Defence Statutory Bodies & Commissions/Committees Closing in 20 days TDR #58431214

Tender For Special Repair Of E/M Infrastructure At Bldg No. P-179 Of 16Ts At Afs Jalahalli

Issued by Statutory Bodies & Commissions/Committees · Bengaluru Urban, Karnataka
Tender Value
Ref. Documents
Estimated cost
Bid Submission
27 Nov 2026
20 days left
EMD
93000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Bengaluru Urban → Karnataka
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Special Repair Of E/M Infrastructure At Bldg No. P-179 Of 16Ts At Afs Jalahalli

BOQ

Name of Work:- SPECIAL REPAIR OF E/M INFRASTRUCTURE AT BLDG NO. P-179 OF 16TS AT AFS JALAHALLI
Sl. No. Item Description
1Taking down carefully copper/aluminium point wiring (light, fan, Power) complete fittings such as switches, ceiling roses pendents, regulators sockets light fittings etc for taking credit and making good disturbed surface of wall, floors, roof etc complete all as specified and directed.
2Material and labour for Point wiring complete with 1. 5 Sq mm single Core PVC insulated FRLS cable, 1100 volts grade unsheathed with multi stranded copper conductor drawn through and including PVC rigid non metalic conduit on surface/concealed with all fittings such as bend, end caps etc fixed on the surface of wall, ceiling, roof, steel structure etc. by means of suitable fixing accessories including provision of 1.5 Sq mm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor, modular metal pressed flush box surface /existing concealed in wall for suitable modules modular white top cover and plate for housing the switches, sockets, regulators etc. all as specified and as directed for One light point controlled by one switch one way 6 Amps all as specified and directed.Note: Modular cover plate,Switches, sockets outlets, Light fittngs, fans, bells & regulators shall be measured and paid for separetely.
3All as per item No. 2 but for One ceiling fan point controlled by one switch one way 6 Amps and fan regulator
4All as per item No. 2 but for One Exhaust fan/Wall mounted point controlled by one switch one way 6 Amps
5All as per item No. 2 but for One socket out let 6 Amps 3 pin on same board.
6All as per item No. 2 here -in - before but for One 2/3 pin switch socket outlet point controlled by one 6 Amps switch on Independent board.
7All as per item No. 2 here -in - before but for One light point controlled by 2 Nos two way switches.
8All as per item No. 2 here -in - before but for One 3 pin switch socket outlet combination, 15 Amps point with cables 4 sq mm all as specified and directed.
9Supply and Fix modular switch 1 way 5/6 Amp,1 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian
10Supply and Fix modular Socket,5/6A - 2/3 pin combined 2 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor/Indoasian
11Supply and Fix modular Socket, 5/15/ and 6/16A - 3/5 pin combined 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian
12Supply and Fix modular switch 1 way 15/16 Amp,1 module, complete all as specified and directed. Make :Legrand/ Crabtree/ Anchor /Indoasian
13Supply and Fix modular switch 2 way 5/6 Amp, 1 module, complete all as specified and directed.Make : Legrand/ Crabtree/ Anchor /Indoasian
14Supply & fix ceiling rose, 3 phase/ PVC/ polycarbonate insolated body all as specified and as directed.
15S&F Modular fan regulator 120W, 2 Module for ceiling fan complete all as specified and directed.
16Supply and fix of modular white cover plate with frame, 1 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian
17Supply and fix of modular white cover plate with frame, 2 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian
18Supply and fix of modular white cover plate with frame, 3 module, complete all as specified and directed. Make : Legrand/ Crabtree/ Anchor/Indoasian
19Supply and fix of modular white cover plate with frame,4 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian
20Supply and fix of modular white cover plate with frame,6 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian
21Supply and fix of modular white cover plate with frame,08 module, complete all as specified and directed. Make : Legrand /Crabtree/ Anchor/Indoasian
22Taking down of old unserviceable ceiling fan of any size sealing cable end, dismantling blades and removing fan and blades to store for re-use or otherwise complete all as specified and directed.
23Refixing existing serviceable ceiling fans 1200/1400 mm sweep after servicing, painting. of ceiling fan with one coat of synthetic enamel paint by spraying including greasing/oiling, filling cavities with filler after cleaning all dust etc. complete all as specified and as directed by Engineer-in-Charge. Note : cost includes for replacement of rubber bush ,hanging hook with new cotter pins etc
24Supply and Fixing in repair 4 feet surface mounted batten type luminaire , lumen output of 2000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability . The luminaire and driver shall be BIS approved, complete all as specified and directed. Make : Philips/ Bajaj / CG/Havells.
25S&F 35/36 W( WW/WH) LED recess /surface type 2x2 ft luminaire with classic design & glare free soft illumination. housing with white high reflection powder coated (RAL9016) CRCA sheet. Glare free, Opal diffuser for symmetrical light distribution fixed in separate CRCA sheet frame held in with housing by screws for easy maintenance. High efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle of 100° to ensure better uniformity. Powered by an independent Isolated, SELF Output electronic LED driver (SMPS based constant current supply) efficiency of 85% with built-in Surge protection 3Kv. System Lumen Output of 3000 lumens. Make : Philips/ Bajaj /CG/Havells.
26S&F Sub main wiring with 2 runs of single core, 1.5 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 1.5 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
27S&F Sub main wiring with 2 runs of single core, 2.5 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 2.5 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
28S&F in repair factory made powder coated distribution board SPN 4 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
29S&F MCB single pole 240 volts 6 to 32 Amps, 10 KA rupturing capacity complete all as specified and as directed.Make : Legrand/ L&T/ Indo Asian.
30S&F in repair factory made powder coated distribution board SPN 8 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
31S & F MCB SPN 240 volts 40 to 63 Amps 'C' series 10 KA breaking capacity complete all as specified and as directed .Make : Legrand/ L&T/ Indo Asian.
32M& L in repair PVC casing medium grade of size 40 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
33M& L in repair PVC casing medium grade of size 32 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
34Dismantling the existing unserviceable False ceiling from the position of size 2' x 2' size with aluminum snap grid complete all as specified and directed.
35S&F PVC insulation panels with EPS stuck to 1mm plain PVC sheet suitably placed in false ceiling grid made of Aluminium/G.I./M.S. as per specification and drawing (Thickness of the PVC insulation panel shall be 10 mm) complete all as specified and directed.
36S&F in repair Sub main wiring with 2 runs of single core, 4 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 4.00 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
37S&F in repair Sub main wiring with 2 runs of single core, 6 Sqmm PVC insulated, unsheathed, 1100 volts grade multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on roof, walls, ceiling etc including 6.00 Sqmm PVC insulated, unsheathed, single core, multistranded, copper conductor as earth continuity wire complete as specified and directed. (Note : Two runs of cable and one run of earth wire including PVC conduit /Casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
38S&F in repair factory made powder coated distribution board SPN 12 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete conforming to IS: 8623, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
39S&F in repair factory made powder coated distribution board TPN, 4 way double door MCB DB including bus bar, Neutral bar, standard DIN rail, earth bar complete all as specified and directed.Make : Indoasian/ Havells/ Legrand.
40Taking down of old unserviceable exhaust fan/Wall mounted fan of any size sealing cable end, dismantling blades and removing fan and blades to store for re-use or otherwise complete all as specified and directed.
41S & F TPN, MCB 40 to 63 Amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
42Refixing existing serviceable Exhaust fans of any size/sweep after servicing, painting Exhaust fan with one coat of synthetic enamel paint by spraying including greasing/oiling, filling cavities with filler after cleaning all dust etc. complete all as specified and as directed.
43M&L for cutting of hole through stone wall with the help of Core cutting machine including providing, fixing and removing shoring,cleaning,internal plastering and removing surplus hard core,rubbish not exceeding 50 mtrs including fixing of exhaust fan of size 250-300 mm all as specified and as directed.
44Supply and fixing in replacement Exhaust fan 300 mm sweep, Heavy duty 230/240 volt AC single phase, metal Body, 1400 RPM, with blade, frame, louvers fixing exhaust fan with suitable nuts bolts and louvers and make good the surface to match with existing surface complete. Make : Havells/ Bajaj/ Crompton Greaves(Note- Old us exhaust fan will be deposited to mes store yard.)
45M&L in repair louver made of galvanised steel suitable for 300/450 mm size exhaust fan, fixed on wall including necessary fixing arrengement up to height 11 mtr complete all as specified and directed.Note : All safety measures shall be the responsible of the contractor.
46Supply and Fixing in repair 2 feet surface mounted batten type luminaire , lumen output of 1000 lumens, high efficiency long life LED package in integral module with lumen efficacy of >100 lm/w, viewing angle not less than 120° to ensure better uniformity with an operating voltage range from 140V-270V. The luminaire shall have a white extrusion housing with a poly carbonate diffuser to provide uniform light and sleek design with width not more than 22 mm. The luminaire shall have a CRI >80, Color temperature 6500K, THD <10% and PF >0.95,SDCM<5, IP20, IK02, Operating Temperature: -10 TO + 45 DEG.C; Input Supply Voltage Range:140-270 V, Frequency :50-55 HZ. The luminaire shall have flicker content<5% and shall have high and low cut off with auto restart feature.Driver Safety requirement stds: IS 15885-2-13. The luminaire shall be EMI/ EMC compliant and shall have a internal surge protection of 4 KV. The luminaire shall have Class-1 Electrical insulation, Class-B serviceability . The luminaire and driver shall be BIS approved, complete all as specified and directed. Make : Philips/ Bajaj / CG/Havells.
47Supply and fixing round/square shape 12 watt 220 volts AC recessed/surface type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete.Make : Philips/ Bajaj /CG/Havells.
48S&F in Replacement of LED building security/street light fitting 35/36 watts made up of pressure diecast housing with toughened glass diffuser, with high power LEDs with option of secondary optic with IP66 protection, 110 LM/ watt and wired with accessories with IP 65/66 protection. Make : Philips/ Bajaj /CG/Havells.
49S & F in repair street light bracket made up of GI tubing 32 mm dia light grade of length 1.0 mtr bent to a shape with 2 Nos suitable clamp incl nut, bolt and washer for fixing on wall complete all as specified and directed.
50Supply & fix LED down/Spot lighter, 3 W complete all as specified and directed.
51Supply & fix LED down/Spot lighter, 6 W complete all as specified and directed.
52M& L in repair PVC casing medium grade of size 25 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
53M& L in repair PVC conduit medium grade of size 40 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
54M& L in repair PVC conduit medium grade of size 32 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
55M& L in repair PVC conduit medium grade of size 25 mm on wall /roof with help of screw and GI shaddle including fixing of existing serviceable copper /aluminium conductor and all fitting fixture such as Tee, Elbow and lapping complete all as specified and as directed.
56M&L for Cutting chases, pinning in brick wall making good to facings where required in brick wall and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10 cm girth complete all as specified and directed.
57M&L for Cutting chases, pinning in. making good to facings where required in brick wall and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting exc 10 cm but not exc 20 cm girth complete all as specified and directed.
58Cutting holes into or through cement concrete slabs, chajjas, etc. reinforced or otherwise not exceeding 100 Sqcm complete all as specified and directed.
59M&L in repair Sub main wiring with 4 runs of 6 Sqmm single core, PVC insulated, unsheathed 1100 Volts grade, multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on, walls, ceiling etc. as required including 6 Sqmm PVC insulated, unsheathed, multistranded, copper conductor, single core cable as earth continuity wire complete as specified and directed. Note : Four runs of cables and one run of earth wire including PVC conduit/ casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
60M&L in repair Sub main wiring with 4 runs of 10 Sqmm single core, PVC insulated, unsheathed 1100 Volts grade, multi-stranded, copper conductor cables (FRLS quality) drawn through PVC casing capping / Conduit with fitting/accessories, fixed on, walls, ceiling etc. as required including 10 Sqmm PVC insulated, unsheathed, multistranded, copper conductor, single core cable as earth continuity wire complete as specified and directed. Note : Four runs of cables and one run of earth wire including PVC conduit/ casing capping shall be measured as one run length) Make : Havells/ Polycab/ Plaza
61S&F factory made powder coated distribution board VTPN, 8 way double door MCCB DB including bus bar, Neutral bar, standard DIN rail, earth bar complete including taking down unserviceable DB with fitting fixture complete all as specified and directed.Make : Indoasian/ Havells/ Legrand.
62S&F distribution board MCCB four pole, 100 Amp ultimate breaking capacity 16 KA conforming to IEC -61439-1, complete all as specified and directed. Make : Legrand/ L&T/ Indo Asian
63Supply and fix 4 Pole MCCB, 415 volts, fixed type, 160 Amp, 50 Hz, with rupturing capacity 25 KA with thermal & magnetic setting with extended terminals,replacemenr to LT panel/ Feeder pillar box including connecting lugs with busbar and mounting arrengments i.e screws,bolt, nut, washers incl taking out old unsv complete all as specified and directed. Make : Indo Asian/L&T/Schneider
64Excavation in trenches not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth and getting out in soft/lose soil , complete all as specified and directed.
65Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick, complete all as specified and directed.
66Removing surplus excavated material (soil) not exc 50 meter and depositing where directed at a level not exc 1.5 meter above the starting point, complete all as specified and directed.
67Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
68Material and labour for well burnt bricks ‘B’ class as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench, complete all as specified and directed.
69Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :-(i) Earth work and excavation in any type of soil(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick ,complete all as specified and as directed.(iii) Removing excavated material out side MD land.(iv) Laying of any type/any bore of pipe in trenches including taking down existing unserviceable pipe. Supply of pipe shall be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
70Supply only GI pipe light grade for cable protection of size 100 mm bore with fittings, complete all as specified and directed.
71Material and labour for Boring of holes under road, pavement hard standings by trenchless technology using ultra sound technique and necessary machine including supply of HDPE pipes upto 100 mm dia suitable for 0.4 Mpa working pressure, complete all as specified and directed.
72Material and labour in repair for 4 core 6 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
73Material and labour in repair for 3 ½ core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make : Havells, Polycab, RPG Asian
74Supply, installation, testing and commissioning LT Feeder pillar box double door CPRI Tested of Size 400X250X350mm suitable for 3 phase 415 Volts of suitable size out door made out of 3.15mm thick CRCA sheet for outdoor panel with angle iron frame of size 32x32x5mm cubical type complete with aluminium bus bar 800 Amp and including PCC foundation as per site requirement to accomodate to the following :-INCOMING(a) MCCB with Microprocessor type 4 Pole, 415 V of capacity 630 Amps, 50 KA - 01 No(b) LED indicating lamp R-Y-B - 03 Nos.(c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. OUTGOING(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amps, 36 KA - 01 No(b)MCCB with thermal magnetic release 4 Pole, 415 V of capacity 320 Amps, 36 KA - 01 No(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amps, 25 KA - 01 No(d)MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amps, 25 KA - 01 No(e)MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amps,16 KA - 01 No
75Supply, installation, commissioning and testing of floor mounted, free standing OEM made type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of CPRI approved IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate for bedding upto a height of 45 CM above ground level, complete all as specified and directed and comprising of the following:- Please Enable Macros to View BoQ information
76Supply, installation, commissioning and testing of floor mounted, free standing OEM made type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of CPRI approved IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel shall be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate for bedding upto a height of 45 CM above ground level, complete all as specified and directed and comprising of the following:- Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58431214
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE Ref. Documents
LAST DATE 27-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Special Repair Of E/M Infrastructure At Bldg No. P-179 Of 16Ts At Afs Jalahalli
Basic Detail
Tender No 8384/E8
Bidding Type Tender
Location
City Bengaluru Urban
State Karnataka
Key Dates
Publish Date 06 Nov 2026
Submission Date 27 Nov 2026
Open Date 04 Dec 2026
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 93000
Exemption Available
Document List
09fb7374-617e-4174-9a3d-649a767040d7.html
8384GENPAGE.pdf
8384PS.pdf
BOQ_894931.xls
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 06, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 27, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 20 days
Dec 04, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 27 days

Tender Documents

Download All (ZIP) ↓
html

09fb7374-617e-4174-9a3d-649a767040d7.html

pdf

8384GENPAGE.pdf

pdf

8384PS.pdf

xls

BOQ_894931.xls

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender