Tender For Supplying, Erecting, Testing And Commissioning Of Isolator,Apfc Panel At Mohadi Truck Terminal special repair No.147/1/B For Electric Bus(Pm E-Bus) Charging Station,Dmc Dhule.
Tender Overview
Project Description
Tender for Supplying, Erecting, Testing And Commissioning Of Isolator,Apfc Panel At Mohadi Truck Terminal special repair No.147/1/B For Electric Bus(Pm E-Bus) Charging Station,Dmc Dhule.
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 17-Nov-2026 | extend date | Date | 20-Nov-2026 |
| 2 | 13-Nov-2026 | extend dates | Date | 16-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable, 1100 V 1 core 630 sq. mm. aluminiumconductor complete erected with glands & lugs on wall/ trusses/pole or laid inprovided trench/ pipe as per specification no. CB-LT/AL |
| 2 | Supplying and erecting fencing of section having size at least 2450 mm in height from ground level and 1200 mm width with angle iron frame workerected in CC foundation and painted complete with provided earthing as per specification no. SS-AS/FSG |
| 3 | Supplying and erecting double leaf hinged door each 1500 mm in width x2450 mm in height using B class GI pipe, hinges and angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundationand painted complete as per specification no SS-AS/DLD |
| 4 | Supplying and fixing PVC synthetic elastomer electrically insulating mat with class C insulation conforming to IS: 15652 – 2006 tested having 3mm thickness upto 33 kV |
| 5 | Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS: 15652 – 2006 having 2 mm thicknessupto 3.3 kV |
| 6 | Supplying & laying (including excavation) half round reinforced cement concrete pipe of NP-2 class of 150 mm diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc.complete. |
| 7 | Supplying, erecting, testing and commissioning of 33 kV, 1600 Amp, 3-Phase, 50 Hz, outdoor type, double-break centre-rotating (DBCR), manually gang-operated isolator with earth switch, suitable for 36 kV highest system voltage, complete with solid-core porcelain post insulators, heavy-duty silver-plated copper contacts, hot-dip galvanised MS base frame, operating mechanism, GI operating rods, manual operating handle, mechanical interlocking between main isolator and earth switch, terminal connectors, earthing arrangements and all necessary accessories.The isolator shall have a rated short-time withstand current of 25 kA for 3 seconds (or higher as required by the approved switchyard design), and conform to IEC/IS 62271-102 and relevant utility specifications ( non csr as per quotation ) |
| 8 | Supplying and erecting 250 kVAr, 440 V 3 phase, 50 Hz., Contactor Logic &Intelligent Relay micro APFC passive filter panel, consisting of suitable stepsof APP/MPP type capacitor units with Detuned (harmonic filter) reactors ofsuitable rating , APFC panel shall be compliance to IEC 61439 and powerquality IEC 61921 standard as per specification no CP-ED/APFC |
| 9 | Supplying, erecting & terminating FR XLPE insulated, galvanised steelformed wire armoured (strip) cable 1100 V, 4 core 240 sq. mm. aluminiumconductor complete erected with glands & lugs, on wall/ trusses/pole or laid inprovided trench/ pipe as per specification no. CB-LT/AL |
| 10 | Providing, fabricating, supplying and erecting of M.S. structural framework for electrical cubicle room, including M.S. angles, channels, square/rectangular hollow sections, vertical supports, cross bracings, roof trusses, base plates, stiffeners and other structural members of approved sizes as per site requirements and approved drawings.The work shall include cutting, bending, welding, drilling, grinding, fabrication and assembly of structural members, providing and fixing colour-coated G.I. sheet roofing and side cladding, M.S. framed lockable entrance doors, ventilation louvers with wire mesh, necessary nuts, bolts, anchor fasteners and other accessories.The cubicle room shall be suitable for housing electrical control panels, APFC panels, distribution panels and associated equipment, with adequate space for operation, maintenance, ventilation, cable entry and safety clearances.Complete in all respects as directed by Engineer-in-Charge (non csr ) |
| 11 | Add 18% GST |
| 12 | Add 1% Insurance Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
TodayCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
TodayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender