Tender For Repair/ Replacement Of Lt Oh Line/ Lt Cable, Painting Of Lt Poles, Repair/Maint Of Earthing, Mccbs, Lt Panel And Maint/Repair Of Apfc Panel And Other Connected Works At New And Old Drde Gwalior Under Ge (I) R&D Delhi
Tender Overview
Project Description
Tender for Repair/ Replacement Of Lt Oh Line/ Lt Cable, Painting Of Lt Poles, Repair/Maint Of Earthing, Mccbs, Lt Panel And Maint/Repair Of Apfc Panel And Other Connected Works At New And Old Drde Gwalior Under Ge (I) R&D Delhi
BOQ
| Sl. No. | Item Description |
| 1 | Disconnecting, taking out and removing old existing unserviceable underground, LT cable of any description and in any portion complete including taking down protection pipe,PCC Cover/Bricks etc all as specified and directed by the Engineer-in-Charge for the following sizes: |
| 2 | 10 Sqmm to 25 Sqmm any core |
| 3 | 35 Sqmm to 70 Sqmm any core |
| 4 | 95 Sqmm to 150 Sqmm any core |
| 5 | Supply, laying, jointing and testing XLPE/ P.V.C insulated, armoured, heavy duty, aluminum conductor cable 1100 volts grade of any description and any make laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed by the Engineer-in-charge for the following sizes |
| 6 | 10 Sqmm 2 core |
| 7 | 16 Sqmm 4 core |
| 8 | 25 Sqmm 4 core |
| 9 | 35 Sqmm 3.5 core |
| 10 | 50 Sqmm 3.5 core |
| 11 | 70 Sqmm 3.5 core |
| 12 | 95 Sqmm 3.5 core |
| 13 | 120 Sqmm 3.5 core |
| 14 | 150 Sqmm 3.5 core |
| 15 | Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as specified and directed.Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers. |
| 16 | Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed |
| 17 | Removal of surplus excavated soil exc. 50 mtr but n. exc. 250 mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 M above the starting point etc complete all as directed. |
| 18 | M & L for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed .Note: - Punned thickness shall be measurement & paid. |
| 19 | Supplying & Laying Sub Class `B’ designation x 75 bricks old size with axis of the bricks perpendicular to the axis of the cable as in cable protection all as specified and directed |
| 20 | Supply and laying in replacement of GI pipe light grade of 80mm dia laid in trenches for protection of UG cable complete |
| 21 | All as per item No 8.00 but GI pipe 50 mm diameter complete |
| 22 | Disconnecting LT cable of size from 16 Sqmm 4 core to 35 Sqmm 3.5 core from existing panel taking out loop of cable not more than 2.5 M length, cut the worn out portion of cable includingreplacement the lugs,nut-bolt and wasers of suitable size and reconnect the existing system |
| 23 | Disconnecting LT cable of size from 50 Sqmm 3.5 core to 95 Sqmm 3.5 core from existing panel taking out loop of cable not more than 2.5 M length, cut the worn out portion of cable includingreplacement the lugs,nut-bolt and wasers of suitable size and reconnect the existing system |
| 24 | Disconnecting LT cable of size from 120 Sqmm 3.5 core to 240 Sqmm 3.5 core from existing panel taking out loop of cable not more than 2.5 M length, cut the worn out portion of cable includingreplacement the lugs,nut-bolt and waser of suitable size and reconnect the existing system |
| 25 | Disconnecting LT cable of size from 300 sqmm 3.5 core to 400 Sqmm 3.5 core from existing panel/ transformar/LT Pols and taking out loop of cable not more than 5 M length, cut the worn out portion of cable includingreplacement the lugs,nut-bolt and waser of suitable size and reconnect the existing system |
| 26 | M&L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60 cm x 6.0 mm buried in the ground to a depth not less than 2.25 mtr below ground level connected to GI 25 x 4 mm strip by means of GI nut, bolts, washers and check nut including GI Pipe pipe 40mm diameter medium grade for earth strip protection pipe complete as shown in electric plate No 03 of Sl- Part-I including 20 mm dia GI pipe medium grade for watering, unnel and PCC of 1:3:6 type C1 pit cover with RCC (1:2:4) cover of size 30cm x 30cm x 40mm with one handle for lifting made out of 8mm dia MS bar including charcoal and salt in alternative layers including all earth work for excavation and removal of surplus soil and Testing Point complete all as specified and directed. |
| 27 | M & L in repairs Earthing complete with galvanished earth plate electrode of size 600 x 600 x 6.00 mm buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanised earth strip 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and galvanised iron or steel including earth work in any type of soil, PCC work in (1:3:6) pit and RCC (1:2:4) type B-1 pit cover reinforced with 6mm diameter ms bar 75 mm c/c 10 mm diameter handle, charcoal salt 15cm alternate layer and around the earth plate as shown in electrical plate no 3 of SSR Part I 2010, 20mm diameter watering pipe medium grade 1.70 mtr long GI protection pipe light grade 40mm dia from earth pit to main board including necessary pit cover complete all as specified and as directed. |
| 28 | Earth continuity conductor passing through PVC Conduit of size 25 mm main earthing lead fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or any other indicated situation for loop earthing etc as required 25x4 mm galvanised iron strip complete all as specified and directed by Engr-in-Charge. |
| 29 | S&F MCB TP (25-63) Amps 10 KA 'C' Series 415 Volts all as specified . |
| 30 | Supply and fix in replacement of 3 Pole MCCB,100 Amp, 50 Hz, 415 V with rupturing capacity 16 KA complete all as specified and as directed. |
| 31 | S&F in repairs MCCB 125 Amps 3 pole, 415 V, breaking capacity 16 KA & connected accessories complete as specified and as directed |
| 32 | All as per item No 19.00 above but MCCB of cap 3 Pole 160 Amp, 36 KA |
| 33 | All as per item No 19.00 above but MCCB of cap 3 Pole 200 Amp, 36 KA |
| 34 | All as per item No 19.00 above but MCCB of cap 3 Pole 250 Amp, 36 KA |
| 35 | S&F in repairs MCCB 350 Amps, 3 Pole, 415 V, Adjustable type, with breaking capacity 36 KA including spreader terminals & connected accessories complete as specified & directed. |
| 36 | All as per item No 23.00 above but MCCB of cap 3 Pole 400 Amp, 36 KA |
| 37 | All as per item No 23.00 above but MCCB of cap 3 Pole 630 Amp, 50 KA |
| 38 | Supply and fix in replacement of 4 Pole MCCB, 160 Amp, 50 Hz, 415 V with rupturing capacity 36 KA. complete all as specified and as directed. |
| 39 | All as per item No 26.00 above but MCCB of cap 4 Pole 400 Amp, 36 KA |
| 40 | All as per item No 26.00 above but MCCB of cap 4 Pole 630 Amp, 50 KA |
| 41 | Supply and fixing of Aluminium thimble of size 35 sqmm for terminal end of cable complete all as specified and directed. |
| 42 | Supply and fixing of Aluminium thimble of size 50 sqmm for terminal end of cable complete all as specified and directed. |
| 43 | Supply and fixing of Aluminium thimble of size 70 sqmm for terminal end of cable complete all as specified and directed. |
| 44 | Supply and fixing of Aluminium thimble of size 95 sqmm for terminal end of cable complete all as specified and directed. |
| 45 | Supply and fixing of Aluminium thimble of size 120 sqmm for terminal end of cable complete all as specified and directed. |
| 46 | Supply and fixing of Aluminium thimble of size 150 sqmm for terminal end of cable complete all as specified and directed. |
| 47 | Supply and fixing of Aluminium thimble of size 185 sqmm for terminal end of cable complete all as specified and directed. |
| 48 | Supply and fixing of Aluminium thimble of size 240 sqmm for terminal end of cable complete all as specified and directed. |
| 49 | Supply and fixing of Aluminium thimble of size 300 sqmm for terminal end of cable complete all as specified and directed. |
| 50 | Supply and fixing of Aluminium thimble of size 400 sqmm for terminal end of cable complete all as specified and directed. |
| 51 | Supply and Fix earth pit chamber alongwith cover of Polymer, FRP Pit Cover of heavy high grade polypropylene for high stress and strain level of size 225mm x 300mm x 195mm complete all as specified and directed. Please Enable Macros to View BoQ information |
| 52 | Supply and Fix earth pit chamber alongwith cover of Polymer, FRP Pit Cover of heavy high grade polypropylene for high stress and strain level of size 225mm x 300mm x 195mm complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 20 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 27 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender