Tender For Construction Of Eklavya Model Residential School Pangi At Killar (Dharwas), Tehsil Pangi, District Chamba (Hp) [Sh: Provision Of Fan Fitting, Power Distribution And Lightening Arrestor In Studio Apartments (Transit Accommodation) Blocks]
Tender Overview
Project Description
Tender for Construction Of Eklavya Model Residential School Pangi At Killar (Dharwas), Tehsil Pangi, District Chamba (Hp) [Sh: Provision Of Fan Fitting, Power Distribution And Lightening Arrestor In Studio Apartments (Transit Accommodation) Blocks]
BOQ
| Sl. No. | Item Description |
| 1 | SUB HEAD-I (Fan & Fittings & Misc.) |
| 2 | Supplying, installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50Hz, Operating temp range -5°C to 40°C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 4000°K/5700°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≤120<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (Preferred make Philips/ Wipro/ Havells/ Crompton/ Bajaj/ Osram/ Surya or Similar Superior Make) |
| 3 | Powder coated CRCA Sheet Body (Thickness ≥0.50 mm) 40 Watt |
| 4 | Powder coated CRCA Sheet Body (Thickness ≥0.50 mm) 18-22 Watt |
| 5 | Supplying, Installation, Testing & Commissioning of LED Recessed/surface Down lighter (Round /Square/Rectangular) SMD type of following body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range - 5 0C to 40 0C, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 4000°K /5700°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≤120<135 lm/Watt output. LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body including trim . |
| 6 | Powder coated die cast /Extruded aluminium Body including trim with Aluminium Reflector 12-15Watt |
| 7 | SITC of following type prewired surface / recess mounted (minimum colour code 840) LED light fixture & integrated electronic driver (wherever required) suitable to operate on 240 volts 50 HZ AC supply including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required. (Preferred make Philips/ Wipro/ Havells/ Crompton/ Bajaj/ Osram/ Surya or Similar Superior Make) |
| 8 | LED retrofit type T Lamp/ Round Lamp /Radial lamp minimum 15Watt with accessories etc as required |
| 9 | 10 watt LED Bulkhead Luminaire with Opal diffuser, PDC Housing 2 KV inbuilt surge protection with IP 65 protection rating with accessories etc as required |
| 10 | 4 module polycarbonated UV stabilized LED Foot light 2.5/3 Watts with accessories etc as required |
| 11 | Supplying, Installation, Testing & Commissioning of 45Watt Street light LED fixture, powder coated pressure die cast aluminium body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, frequency 50/60 hz, Operating temp range -5 0C to 50 0C, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2, P. F.≥0.95, IP-66,IK-10, CRI >70, under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen ≤120<135 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted.. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). (Preferred make Philips/ Wipro/ Havells/ Crompton/ Bajaj/ Osram/ Surya or Similar Superior Make). |
| 12 | Supply, Installation, Testing and Commissioning of 1200mm sweep BEE 5 Star rated ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) ≥6.0, air delivery 210 CM/Min (minimum), 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75°C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. |
| 13 | SITC of 250 mm sweep Ventilating fan with plastic body and louvers i/c connection with 2x1.5 sqmm cu. Conductor FR PVC cable etc as required at site. (M/s HAVELLS / Crompton Greaves/Usha/ Khaitan/Bajaj/Orient) |
| 14 | SITC of 150 mm sweep round Ventilating fan with plastic body and louvers i/c connection with 2x1.5 sqmm cu. Conductor FR PVC cable etc as required at site. (M/s HAVELLS / Crompton Greaves/Usha/ Khaitan/Bajaj/Orient) |
| 15 | SITC of 300 mm sweep fresh air fan With metalic body and net i/c connection with 2x1.5 sqmm cu. Conductor FR PVC cable etc as reqd at site. (M/s Havel, Usha, Bajaj, Khaitan or similar superior make). |
| 16 | Supplying and fixing musical/Ding Dong call bell suitable for D.C./A.C. single phase, 230 volts, complete as required. |
| 17 | Supplying and fixing Batten/Angle holder i/c 10W LED Ball Lamp, connections, testing etc. complete as required. |
| 18 | Supplying ,Installation, testing and commissioning of following type rating and size Geyser (Electric Storage Water Heater), suitable for single phase AC supply , including supplying of two no flexible connection pipes for water connection and suitable size PVC insulated, copper conductor, three core flexible wire for power supply connection etc. as required. |
| 19 | 1Liter 3KW rating Instantaneous water heater with ultra thick SS tank and ABS shock proof body ( Make Havells/Bajaj/Crompton or similar superior make) |
| 20 | 25 Ltr Capacity Energy efficient Storage water Heater with thermostat control and preset thermal cutout , Steel tank and having 5 star rating ( Make Havells/Bajaj/Crompton or similar superior make) |
| 21 | Supplying and fixing of G.I bracket for mounting of LED street light fitting on wall fabricated out of 40mm dia G.I pipe (medium class) of 1 Meter length having suitable machine made curve with suitable size of reducers, 40mmx3mm flat iron clamp and shall be painted with two coats of red oxide and two coats of aluminium paint including numbering complete as required. |
| 22 | Supplying and fixing Adaptor Box(s) fabricated out of 16 SWG M.S. sheet complete with cutting, welding, painting, sign writing etc. all as required. |
| 23 | Supplying and laying 1 Meter X 2 Meters, 6 mm. Thick -chequered Rubber Matting as required. (ISI marked) |
| 24 | Supplying & fixing One No. First aid box of Standard type containing the following:- a) Instruction book (first aid to injured). b) 3 wound dressing large (for other injury) c) 3 wound dressing medium (for injured hands and feet) d) 1 absorbent cotton wool 200 gms. e) Antiseptic solution f) Bandages. g) 1 tube of burn ointment. h) 1 dressing scissors. i) 10 tablets of asprin. |
| 25 | SH:- II- Distribution System & Cabling |
| 26 | Supplying and fixing M.S. cubicle of depth 225 mm fabricated out of combination of 16 SWG M.S. sheet & 25mmx25mmx3mm angle iron complete with cutting, welding, painting, sign writing etc. having arrangement for housing HPSEB energy meter, SFU, MCB /RCCBs etc. & 6mm thick backlite sheet on back side complete as required. (Note : Measurement shall be done as per front surface area of panel) |
| 27 | SITC of 200 A Three Phase Neutral (TPN) 4 Ways Busbar Chamber Box having size not less than 15\\"x15\\"x15\\" made out of 1.2 Mm Thick (16 G) i/c Fixing , interconnections etc Complete as reqd. (Havells Model IHBC020004) |
| 28 | Supplying and fixing Four Pole 250A MCCB with variable Thermo-Magnetic Realese (Release range 160-200A) breaking capacity 36KA, (Ics = 100% Icu) at suitable for operation on 415 volts, 3 phase, 4 wire, 50HZ A.C. including spreaders for installation in the existing M.S. sheet steel , Medium Voltage, Cubicle Panel including drilling the holes in cubicle panel, making interconnections , etc. as required. (M/s L&T D-sine model DN2-250D or equivalent similar superior make) |
| 29 | Supplying and fixing of following sizes of medium class PVC pipe along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 30 | 50 mm |
| 31 | 75 mm |
| 32 | Supplying & Laying XLPE Aluminium conductor armoured cable of 1.1 KV grade of following sizes on surface/ existing cable tray/pipe etc. as required. |
| 33 | 2 x 6 Sq.mm. |
| 34 | 2 x 16 Sq.mm. |
| 35 | 4x16 Sq.mm. |
| 36 | 3½ x35 Sq.mm. |
| 37 | 3½ x50 Sq.mm. |
| 38 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 39 | 2 x 6 Sq.mm.(19mm) |
| 40 | 2 x 16 Sq.mm.(22mm) |
| 41 | 3½ x 35 Sq.mm.(32mm) |
| 42 | 3½ x 50 Sq.mm.(32mm) |
| 43 | SUB HEAD-III (Earthing and Lightning Conductor) |
| 44 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
| 45 | Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) |
| 46 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 47 | Providing and fixing 25mmx5mm GI strip on surface or in recess for connections etc as required |
| 48 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. |
| 49 | Providing and fixing of lightning conductor finial, made of 25 mm dia 300mm long, G.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate including holes etc. complete as required. |
| 50 | Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/sweating and soldering etc as required. |
| 51 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run) |
| 52 | Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run) |
| 53 | Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required. |
| 54 | Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender