. as required complete in all respect. . |
| 40 | Gravelling of Transformer / RMU Yard with 100 mm Height Gravels of Size 20 to 25 mm including leveling, Dressing etc. as Required. |
| 41 | Replacement of existing transformer oil confirming to IS: 335 after removing of old oil and remove from site (old oil shall be retained by the contractor) |
| 42 | Charges for Testing of transformer oil for its viscosity and dielectric strength including collection of sample from top and bottom of the existing transformer tank and submission of test report complete with all T & P , labour etc as required . |
| 43 | Charges for Collection , Filtration and dehydration of existing transformer oil with the help of high vaccum filtration machine and cleaning of core-coil assembly by hot oil for removal of sludge / dust particles etc. as required. |
| 44 | Supply and filling of fresh transformer oil as per IS: 335 in existing transformer along with submission of oil test report for its physical and chemical properties.The oil shall be clear and free from any suspended matter or sediments complete as required complete in all respect. . |
| 45 | Repairing of LT/HT bushings of Distribution Transformers including replacement of brass studs , porcelain insulators , nut bolts , oil seals , gaskets etc. complete as required complete in all respect. . |
| 46 | LT Bushing Set |
| 47 | 315 KVA |
| 48 | 500 KVA |
| 49 | 800 KVA |
| 50 | 1000 KVA |
| 51 | HT Bushing Set |
| 52 | 63 KVA to 500 KVA |
| 53 | 630 KVA to 1600 KVA |
| 54 | Replacement of Silica gel Breather of Distribution Transformers of following capacities complete in all respect. . |
| 55 | 250 KVA |
| 56 | 315 KVA |
| 57 | 500 KVA |
| 58 | 630 KVA |
| 59 | 800 KVA |
| 60 | 1000 KVA |
| 61 | 1250 KVA |
| 62 | Replacement of gasket of Distribution Transformers of following capacities complete in all respect. |
| 63 | 63 KVA to 500 KVA |
| 64 | 630 KVA to 1600 KVA |
| 65 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 66 | Three phase Ammeter with Inbuilt Selector Switch |
| 67 | Three phase Voltmeter with Inbuilt Selector Switch |
| 68 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 69 | Ring type tape wound CT |
| 70 | C T Class 1, Ratio 800/5 to 1200/5, Burden 15 VA |
| 71 | C T Class 1, Ratio 1500/5 to 3000/5, Burden 15 VA |
| 72 | Providing & Fixing of 110/220 V, unibody LED Indicating lamp IEC 60947 with integral circuit, IP 65 above panel & IP 20 terminal block, Approx. body dia for panel not less then 20 mm, length min. 50mm, front LED cover dia min. 27 mm, contact material phospher bronze for Led, PCB contacts shall be of brass (tin plated), impulse dielectric tested for 2.5 KV, Rated insulation resistance shall be 100 M ohm at 500VDC including connection etc. as required. |
| 73 | Red/yellow/Green colour |
| 74 | Blue / white Colour |
| 75 | Providing & Fixing of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid aberration marks and pasting the mat with synthetic rubber adhesive as required. |
| 76 | 11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage 45 KV AC (rms) |
| 77 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, life expectancy greater than 100000hrs (temp class - 25 D) in 440 V including making connections, testing etc. as required. |
| 78 | Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor (Bank) |
| 79 | Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. |
| 80 | 12.5 KVAR |
| 81 | 15.0 KVAR |
| 82 | 20.0 KVAR |
| 83 | 50.0 KVAR |
| 84 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 85 | 3 pole MCCB With Thermal Magnetic release |
| 86 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 87 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 88 | 630 Amp , 50 kA, adjustable O/L & adjustable S/C setting, |
| 89 | 4 pole MCCB With Thermal Magnetic release |
| 90 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 91 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 92 | Supply and fixing of following accessories for Moulded case circuit breaker (MCCB) compatible to main MCCB OEM as per PWD specification for electrical Works, conforming to IS/IEC 60947 P - 2 :2003 including making connection etc complete in all respect. |
| 93 | Direct Rotary Handle |
| 94 | Spreaders for 400A, 4Pole MCCB |
| 95 | Spreaders for 630A, 4Pole MCCB |
| 96 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 97 | 3.5 x 95.0 sq.mm |
| 98 | 3.5 x 120.0 sq.mm |
| 99 | 3.5 x 150.0 sq.mm |
| 100 | 3.5 x 185.0 sq.mm |
| 101 | 3.5 x 240.0 sq.mm |
| 102 | 3.5 x 300.0 sq.mm |
| 103 | 3.5 x 400.0 sq.mm |
| 104 | 3.5 x 630.0 sq.mm |
| 105 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 106 | 35.0 Sq.mm |
| 107 | 50.0 Sq.mm |
| 108 | 70.0 Sq.mm |
| 109 | 95.0 Sq.mm |
| 110 | 120.0 Sq.mm |
| 111 | 150.0 Sq.mm |
| 112 | 185.0 Sq.mm |
| 113 | 240.0 Sq.mm |
| 114 | 300.0 Sq.mm |
| 115 | 400.0 Sq.mm |
| 116 | 630.0 Sq.mm |
| 117 | All in all Comprehensive annual maintenance and repair contract for On line UPS of following Capacity ( Excluding Replacement of Batteries ) |
| 118 | 60KVA Online UPS |
| 119 | All in All annual maintenance contract for Servo Stablizers installed in various places at SMS Hospital of the following capacity complete in all respect etc as reqd. |
| 120 | 5 KVA |
| 121 | 10 KVA |
| 122 | 15 KVA |
| 123 | 30 KVA |
| 124 | Add: GST@18% Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 19, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 12 daysNov 20, 2026