Tender For Addition/Alteration Of Opg X Ray Room At Mdc Panaji
Tender Value
4.23 Lakhs
Estimated cost
Bid Submission
26 Nov 2026
11 days left
EMD
8500
Bank guarantee accepted
Document Fee
300
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
panaji → Goa
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Addition/Alteration Of Opg X Ray Room At Mdc Panaji
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 10-Nov-2026 | 8351 BOQ Corrigendum | BOQ | 26-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Demolition of brickwork or stone/boulder masonry, built in CM including all quoins arches pillars etc. |
| 2 | Brickwork with subclass ‘B’ bricks, straight or curved on plan to any radius in half brick thick walls built in CM 1:4 |
| 3 | M&L for cement concrete 25mm thick, type B-1, 1:2:4 (using 20 mm graded aggregate) for padding complete all as specified and directed. |
| 4 | M&L for 10mm thick plastering in CM 1:4 on fair faces of bricks or concrete surfaces (internal surfaces) finished even and smooth w/o using extra cement |
| 5 | M&L for Preparation of new surface of wall and applying two coat of oil emulsion distemper over 3mm thick wall care putty over a coat of primer on internal walls surfaces complete all as specified and directed. |
| 6 | M&L for complete removal of existing treatment on wall and applying two coats of oil bond distemper over & including one coat of primer over 3mm thick wall care putty complete all as specified and directed. |
| 7 | Taking down chowkat with shutter(without taking off shutter from the frame) area exc 1.5 sqm but n exc 4 sqm each |
| 8 | Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises |
| 9 | M&L Glazed ceramic tiles in vertical surface 300x200x 7 mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match over backing coat with cement mortar 1:4, 10mm thick on fair faces of brick work or concrete surfaces complete all as specified and directed. |
| 10 | M&L Non - skid Ceramic tiles (coloured) 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11sqm but not exceeding 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match etc including 15mm thick screed bed in CM 1:6. complete all as specified and directed. |
| 11 | S & F 2nd Class H.W. plain solid straight chowkats & frames wrought, framed, rebated on the solid rounded or chamfered put together with glue, pinned at joints. |
| 12 | S&F HPL Lead Hinge Door CIVIL SIZE 1350X2050MM (Approx) 44MM thickness of Door shutter, 4mm Thickness of HPL sheet on both side 2 mm Thickness of Lead Sheet, SS Ball bearing hinges, \\"D \\" Handles, infill material Puff, Both side Key operation dead lock, 325x325mm. (Lumsum charges for trasportation and installation plus 15000 for item No 12 to 14) No vision Glass all as specified and directed |
| 13 | Supply and fixing of HPL finished radiation-shielded lead glass window of overall size 1200 mm × 1450 mm (approximately) and 10mm nominal thickness of glass, comprising clear transparent radiation-protective lead glass of minimum lead equivalence as per approved radiation shielding design, fixed in suitably designed heavy-duty MS/aluminium frame with HPL finish, including lead lining of frame and rebates wherever required to ensure continuity of radiation shielding, suitable glazing beads, rubber/neoprene gaskets, sealants, screws, fasteners, supports, cutting, drilling, making good and finishing complete, ensuring proper alignment, rigidity and radiation protection, all as per manufacturer's specifications, and directions of the Engineer-in-Charge |
| 14 | Supply and fixing of clear transparent radiation-protective lead glass of size 300 mm × 300 mm and 10 mm nominal thickness, having certified lead equivalence as per approved radiation shielding design, suitable for use in diagnostic X-ray room, including machine-ground and polished edges, fixing in suitable MS/aluminium frame with lead-lined rebates wherever required, glazing beads, rubber/neoprene gaskets, compatible sealants, screws, fasteners and all necessary accessories, ensuring proper fixing, optical clarity and continuity of radiation shielding at all joints, complete as per manufacturer's specifications, and directions of the Engineer-in-Charge. |
| 15 | Supply and fixed Door closer hydraulically regulated,designation No, 3,universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between 61 to 80 kg and fixed (aluminium) complete all as specified and directed. |
| 16 | Supply, install, testing and commissioning of Hi wall split inverter type AC of capacity 1.5 TR 5 star rated with copper condenser coil. ISEER should be greater than or equal to 4.51 with referigerent R-32 and compresser type dual /twin rotary complete including Connection Copper Pipe as per Site requiement upto 08 meter & with all necessary accessories complete all as specified |
| 17 | Supply and fix Voltage stabilizer for automatic operation, single phase intelligent time delay system, high and low voltage cut of having ABC body and voltage range 90V-300 V-15 Amps, suitable for 1.5 ton AC from inverter motor AC complete all as specified |
| 18 | M&L Sub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 6.00 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 6.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of PVC conduit drawn through rigid concealed PVC conduit ISI Marked, heavy duty and connected to main board and making good disturbed surface complete all as specified and as directed. Make of conductor : Havells/polycab/KEI. Note: Two runs each of 6.00 sqmm cable and one RM of 6.00sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose. |
| 19 | M&L for point wiring complete with PVC insulated and unsheathed cable 4.0 sqmm (nominal area) ISI marked multi-stranded copper conductor single core including ISI marked 20mm dia medium grade PVC conduit for point wiring in Surface concealed PVC Conduit with pressed steel concealed Sunken boxes not less than 1.6mm thick of reqd size (factory painted) and with top cover 3 mm thick of Hylam sheets of required colour, painting Sunken boxes inside and out side with one coat of red oxide primer complete including 4.0 sqmm PVC insulated and unsheathed ISI marked copper cable to common earth connected to earth dolly colour coding of cable as per IE Rule complete surface making good all as specified & directed. (Make of cable - Finolex / Havells/ Anchor/KEI/ Polycab ) |
| 20 | Supply & fixing of, including connection modular Switch socket combination 2 in 1, 6 pin 16 amps 3 modules complete suitable size modular plate all as specified and directed. |
| 21 | M&L of MCB distribution board having IP-54 protection, powder coated, double door, flush mounted complete with lock & arrangement suitable for 8 way SPN with 200 Amp rated bus bar 203 volt AC supply including complete all as specified. |
| 22 | M&L MCB SPN 40 Amps, 240 Volts, having breaking capacity 10 kA, 'C' characteristic complete all as specified and as directed. |
| 23 | M&L MCB SP 6-32 Amps, 240 Volts, having breaking capacity 10 kA, 'C' characteristic complete all as specified and as directed. |
| 24 | Supply and fixing of Heavy duty AC Static/AC Outdoor unit mounting bracket AC Wall stand /Bracket for Microwave Open OTG Printer speaker (Cap Up to 160Kgs) complete all as specified and as directed. |
| 25 | M&L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25 metre deep below normal ground level with top edge of the plate not less than 1.5 metre below normal ground level surrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt, filling in alternate layer and electrode connections by using galvanized iron earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers made of galvanized iron or steel and protected by light grade 15 mm dia GI pipe connected to main switch board or main control board, and GI pipe light grade 20 mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1: 2: 4 type C2 including excavation and earth work, disposal of surplus soil to a distance not exc. 50 mtr all as specified and as shown on Plate No 5 of SSR Part I (1991) all as specified and as directed by Engr-in-Charge. |
| 26 | M&L Sheet metal enclosures for single pole and neutral enclosure with a two pin and earth plug and socket complete with single pole mcb 20 Amp 240 Volt complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 10, 2026
11:30 IST
Tender Published
Tender notice published.
Completed
Nov 26, 2026
18:00 IST
Corrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 11 daysNov 26, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender