Tender For special Repair For Replacement Of Damage Lt Feeder Pillar Boxes, Lt Xlpe Cable And All Connected Accessories And Provn Of 03 High Mast Light In Hosp Area (Maty Ward, Csd Canteen And Gurudwara) At 167 Mh Under Ge South Pathankot
Tender Overview
Project Description
Tender for special Repair For Replacement Of Damage Lt Feeder Pillar Boxes, Lt Xlpe Cable And All Connected Accessories And Provn Of 03 High Mast Light In Hosp Area (Maty Ward, Csd Canteen And Gurudwara) At 167 Mh Under Ge South Pathankot
BOQ
| Sl. No. | Item Description |
| 1 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1,5 mtrs in depth for laying of cables including getting out in hard and dense of soil complete all as specified and directed. |
| 2 | Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge. |
| 3 | Returning, filling in, including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required complete all as specified and directed by Engineer-in-Charge. |
| 4 | M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified and directed. Note: Punned thickness of sand shall be measured. |
| 5 | Supply and laying sub class 'B' bricks of (230x115x75 mm) or of size locally available , laid along alignment of cable as protection to cable in trenches complete all as specified and directed by Engineer-in-Charge |
| 6 | Supply, laying, jointing and testing LT cable 1100 volts grade of cross sectional area 120 Sqmm x 3.5 Core as per IS-7098 (Part-I), XLPE insulated armoured aluminium conductors heavy duty served with an inner sheathing of PVC tape, galvanized steel strip or wire armoured with an overall PVC sheathing laid in trenches with suitable size of lugs etc each cable termination is to be made with suitable size of aluminium thimbles for junction boxes & LT panels etc) for incoming and outgoing cables complete all as specified and directed by Engr In charge. |
| 7 | All as per item No. 6 here-in-before but of size 150 Sqmm 3.5 core |
| 8 | All as per item No. 6 here-in-before but of size 400 Sqmm 3.5 core |
| 9 | Material, labour jointing, testing & commissioning of LT indoor/outdoor End jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 120 sqmm x 3.5 core with working voltage 1100 volts, complete all as specified and directed. |
| 10 | Material, labour jointing, testing & commissioning of LT indoor/outdoor End jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 150 Sqmm 3.5 core with working voltage 1100 volts, complete all as specified and directed. |
| 11 | Material, labour jointing, testing & commissioning of LT indoor/outdoor End jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 400 Sqmm core with working voltage 1100 volts, complete all as specified and directed. |
| 12 | Dismantling and taking out old UNSV LT cable of any size, any make and any type from trenches with brick protection complete all as specified and directed by Engr - in - Charge. |
| 13 | Dismantling and taking out old UNSV LT Bus Bar chamber along with all accessories, of any size, make and type from site, complete all as specified and directed by Engr - in - Charge. |
| 14 | Dismantling and taking out bold UNSV of LT indoor/outdoor End jointing kit, heat shrinkable type suitable for XLPE/ PVC cables of size 16 to 400 Sqmm 3.5 core with working voltage 1100 volts, complete all as specified and directed. |
| 15 | Dismantling and taking out old UNSV LT Feeder Pillar Box (LT Panel) along with all accessories, of any size, make and type from site, complete all as specified and directed by Engr - in - Charge. |
| 16 | Dismantling and taking out old UNSV GI Pipe 50/80 mm dia with all accessories, of any capacity, size, make and type from site complete all as specified and directed by Engr - in - Charge. |
| 17 | M & L for cutting of existing hard standing / Road not exceeding 0.30 mtrs wide and 45 cm deep by using necessary tools and plants , returning filling in of excavated material upto required depth and making good the same to match with the existing level, using PCC 1:3::6 of minimum 200 mm thick, the same should be compact and protected untill dried up, If the PCC done by the contractor is settled down due to the impact of the vehicle movement the same will be redone by the Contractor without any extra cost. The balance excavated material will be deposited within 100 mtrs and all as specified and directed by Engr - in - charge. |
| 18 | Supply and laying of GI pipe Med grade 80 mm bore complete for cable protection under road culvert or PCC floor complete all as specified and directed by Engr - in - Charge. |
| 19 | M&L for PCC 1:2:4 type B-1 with 20 mm graded aggregate for coping of poles etc, including form work complete all as specified and directed. |
| 20 | Supply, Installation, Testing and Commissioning of 20 mtrs High Mast Lighting system comprising of continuously tapered polygonal high mast pole manufactured from high Tensile Steel confirming to IS : 2062 (IEC). The High mast should be designed to withstand the specified wind load upto 180 KM/h as per IS : 875 Part-3, bottom dia of high mast pole should be not less than 380 mm and top dia should be not less than 160 mm and thickness of bottom pole section should not less than 3 mm and thickness of top pole section should not less than 2 mm , size of base plate should not less than 30 mm thick, size of base plate of high mast pole should be not less than 540x460x30 mm ( Meet as per IS Standard), and shall be hot - dip galvanised in accordance with IS : 4759. The High mast shall be complete with a head frame (Latern Carriage) suitable for mounting 12 Nos LED Flood light of 250 watt or any other capacity, a rising and lowering mechanism consisting of a stainless Steel wire rope of size not less than 6 mm dia 97/19 gauge, double drum winch , Pulley system , gera box and automatic locating arrangement for safe maintenance of high mast . The system shall Include all necessary accessories such as foundation , anchor nuts and bolts ,base plate , cable termination arrangement , aviation obstruction light , weather proof junction box , internal FRLS copper wiring , Earthing terminals , and all hardware items required for complete Installation of High Mast light. The complete system shall be included 20 mtrs hot - deep galvanized polygonal High Mast with base plate and foundation nuts and bolts , lantern carriage suitable for mounting 12 nos LED Flood Lights . RCC foundation of suitable size and grade based on soil bearing capacity including excavation , PCC , reinforcement , anchor nuts and bolts fixing , concerting , backfilling and disposal of surplus earth soil and erection of High mast using suitable equipment , alignment , testing , commissioning. and system is suitable for power supply of Voltage 415 Volts , Plus and minus 10%, Three (3) Phase , 4 wire , 50 Hz . power supply. Note :- Detail of complete foundation drawing will be submitted by contractor as per manufacturer/OEM (As per IS Standard), complete all as specified and directed by Engr - in - Charge. |
| 21 | Supply and fixing LED flood light out door type high along with adjustable heavy duty GI/SS mounting bracket and weather proof cable gland, efficiency rated watt 250 ±10% and rated power 230 Volts AC , 50 Hz single phase and input voltage range 160- 285 Volts AC , 50 Hz, having power factor 0.95 and driver efficiency not less than 90% and high power SMDs LED and luminous flux range between 30000- 32000 lumens or higher, outdoor type with thermal management in multiple optics toughened/tempered glass or suitable uv resistant optical cover and equipped with IP66 protection, short - circuit, over voltage, over current and thermal protection with impact die-cast aluminium and corrosion resistant and relevant IS/IEC standards minimum 10 KV Surge protection complete with driver and lamp and suitable for mounting on high mast poles and complete all as directed by the Engr-in-Charge |
| 22 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as directed by the Engr-in-Charge. |
| 23 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sqmm 4 core complete all as directed by the Engr-in-Charge. |
| 24 | Supply, installation, testing and commissioning of LT Bus bar panel of size not less than (600Lx450Bx750H) mm, outdoor type with suitable size of canopy, suitable for 3 phase, 4 wire 415 Volt 50 Hz electric power supply and both side opening ( Front and Back) single door type of both side front and back with stainless steel butt hinges minimum 02 nos for each door of size not less than 4 inchs and thickness not less than 2.0 mm, fixed with suitable size of screws/welding works and 01 no steelness steel aldrop of size not less 150 mm with complete accessories for each door for locking arrangement of bus bar/LT panel , bus bar shall be made out 3.0 mm thick CRCA sheet with angle iron base frame of size not less than 65 x 65 x 5 mm cubical type and frame height is not less than 60 cm complete with 4 Nos Aluminium bus bar 200 Amp, MCCB 4 Pole , 100 Amp, 415 V, 25 KA (Thermal magnetic release) Ics=100%Icu and adjustable overload setting 80% to100%- 01 No (As incommer) and 04 Nos suitable size hole in each bus bar for outgoing cables, RYB LED indicator- one set with IP 55 as per IS 13947 protection, internal wiring by FRLS grade multi stranded PVC insulated copper conductor of suitable size duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection along with suitable size of lugs/thimbles and glands complete all as directed by the Engineer –in - charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC of thickness not less than 150 mm thick for grouting of panels and mounted on PCC platform made out of PCC 1:3:6, 150 mm thick, 0.5 Mtr all round the bus bar/ LT Panel board and all as specified and directed. |
| 25 | Supply, installation, testing and commissioning of LT Bus Bar Panel of size not less than (750x600x450) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening door (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 400 Amp (The size of Bus bar copper Strip should not less than 50 mm x5 mm) and MCCB Microprocessor LSIG , 4 Pole , 250 Amp, 415 V, 16 KA with Integrated energy metering with accuracy class 2 adjustable thermal & adjustable magnetic release (Measure for currents, voltage, frequency, power, energy and harmonics), Ics = Icu=100% , 415 volts, 50 Hz with phase barrier/phase separator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete -01 No ( As incommer) |
| 26 | TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs complete all as specified and directed by Engr - in - Charge. |
| 27 | Supply, installation, testing and commissioning of LT Bus Bar Panel of size not less than (750x600x450) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening door (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 250 Amp (The size of Bus bar copper Strip should not less than 20 mm x5 mm) and MCCB Microprocessor LSIG , 4 Pole , 200 Amp, 415 V, 16 KA with Integrated energy metering with accuracy class 2 adjustable thermal & adjustable magnetic release (Measure for currents, voltage, frequency, power, energy and harmonics), Ics = Icu=100% , 415 volts, 50 Hz with phase barrier/phase separator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete -01 No ( As incommer) |
| 28 | The TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs complete all as specified and directed by Engr - in - Charge. |
| 29 | Supply, installation, testing and commissioning of LT Bus Bar Panel of size not less than (750x600x450) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening door (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 160 Amp (The size of Bus bar copper Strip should not less than 25 mm x5 mm) and MCCB Microprocessor LSIG , 4 Pole , 100 Amp, 415 V, 16 KA with Integrated energy metering with accuracy class 2 adjustable thermal & adjustable magnetic release (Measure for currents, voltage, frequency, power, energy and harmonics), Ics = Icu=100% , 415 volts, 50 Hz with phase barrier/phase separator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete -01 No ( As incommer) |
| 30 | TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs complete all as specified and directed by Engr - in - Charge. |
| 31 | Supply, installation, testing and commissioning of LT feeder pillar box factory made of size not less than (1000x1500x500) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening double doors (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 1000 Amp (The size of Bus bar copper Strip should not less than 80 mm x10 mm) TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. |
| 32 | Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs/glands etc complete all as specified and directed by Engr - in - Charge.BUSBAR :- 1000 Amps rated TPN Copper bus bar with 4 Nos Copper strips (The size of Bus bar copper Strips should not less than 80 mm x10 mm each ) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports/insulators made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level.INCOMING:- (i) 4 pole MCCB of capacity 630 Amps, 50 KA , 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 No (ii) Digital type Panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio (CT ratio should be equal to the rated current carrying capacity of incomer MCCB) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 430/230 volts AC at the incomer of the unit to show three phase power supply availability(iii) CT ratio as per panel design suitable for 3 phase 4 wire LT supply system OUTGOING:- (i) 4 pole MCCB of capacity 400 Amps, 36 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos (ii) 4 pole MCCB of capacity 250 Amps, 36 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos |
| 33 | (iii) 4 pole MCCB of capacity 100 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos |
| 34 | Supply, installation, testing and commissioning of LT Bus Bar Panel of size not less than (900x750x450) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening door (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, and outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 1000 Amp (The size of Bus bar copper Strip should not less than 80 mm x10 mm) and MCCB Microprocessor LSIG , 4 Pole , 630 Amp, 415 V, 50 KA with Integrated energy metering with accuracy class 2 adjustable thermal & adjustable magnetic release (Measure for currents, voltage, frequency, power, energy and harmonics), Ics = Icu=100% , 415 volts, 50 Hz with phase barrier/phase separator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete -01 No ( As incommer) |
| 35 | The TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 04 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs complete all as specified and directed by Engr - in - Charge. |
| 36 | Supply, installation, testing and commissioning of LT Bus Bar Panel of size not less than (900x750x450) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening door (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 630 Amp (The size of Bus bar copper Strip should not less than 50 mm x10 mm) and MCCB Microprocessor LSIG , 4 Pole , 400 Amp, 415 V, 36 KA with Integrated energy metering with accuracy class 2 adjustable thermal & adjustable magnetic release (Measure for currents, voltage, frequency, power, energy and harmonics), Ics = Icu=100% , 415 volts, 50 Hz with phase barrier/phase separator/spacer with copper spreader links and required nut, bolts or other fixing accessories complete -01 No ( As incommer) |
| 37 | The TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 05 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs complete all as specified and directed by Engr - in - Charge. |
| 38 | Supply, installation, testing and commissioning of LT feeder pillar box factory made of size not less than (1000x2000x500) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening double doors (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 630 Amp (The size of Bus bar copper Strip should not less than 50 mm x10 mm) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge.Note : (i) The panel shall be as per CPRI certificate. |
| 39 | (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs/glands etc complete all as specified and directed by Engr - in - Charge.BUSBAR :- 630 Amps rated TPN Copper bus bar with 4 Nos Copper strips (The size of Bus bar copper Strips should not less than 50 mm x10 mm each ) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports/insulators made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault levelINCOMING:- (i) 4 pole MCCB of capacity 400 Amps, 36 KA , 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 No (ii) Digital type Panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 430/230 volts AC at the incomer of the unit to show three phase power supply availability(iii) CT ratio as per panel design suitable for 3 phase 4 wire LT supply system OUTGOING:- (i) 4 pole MCCB of capacity 250 Amps, 36 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos (ii) 4 pole MCCB of capacity 160 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos(iii) 4 pole MCCB of capacity 100 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos |
| 40 | Supply, installation, testing and commissioning of LT feeder pillar box factory made of size not less than (1000x2000x500) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening double doors (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 1000 Amp (The size of Bus bar copper Strip should not less than 80 mm x10 mm) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. |
| 41 | (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs/glands etc complete all as specified and directed by Engr - in - Charge.BUSBAR :- 1000 Amps rated TPN Copper bus bar with 4 Nos Copper strips (The size of Bus bar copper Strips should not less than 80 mm x10 mm each ) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports/insulators made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault levelINCOMING:- (i) 4 pole MCCB of capacity 630 Amps, 50 KA , 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 No (ii) Digital type Panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 430/230 volts AC at the incomer of the unit to show three phase power supply availability(iii) CT ratio as per panel design suitable for 3 phase 4 wire LT supply system OUTGOING:- (i) 4 pole MCCB of capacity 250 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos (ii) 4 pole MCCB of capacity 125 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos(iii) 4 pole MCCB of capacity 100 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos |
| 42 | Supply, installation, testing and commissioning of LT feeder pillar box factory made of size not less than (1000x2100x500) mm, outdoor type Canopy type( The length of outside extended portion of Canopy shall not be less than 150 mm all around the LT Bus bar/LT panel ), suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and both side opening double doors (front and Back) double door type with 01 No Steel aldroop locking arrangement with all connected accessories of size not less than 6 inch on middle section of the both front and back doors and push type metal lock, heavy duty wide hinges, outer portion of panel made out 3.15 mm thick CRCA sheet and inner portion of panel made out 2.0 mm thick CRCA sheet and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 1000 Amp (The size of Bus bar copper Strip should not less than 80 mm x10 mm) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. |
| 43 | (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs/glands etc complete all as specified and directed by Engr - in - Charge.BUSBAR :- 1000 Amps rated TPN Copper bus bar with 4 Nos Copper strips (The size of Bus bar copper Strips should not less than 80 mm x10 mm each ) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports/insulators made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault levelINCOMING:- (i) 4 pole MCCB of capacity 630 Amps, 50 KA , 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 No (ii) Digital type Panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 430/230 volts AC at the incomer of the unit to show three phase power supply availability(iii) CT ratio as per panel design suitable for 3 phase 4 wire LT supply system OUTGOING:- (i) 4 pole MCCB of capacity 250 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 04 Nos (ii) 4 pole MCCB of capacity 200 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos(iii) 4 pole MCCB of capacity 100 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos |
| 44 | Supply, installation, testing and commissioning of LT feeder pillar box factory made of size not less than (1000x2100x500) mm, Indoor type and seperate cubical type compartments for each incoming and outgoing MCCBs , suitable for 3 phase , 4 wire 415 Volt , 50 Hz power supply system and push type metal locking arrangement for each MCCB compartments , heavy duty wide hinges, outer and inner portion of panel made out 2.0 mm thick CRCA sheet on a MS Angle structure, the size of MS angle structure should not less than (40x40x5) and the qty of total nos of vertical MS angle supports should not less than 06 nos and a total nos of horizontal MS angle supports should not less than 04 nos through out the panel with the help of suitable welding works and mounted on 600 mm long angle iron frame of size not less then 75 x 75 x 6 mm cubical type complete with 4 Nos Copper TPN bus bar of rating 1000 Amp (The size of Bus bar copper Strip should not less than 80 mm x10 mm) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault level & Digital panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio ( CT ratio should be equal to the rated current carrying capacity of incomer MCCB ) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 230 volts AC at the incomer of the unit to show three phase power supply availability and Bus Bars having suitable holes for minimum 06 nos outgoing cables connections , internal wiring by FRLS grade multi stranded PVC insulated copper conductor of size not less than 2.5 Sq.mm duly marked with ferrule, incl powder coated painting in inner & outer side, including making all suitable necessary electrical connection and canopy at top of the panel for protection of panel from rain complete all as directed by the Engineer -in - Charge. Note : (i) The panel shall be as per CPRI certificate. |
| 45 | (ii) The rates deemed to be inclusive necessary PCC 1:2:4 (20mm Graded Stone Aggregate) for grouting of panels on a leveled surface and 60 cm radius of all around panel and thickness of PCC is not less then 10 cm and the rates are also inclusive for connection of all existing/new cables with the help of suitable size lugs/glands etc complete all as specified and directed by Engr - in - Charge.BUSBAR :- 1000 Amps rated TPN Copper bus bar with 4 Nos Copper strips (The size of Bus bar copper Strips should not less than 80 mm x10 mm each ) the TPN bus bar shall be insulated with colour coded heat shrinkable/PVC Sleeving as required track resistant and bus bar supports/insulators made out of high strength FRP/SMC/DMC/epoxy material , suitable for fault levelINCOMING:- (i) 4 pole MCCB of capacity 630 Amps, 50 KA , 415 Volts, 50 Hz, 3 phase breaking capacity 36 KA with thermal magnetic trip/release type with overload adjustability - 01 No (ii) Digital type Panel multi function meter to measure current , voltage , frequency and power factor having programmable CT ratio (CT ratio should be equal to the rated current carrying capacity of incomer MCCB) & built in selector switch with IP-54 as per IS-13947 protection of size not less than 96mm x 96mm , accuracy class 1.0 suitable to work on ausitiary power supply of 430/230 Volts AC with back up protection by 6/10 amp MCB SP and indicating lamps 22.5 mm dia LED type, 430/230 volts AC at the incomer of the unit to show three phase power supply availability(iii) CT ratio as per panel design suitable for 3 phase 4 wire LT supply system OUTGOING:- (i) 4 pole MCCB of capacity 400 Amps, 50 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 50 KA with thermal magnetic trip/release type with overload adjustability - 01 Nos (ii) 4 pole MCCB of capacity 250 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02 Nos |
| 46 | (iii) 4 pole MCCB of capacity 200 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02Nos(iv) 4 pole MCCB of capacity 160 Amps, 16 KA , 415 Volts, 50 Hz, 3 phase, breaking capacity 16 KA with thermal magnetic trip/release type with overload adjustability - 02Nos |
| 47 | M&L for fixing in replacement Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required with galvanised iron strip 25x4 mm including dismantling old one, complete all as specified and directed. |
| 48 | M&L for Earthing complete with galvanized cast iron earth plate electrode of size 600x600x6 mm thick as earth electrode with top edge of the earth plate not less than 1.5mtr below ground level using galvanized iron strip 25x4mm earthing lead as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade 40mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil remain surplus excavated material all as required at site and specified in EP No 3 of SSR complete all as specified and directed by Engineer-in-charge incl testing on completion. |
| 49 | Note: (i) In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.(ii) The Schedule of Credit amount shall be deducted from the total of this schedule (BoQ) to arrive at Contract Sum. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 19 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 21 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender