Tender For Provn Of Sub Main Wiring Alongwith Wall Mounted Mccb Dbs And Allied Works At Golden Key Div Csd Under Ge, Clement Town.
Tender Value
9.65 Lakhs
Estimated cost
Bid Submission
27 Nov 2026
17 days left
EMD
19300
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Dehradun → Uttarakhand
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Provn Of Sub Main Wiring Alongwith Wall Mounted Mccb Dbs And Allied Works At Golden Key Div Csd Under Ge, Clement Town.
BOQ
| Sl. No. | Item Description |
| 1 | Supply and fixing wall mounted MCCB DB suitable for compact MCCBs of capacity 400 Amps, 6 ways, double door main enclosure with provision to mount TP MCCBs as outgoing, suitable size as the capacity of DBs, IP-43, factory made box of thickness min of 2mm, the panel should be factory ready enclosure type, cement spill protectors and modular designs, isolated neutral bars and zero live part exposure, airflow channels for MCCBs and multiple knockouts for cabling flexibility, type of DB with MCCB should be HSN code : 8536 or equivalent complete all as specified. Note: (i) The cost of compact MCCB will be paid separately. |
| 2 | Supply and fixing of compact MCCB suitable for wall mounted DB as per Item No 01, capacity 400 Amps, 25 KA, 50 Hz, Ics = 100%,Icu as per IEC 60947-II, suitable for isolation, adjustable overload protection & short circuit setting complete all as specified |
| 3 | Supply and fixing of compact MCCB suitable for wall mounted DB as per Item No 01, capacity 100 Amps, 16 KA, 50 Hz, Ics = 100%,Icu as per IEC 60947-II, suitable for isolation, adjustable overload protection & short circuit setting complete all as specified |
| 4 | Supply and fixing of compact MCCB suitable for wall mounted DB as per Item No 01, capacity 63 Amps, 16 KA, 50 Hz, Ics = 100%,Icu as per IEC 60947-II, suitable for isolation, adjustable overload protection & short circuit setting complete all as specified |
| 5 | M&L for Sub main wiring with proper colour coding , insulated , unsheathed , multistranded ,copper conductor FRLS, cable of 2 run 6 Sqrmm for phase and neutral and one run of 6.0 Sqrmm for earth wire unsheathed , multistranded , copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length. Note : Wiring shall be done in proper colour coding. |
| 6 | M&L for Sub main wiring with proper colour coding , insulated , unsheathed , multistranded ,copper conductor FRLS, cable of 2 run 4 Sqrmm for phase and neutral and one run of 4.0 Sqrmm for earth wire unsheathed , multistranded , copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length. Note : Wiring shall be done in proper colour coding. |
| 7 | M & L for complete point wiring with 1.5 Sqmm single core multi stranded copper conductor FRLSH insulated and unsheathed heavy duty cable in colour code including continuous earth wire with cable of size 1.5 sqmm copper conductor flexible FRLSH insulated drawn in and including concealed PVC rigid conduit medium grade ISI marked after cutting chases in wall , plastering after concealing conduit , including modular galvanised flush boxes of suitable size and white cover plate with frame as per relevant IS for mounting modular switches, sockets, fan regulators etc and including making good the disturbed surface as per existing complete all as specified and as directed by Engr In Charge for the following :- |
| 8 | All as per item No 7 above but for multi 5 pin 5 amp socket outlet on same board ISI marked complete all as specified and directed |
| 9 | All as per item No 7 above but for multi 5 pin socket outlet 5 amp socket on independent board ISI marked complete all as specified and directed |
| 10 | All as per item No 7 above but for multi 6 pin 15 Amp socket outlet independent controlled by 15 Amp switch with 2.5 sqmm copper conductor multistrand cable pvc insulated FRLS and unsheathed cable in and including PVC rigid concealed conduit 20/25 mm dia and unsheathed copper conductor multistranded cable 2.5 sqmm as earth wire FRLS pvc insulated in green color all as directed by engr-in-charge. |
| 11 | S&F of Modular Socket, 6A - 5 pin combined 2 module, 240 volts ISI marked complete all as specified and directed |
| 12 | S&F of Modular switch 1 module 6A,1 module , 240 volts ISI marked complete all as specified and directed |
| 13 | S&F of ceiling rose, 3 Pin/PVC/polycarbonate isolated body ISI marked complete all as specified and directed |
| 14 | S&F of Modular switch 1 way 16A, 1 module , 240 volts ISI marked complete all as specified and directed |
| 15 | S&F of Modular Socket 6A/16A - 6 pin combined 2 module, , 240 volts ISI marked complete all as specified and directed |
| 16 | S&F of LED lights fitting 1x 20W, 220V, AC decorative box type complete with LED tube rod 20 watts driver, holder and power factor >0.9, 100 Lumen/Watt, 6500 K cool day type conforming to ISI including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete. |
| 17 | Supply and fixing of LED luminaire 600 mm x 600 mm, 36 watt, WW, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete |
| 18 | M&L of distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 12 way 240 volts double door complete all as directed by Engr-in-Charge.Note:- Distribution board and MCBs should be same make. |
| 19 | Supply and fixing of MCB SPN 40 to 63 Amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning. |
| 20 | S&F of 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single pole and current carrying capacity 6 to 32 AMP Complete with connection testing and commissioning. |
| 21 | M&L of Earthing complete with galvanised mild steel earth plate electrode of size 600x600x6mm thick burried directly in ground earth (in vertical) earth pit not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr below ground level connected to galvanised iron or earth lead wire 4mm dia (8 SWG) by means of nut, bolt, check nuts and washer of galvanised ironl including PCC pit in PCC 1:2:4 type B-1 pre-cast RCC cover slab using reinfocement with suitable handle made of round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanised steel tube flor watering with one end fixed with cast iron funnel and wire mesh 15mm dia bore light grade galvanised steel tubing upto 5 m length for drawing earth lead wire protection, common salt, charcoal, etc complete all as shown in electrical plate No 3 of SSR Part-I and testing on completion. |
| 22 | Supply and fixing of LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. |
| 23 | Supply and fixing of Fan step regulator, 100W - 1 module 240 volts ISI marked complete all as specified and directed |
| 24 | Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 50 sqmm 3.5 core laid on wall or passing through existing/new pipe, clamping on wall etc. |
| 25 | Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 35 sqmm 3.5 core laid on wall or passing through existing/new pipe, clamping on wall etc. |
| 26 | S&F of Vertical Distribution Board (V.TP&N) 4 way double door suitable for 4 pole 125 Amp 16 KA four pole as incomer, it should be IP 43 protected with Copper BusBars, Neutral Links, Earthing bar all as specified and directed. |
| 27 | Supply and fixing of 415V 10KA 'B' curve miniature circuit breaker 4 pole, upto 125 Amps of following poles and current carrying capacity in the DB complete with connection testing and commissioning |
| 28 | S&F of power unit for AC with MCB 25 Amps incl protected socket 25 Amps, white modular gang box & plate 4 way complete with connection testing and commissioning. |
| 29 | Supply and fixing of ceiling fans complete with blades, down rods and accessories, 230V, 1200 mm sweep. Five star rated, suitable for fan regulator operating with brushless direct current motor (BLDC) complete |
| 30 | Supply and fix electronic meters temper proof LCD display with polycarbonate cover 415 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH incl necessary CT as suitable ratio complete all as specified and directed by Engineer-in-charge. |
| 31 | NOTES :-1. For the items for which specifications not mentioned any where in the tender, the BIS specifications shall be followed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 06, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 17 daysDec 04, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 24 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender