Tender For Establishment Of 132/33 Kv, 2X10 Mva Sub-Station At Wakro With Associated 132 Kv Lilo Line.
Tender Value
64.08 Crore
Estimated cost
Bid Submission
27 Nov 2026
11 days left
EMD
1.28 Crore
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Lohit → Arunachal Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Establishment Of 132/33 Kv, 2X10 Mva Sub-Station At Wakro With Associated 132 Kv Lilo Line.
BOQ
| Sl. No. | Item Description |
| 1 | SUPPLY SERVICES :- |
| 2 | SH-I: 132 KV LILO DOUBLE CIRCUIT TRANSMISSION LINE:- |
| 3 | Tower foundation Works: |
| 4 | Concreting: |
| 5 | Steel rods of all sizes for RCC works as per design. |
| 6 | Galvanized Iron Structure: |
| 7 | Galvanized Towers, steel members for structure, including Tower template. |
| 8 | Galvanizing stubs, template Nuts & Bolts of various types of Towers. |
| 9 | Earthing System: |
| 10 | Tower earthing with GI Pipe & strips as per specification. |
| 11 | Safety Alert System: |
| 12 | Danger plates of size 250 mm x 200 mm of thickness 3 mm. |
| 13 | Number plates of size 250 mm x 200 mm of thickness 3 mm. |
| 14 | Phase plates (set of three pieces). |
| 15 | Anti climbing devices with G.I. Thornwire/ Barbed wires. |
| 16 | ACSR Conductor as per ISS: |
| 17 | ACSR Panther (30/7/3.00 sqmm) |
| 18 | Composite Polymer Insulator (Tension): |
| 19 | 132 kV, 120 kN |
| 20 | Hardware fittings and accessories: |
| 21 | Single tension 120 kN hardware fittings with all accessories as per IS for Panther. |
| 22 | Double tension 120 kN hardware fittings with all accessories as per IS for Panther. |
| 23 | Midspan compression joints for panther. |
| 24 | Repair Sleeve for ACSR Panther conductor. |
| 25 | Vibration Damper for ACSR Panther conductor. |
| 26 | OPGW Cable and accessories: |
| 27 | 24 Fiber (DWSM) Optical Fiber Ground Wire (OPGW). |
| 28 | Hardware set for 24 fibre OPGW cable i/c all fittings & accessories. |
| 29 | Joint box (24 Fibre) for OPGW. |
| 30 | SH-II: 132/33 KV, 2X10 MVA SUB-STATION :- |
| 31 | Galvanised Structure: |
| 32 | Design, fabrication and supply of hot-dipped GI lattice type tower made with angle iron for 132kV and 33 kV gantry towers and switchyard equipments support structures. |
| 33 | Design, fabrication and supply of galvanizing stubs, template Nuts & Bolts, spring washers etc. as reqd. |
| 34 | 132 kV Switchyard Equipments: |
| 35 | 3Ф, 10 MVA, 132/33 kV Transformer. |
| 36 | EHT transformer oil as per ISI specification amended up to date. |
| 37 | Nitogen Injection Fire Protection System (NIFPS) |
| 38 | Online insulating oil drying system (Catridge type). |
| 39 | 145 kV, SF6, 3- Phase, Circuit Breaker, with support structure. |
| 40 | 145 kV, 600 A, 31.5 kA, 1- Phase, 3- Core current transformer with 120% extended current rating complete in all respects, along with associated accessories and a common MB. (Set of 3 Nos.) |
| 41 | 145 kV, 1250 A, 31.5 kA, 3- Phase Horizontal Centre Break Isolator with earth switch. |
| 42 | 145 kV, 1250 A, 31.5 kA, 3- phase Horizontal Centre Break Isolator without earth switch. |
| 43 | 145 kV, 1250 A, 31.5 kA, 3- phase Horizontal Centre Break Isolator without earth switch (Tandem) |
| 44 | 120 kV, 1-Phase, gapless Surge Arrester, rating (kV rms) - 120, complete in all respects with insulating base and surge monitor |
| 45 | 132 kV, 1-Phase, Capacitive Voltage Transformer with accessories complete in all respect. (Set of 3 Nos.) |
| 46 | 132 kV Control, Relay and Protection Panels: |
| 47 | Control & Relay panel for line Bay with primary & backup protective relays, LBB relay and other auxiliary relays as required with SAS and all associated accessories. |
| 48 | Control & Relay panel for Transformer Bay with differential, overfluxing, LBB and backup protective relays and other auxiliary relays as required with SAS and all associated accessories. |
| 49 | Control & Relay panel for bus coupler bay with primary & backup protective relays, LBB relay and other auxiliary relays as required with SAS and all associated accessories. |
| 50 | Sub-Station Automation: |
| 51 | Substation Automation System (SAS) confirning IS 61850 with BCU and other complete associated equipment and accessories. |
| 52 | Remote Terminal Unit and SCADA Gateway with all required ancilliary equipment/materials. |
| 53 | 33 kV Equipment: |
| 54 | 33 kV Gas Insulated Switchgear, 1250 A, 31.5 kA for 3 Sec, 50 Hz, as per technical specification. [Incomer- 2 Nos, Outgoing-4 Nos, Bus Coupler-1 and LT Transformer -2 Nos]. |
| 55 | 36 kV, 1250A, 25 kA, 3-phase, Horizontal Double Break Isolator with earth switch. |
| 56 | 36 kV, 1250 A, 25 kA, 3-phase, Horizontal Double Break Isolator without earth switch. |
| 57 | 36 kV, 1-phase, gap less Surge Arrester complete in all respects with insulating base and surge monitor. |
| 58 | CONTROL & POWER CABLE |
| 59 | Armoured Power Cable (1.1 kV Grade PVC Multi-stranded Aluminium Conductor) |
| 60 | 2 C x 6 Sq. mm |
| 61 | 4 C x 6 Sq. mm |
| 62 | 4 C x 16 Sq. mm |
| 63 | Armoured Control Cable (1.1 kV Grade PVC multi-stranded Copper Conductor) |
| 64 | 2 C x 2.5 Sq. mm |
| 65 | 7 C x 2.5 Sq. mm |
| 66 | 10 C x 2.5 Sq. mm |
| 67 | 12 C x 2.5 Sq. mm |
| 68 | 16 C x 2.5 Sq. mm |
| 69 | 19 C x 2.5 Sq. mm |
| 70 | 33 kV, XLPE Aluminum armoured Cable and accessories as per technical specification. |
| 71 | 33 kV, 1C x 300 sqmm |
| 72 | 33 kV, 3C x 300/240 sqmm |
| 73 | 33 kV XLPE Cable termination equipment along with struncture & accessories for outdoor termination (one set consists for complete requirement for one bay) |
| 74 | Remote Access & Communication System: |
| 75 | (Optical Power Ground Wire (OPGW)) |
| 76 | FODP: |
| 77 | FODP 48F- Indoor type, rack mounted with FCPC coupling and pig tails. |
| 78 | Fiber Optical (ADDSS) Cabling: |
| 79 | 24 Fiber ADSS aerial (DWSM) fiber optic cable. |
| 80 | Telecom equipment: |
| 81 | SDH Equipment (STM-4 MADM, upto 3 MSP protected directions). |
| 82 | Base equipment (Commn cards, Power Supply cards, Power cabling, other hardware & accessories i/c sub-racks, patch cards, DDF etc. fully equipped excluding ii & iii below. |
| 83 | Optical interface cards / SFP: |
| 84 | Optical Line interface Card (to support upto 200 kms). |
| 85 | Tributary Cards: |
| 86 | E1 Interface Card (Min. 16 Interface per card). |
| 87 | Ethernet Interface 10/100 Base T with Layer-2 Switching Min. 8 interface per card). |
| 88 | Termination equipment (Drop and insert multiplexer): |
| 89 | Base equipment (Commn cards, power supply cards, power cabling other hardware & accessories i/c sub-racks, patch cards, DDF etc. Fully equipped excluding subscribed line interface cards. |
| 90 | Subscriber Line Interface Cards: |
| 91 | 2 Wire (sub / sub) voice channel cards (min.8 channels per card). |
| 92 | 2 Wire (sub / Exch) voice channel cards (min.8 channels per card). |
| 93 | Digital Access Cross Connection Switch (DACS) 16 x 16 ports switching matrix, fully equipment for min 16 E-1 Ports. |
| 94 | Equipment Cabinet: |
| 95 | 2 Wire (sub / Exch) voice channel cards (min.8 channels per card). |
| 96 | Digital Access Cross Connection Switch (DACS) 16 x 16 ports switching matrix, fully equipment for min 16 E-1 Ports. |
| 97 | Craft terminal: |
| 98 | Hardware. |
| 99 | Software. |
| 100 | Network manager and element manager system: |
| 101 | Hardware. |
| 102 | Software. |
| 103 | Printer (Laser jet). |
| 104 | Main Distribution Frame (200 Pairs). |
| 105 | Synchronization equipment: |
| 106 | GPS clock including all hardware & accessories. |
| 107 | 4-points VOIP gateway |
| 108 | Telephone set. |
| 109 | DTPC: |
| 110 | Digital Tele-Protection Coupler. |
| 111 | PLCC Equipment: |
| 112 | Wave Trap |
| 113 | PLCC Panels |
| 114 | Modular Coupling Device |
| 115 | HF Cable |
| 116 | Direct Current Power Supply System: |
| 117 | 200 AH 2V, with required numbers plus 10% spares to add to 110V DC nominal voltage Lead-Acid type battery set having electrolyte level float indicators, terminal, connections, required quantity of electrolyte with connectors & all other accessories, complete as required including float cum boost battery charger with full wave rectification, 50 Hz input voltage for charging 200 AH battery & for making auxiliary DC power required for the sub-station with required cable connectors etc. complete & connection with designed DC back up voltage battery set and AC input supply. |
| 118 | 110 V DCDB. |
| 119 | 200 AH 2V, with required numbers plus 10% spares to add to 48V DC nominal voltage Lead-Acid type battery set having electrolyte level float indicators, terminal, connections, required quantity of electrolyte with connectors & all other accessories, complete as required including float cum boost battery charger with full wave rectification, 50 Hz input voltage for charging 200 AH battery & for making auxiliary DC power required for the sub-station with required cable connectors etc. complete & connection with designed DC back up voltage battery set and AC input supply. |
| 120 | 48 V DCDB. |
| 121 | Earthing System: |
| 122 | Mat earthing for entire switchyard with 100x10 mm MS Flat iron including 32 mm dia MS Rod. |
| 123 | Copper plate earthing of transformer CBS, Battery charger, etc. including cost of copper plate size 600 x 600 x 6 mm & copper strip of size 25 x 4 mm i/c salt, charcoal etc as required. |
| 124 | Bus-bar Materials (Hardware Kits): |
| 125 | Bus post insulators & insulator strings, Disc insulators, Hardware, Spacers, Conductor(s), bus bar materials, cable trays, Bay MB, Clamps, connectors including equipment connectors, junction box, Earthwire , Earthing materials, risers, auxiliary earth mat (excluding main earth mat), buried / RCC cable trenches/pipes for equipment & lighting, all accessories etc for the following:- |
| 126 | 132 /33 kV Sub-Station. |
| 127 | Sub-Station Auxillaries: |
| 128 | Fire Protection System: |
| 129 | 9 litre water type. |
| 130 | 4.5 kg carbon di-oxide type. |
| 131 | 5 kg dry chemical powder type. |
| 132 | Air Conditioning: |
| 133 | Split type inverter Air Conditioning Systems. |
| 134 | Switchyard & Building Illumination (lighting) Systems: |
| 135 | Switchyard lighting with complete cabling. |
| 136 | Street lighting with complete cabling & light posts. |
| 137 | Diesel Generating Set : |
| 138 | 100 kVA, 415 Volt with control Panel. |
| 139 | Station Transformer as per ISS: |
| 140 | 3- Ph, 400 kVA, 33/0.433 kV, transformer. |
| 141 | 120 sqmm, 3.5 core XLPE cable for Station DT to LT ACDB panel. |
| 142 | LT Switch Gear Systems: |
| 143 | 415 Volts main switchboard with panel, Fuse-switch combined unit for LT feeders. |
| 144 | 415 V ACDB. |
| 145 | Civil Works associated with equipment foundation: |
| 146 | Steel rods of all sizes for RCC works as per design. |
| 147 | Civil Works for masonary enclosure for equipment earthing: |
| 148 | Cast iron cover of size 650x650 mm along with base for masonry enclosure. |
| 149 | Power Transformer Fire Protection CC Wall: |
| 150 | Steel reinforcement of appropriate size. |
| 151 | Sub-Station Land Development: |
| 152 | Gravel filling two layer of 100 mm with 10 mm (minimum 100 mm thick) upgraded normal size pebbles and one layer of 100 mm sand filling in switchyard area as per technical specification. |
| 153 | SH-III: MANDATORY SPARES |
| 154 | 132 kV Equipment: |
| 155 | 145 kV, 3-φ, Circuit Breaker with accessories. |
| 156 | 145 kV, 600 A, 31.5 kA, 1- Phase, 3- core current transformer with 120% extended current rating complete in all respects along with associated accessories and a common MB (Set of 3 Nos.). |
| 157 | 145 kV, 1250 A, 31.5 kA, 3- Phase Horizontal Centre Break Isolator with earth switch. |
| 158 | 145 kV, 1250 A, 31.5 kA, 3- Phase Horizontal Centre Break Isolator without earth switch. |
| 159 | 120 kV, 1-Phase, gapless Surge Arrester complete in all respects with insulating base and surge monitor. |
| 160 | 132 kV 1-Φ Capacitive Voltage Transformer (CVT) with accessories (Set of 3 Nos.) |
| 161 | 33 kV Gas Insulated Switchgear (GIS): |
| 162 | Solenoid for Blocking Coil on Earthing Switch |
| 163 | Auxiliary Switch for Circuit Breaker |
| 164 | Auxiliary Contact on Close Trip Push button |
| 165 | Blocking Coil Circuit Breaker |
| 166 | Solenoid cpl. for Shunt Closing Release |
| 167 | Solenoid cpl. for Shunt Tripping Release |
| 168 | Solenoid cpl. for Shunt Tripping Release |
| 169 | Hand Crank for Circuit Breaker |
| 170 | Pressure Relief |
| 171 | Auxiliary Switch Disconnector and Earthing Switch Attachment BB top |
| 172 | O-ring for Bottom cable tank with Single Phase Bushing |
| 173 | O-ring for Inspection cover at Bottom cable tank |
| 174 | O-ring for Outer Cone Bushing |
| 175 | O-ring for busbar tank cover width 600 mm |
| 176 | Desiccant Attachment Busbar |
| 177 | Desiccant Attachment CB Compartment |
| 178 | Cam-Disc |
| 179 | PT Bushing size 2 |
| 180 | O-ring for PT Bushing |
| 181 | Bearing block |
| 182 | SF6 gas leakage detector |
| 183 | 33 kV Power Cable termination kit. |
| 184 | Armoured Control Cable (1.1 kV grade PVC multi-stranded Copper Conductor) |
| 185 | 4C x 2.5 Sq.mm |
| 186 | 7C x 2.5 Sq.mm |
| 187 | Armoured Power Cable (1.2 kV Grade PVC Multi-stranded Aluminium Conductor) |
| 188 | 4C x 6 Sq.mm |
| 189 | 132 kV Transmission Line: |
| 190 | ACSR Panther Conductor for 132 kV Transmission Line. |
| 191 | 132 kV 120 kN Composite Polymer Insulator (Tension) as per ISS |
| 192 | Single tension 120 kN hardware fittings with all accessories as per ISS for Panther. |
| 193 | Double tension 120 kN hardware fittings with all accessories as per ISS for Panther. |
| 194 | Midspan compression joints for Panther. |
| 195 | Repair Sleeve for ACSR Panther conductor. |
| 196 | Vibration Damper for ACSR Panther conductor. |
| 197 | ERECTION SERVICES: |
| 198 | SH-I: 132 KV LILO DOUBLE CIRCUIT TRANSMISSION LINE:- |
| 199 | Survey: |
| 200 | Detailed survey including route alignment profiling, tower spotting & final check survey. |
| 201 | Check survey. |
| 202 | Soil Investigation: |
| 203 | All kinds of soil except the following classifications. |
| 204 | Fissured rock with mixed soil. |
| 205 | Hard soil with Fissured Rock. |
| 206 | Tower Foundation Works: |
| 207 | Benching & Excavation works: |
| 208 | Excavation in Hill Area in Soil by Mechanical Means (Excavation in soil in hilly area by mechanical means including cutting and trimming of side slopes and disposing of excavated earth with all lifts and lead upto 1000 metres). |
| 209 | Excavation in Hilly Area in Ordinary Rock by Mechanical Means not Requiring Blasting. (Excavation in hilly area in ordinary rock not requiring ballasting by mechanical means including cutting and trimming of slopes and disposal of cut material with all lift and lead upto 1000 metres). |
| 210 | Pit excavation: |
| 211 | All kind of soil except the following classification. |
| 212 | Fissured Rock with mixed soil. |
| 213 | Hard soil with Fissured Rock. |
| 214 | Hard Rock. |
| 215 | Concreting: |
| 216 | Design & Concreting of Tower footing work on 100% full rate (i.e. Supply & erection of RCC works with cement & concrete) excluding cost of reinforcement steel: |
| 217 | Normal mix Ratio 1:2:4 for M15 compressive strength. |
| 218 | Plain Cement Concrete (PCC) work at base of Tower footings on 100 % full rate at nominal ratio of 1:3:6 or minimum M10 Compressive strength. |
| 219 | Steel rods of all sizes for RCC works as per design. |
| 220 | Pavement (Protection of Tower): |
| 221 | Random rubble stone masonry i/c excavation (with 1:4:8 mixture). |
| 222 | Stone bound in galvanized wire netting i/c excavation. |
| 223 | Back filling and levelling of volumes enclosed in revetment. |
| 224 | Concrete for top seal cover of pavement mix ratio:1:2:4 (M15) |
| 225 | Erection of Tower parts: |
| 226 | Erection of various types of towers and its body leg extension set (complete) i/c tuck and nuts, step bolts, hangers, D-shackles etc and i/c tuck welding and supply & application of enamel and Zinc rich paint. |
| 227 | Safety Alert System: |
| 228 | Danger Plates of size 250 mm x 200 mm of thickness 3 mm. |
| 229 | Number Plate of size 250 mm x 200 mm of thickness 3 mm. |
| 230 | Phase plate (set of three pieces). |
| 231 | Anti climbing devices with G.I. Thornwire/ Barbed wires. |
| 232 | Stringing of line and accessories: |
| 233 | Stringing of Double circuit transmission line, (Six ACSR Panther Conductor) installation of insulator strings (complete fitting) with arcing horns and necessary hardware fitting, (i/c fixing of accessories for power line and OPGW Conductors). |
| 234 | Hill Road Transportation & Head Loading: |
| 235 | Transportation from Designated Bare store (DBS) at Assam-Arunachal boarders to the last road head. (80 MT x 140 km). |
| 236 | Transportation of Materials by head loading from road head to the site of work. Beyond a lead of 100 meters from road to the head load end point payable extra for head load (80 x 150mtr.) |
| 237 | SH-II: 132/33 KV, 2x10 MVA SUB-STATION: |
| 238 | SURVEY & INVESTIGATION: |
| 239 | Soil Investigation: |
| 240 | All kinds of soil except the following classifications. |
| 241 | Fissured rock with mixed soil. |
| 242 | Hard soil with fissured rock. |
| 243 | Galvanised Iron Structure: |
| 244 | Design, fabrication and supplying of hot-dipped GI lattice type tower made with angle iron for 132 kV and 33 kV gantry towers and switchyard equipments support structures. |
| 245 | Galvanizing Stubs, template Nuts & Bolts, spring washers etc. as reqd. |
| 246 | 132 kV Switchyard Equipment: |
| 247 | 3Ф, 10 MVA, 132/33 kV Transformer. |
| 248 | Nitogen Injection Fire Protection System (NIFPS) |
| 249 | Online insulating oil drying system (Catridge type). |
| 250 | 145 kV, SF6, 3- Phase, Circuit Breaker, with support structure. |
| 251 | 145 kV, 600 A, 31.5 kA, 1- phase, 3- Core current transformer with 120% extended current rating complete in all respects, along with associated accessories and a common MB. (Set of 3 Nos.) |
| 252 | 145 kV, 1250 A, 31.5 kA, 3- Phase Horizontal Centre Break Isolator with earth switch. |
| 253 | 145 kV, 1250 A, 31.5 kA, 3- phase Horizontal Centre Break Isolator without earth switch. |
| 254 | 145 kV, 1250 A, 31.5 kA, 3- phase Horizontal Centre Break Isolator without earth switch (Tandem). |
| 255 | 120 kV, 1-phase, gapless Surge Arrester, rating (kV rms) - 120, complete in all respects with insulating base and surge monitor |
| 256 | 132 kV, 1-Phase, Capacitive Voltage Transformer with accessories complete in all respect. (Set of 3 Nos.) |
| 257 | 132 kV Control, Relay and Protection Panels: |
| 258 | Control & Relay panel for line Bay with primary & backup protective relays, LBB relay and other auxiliary relays as required with SAS and all associated accessories. |
| 259 | Control & Relay panel for Transformer Bay with differential, overfluxing, LBB and backup protective relays and other auxiliary relays as required with SAS and all associated accessories. |
| 260 | Control & Relay panel for bus coupler bay with primary & backup protective relays, LBB relay and other auxiliary relays as required with SAS and all associated accessories. |
| 261 | Sub-Station Automation: |
| 262 | Substation Automation System (SAS) confirning IS 61850 with BCU and other complete associated equipment and accessories. |
| 263 | Remote Terminal Unit and SCADA Gateway with all required ancilliary equipment/materials. |
| 264 | 33 kV Equipment: |
| 265 | 33 kV Gas Insulated Switchgear, 1250 A, 31.5 kA for 3 Sec, 50 Hz, as per technical specification.[Incomer- 2 Nos, Outgoing-4 Nos, Bus Coupler-1 and LT Transformer -2 Nos]. |
| 266 | 36 kV, 1250A, 25 kA, 3-Phase, Horizontal Double Break Isolator with earth switch. |
| 267 | 36 kV, 1250 A, 25 kA, 3-Phase, Horizontal Double Break Isolator without earth switch |
| 268 | 36 kV, 1-Phase, gap less Surge Arrester complete in all respects with insulating base and surge monitor. |
| 269 | Control & Power Cable: |
| 270 | Armoured Power Cable (1.1 kV Grade PVC multi-stranded Aluminium Conductor): |
| 271 | 2 C x 6 Sq. mm |
| 272 | 4 C x 6 Sq. mm |
| 273 | 4 C x 16 Sq. mm |
| 274 | Armoured Control Cable (1.1 kV Grade PVC multi-stranded Copper Conductor): |
| 275 | 2 C x 2.5 Sq. mm |
| 276 | 7 C x 2.5 Sq. mm |
| 277 | 10 C x 2.5 Sq. mm |
| 278 | 12 C x 2.5 Sq. mm |
| 279 | 16 C x 2.5 Sq. mm |
| 280 | 19 C x 2.5 Sq. mm |
| 281 | 33 kV, XLPE Aluminum armoured Cable and accessories as per technical specification: |
| 282 | 33 kV, 1C x 300 sqmm |
| 283 | 33 kV, 3C x 300/240 sqmm |
| 284 | 33 kV XLPE Cable termination equipment along with structure & accessories for outdoor termination (one set consists for complete requirement for one bay) |
| 285 | Remote Access & Communication System: |
| 286 | Integration of Hardware systems with last mile connections with Optical Power Ground Wire and Optical Fiber Cables in each Sub Station. |
| 287 | Telecom equipment: |
| 288 | Installation of various Telecom Equipments, Software and Integrating all the Systems, Testing, Commissioning and Operationalising them in each Sub Station. |
| 289 | Tributary Cards: |
| 290 | E1 Interface Card (Min. 16 Interface per card). |
| 291 | Ethernet Interface 10/100 Base T with Layer-2 Switching Min. 8 interface per card). |
| 292 | Termination equipment (Drop and insert multiplexer): |
| 293 | Base equipment (Commn cards, power supply cards, power cabling other hardware & accessories i/c sub-racks, patch cards, DDF etc. Fully equipped excluding subscribed line interface cards. |
| 294 | Subscriber Line Interface Cards: |
| 295 | 2 Wire (sub / sub) voice channel cards (min.8 channels per card). |
| 296 | 2 Wire (sub / Exch) voice channel cards (min.8 channels per card). |
| 297 | Digital Access Cross Connection Switch (DACS) 16 x 16 ports switching matrix, fully equipment for min 16 E-1 Ports. |
| 298 | Equipment Cabinet: |
| 299 | For SDH Equipment (including DDF patching facilities) for Primary Multiplex & other accessories. |
| 300 | For DACS / Mux Equipment. |
| 301 | Craft terminal: |
| 302 | Hardware. |
| 303 | Software. |
| 304 | Network manager and element manager system: |
| 305 | Hardware. |
| 306 | Software. |
| 307 | Printer (Laser jet). |
| 308 | Main Distribution Frame (200 Pairs). |
| 309 | Synchronization equipment: |
| 310 | GPS clock including all hardware & accessories. |
| 311 | PABX. |
| 312 | 4-points VOIP gateway. |
| 313 | Telephone set. |
| 314 | DTPC: |
| 315 | Digital Tele-Protection Coupler. |
| 316 | PLCC Equipment: |
| 317 | Wave Trap. |
| 318 | PLCC Panel. |
| 319 | Modular Coupling Device. |
| 320 | HF Cable. |
| 321 | Direct Current Power Supply System: |
| 322 | 200 AH, 2V, with required numbers plus 10% spares to add to 110 V DC nominal voltage Lead-Acid type battery set having electrolyte level float indicators, terminal, connections, required quantity of electrolyte with connectors & all other accessories, complete as required including float cum boost battery charger with full wave rectification, 50 Hz input voltage for charging 200 AH battery & for making auxiliary DC power required for the sub-station with required cable connectors etc. completed & connection with designed DC back up voltage battery set and AC input supply. |
| 323 | 110 V DCDB. |
| 324 | 200 AH, 2V, with required numbers plus 10% spares to add to 48 V DC nominal voltage Lead-Acid type battery set having electrolyte level float indicators, terminal, connections, required quantity of electrolyte with connectors & all other accessories, complete as required including float cum boost battery charger with full wave rectification, 50 Hz input voltage for charging 200 AH battery & for making auxiliary DC power required for the sub-station with required cable connectors etc. complete & connection with designed DC back up voltage battery set and AC input supply. |
| 325 | 48 V DCDB. |
| 326 | Earthing System: |
| 327 | Mat earthing for entire switchyard with 100x10 mm MS Flat iron including 32 mm dia MS Rod. |
| 328 | Copper plate earthing of transformer CBS, Battery charger, etc. including cost of copper plate size 600 x 600 x 6 mm & copper strip of size 25 x 4 mm i/c salt, charcoal etc as required. |
| 329 | Bus Bar Materials ( Hardware Kits): |
| 330 | Bus post insulators & insulator strings, Disc insulators, Hardware, Spacers, Conductor(s), bus bar materials, cable trays, Bay MB, Clamps, connectors including equipment connectors, junction box, Earthwire , Earthing materials, risers, auxiliary earth mat (excluding main earth mat), buried / RCC cable trenches/pipes for equipment & lighting, all accessories etc for the following:- |
| 331 | 132 /33 kV Sub-Station. |
| 332 | Sub-Station Auxillaries: |
| 333 | Fire Protection System: |
| 334 | 9 litre water type. |
| 335 | 4.5 kg carbon di-oxide type. |
| 336 | 5 kg dry chemical powder type. |
| 337 | Air Conditioning: |
| 338 | Split type inverter Air Conditioning Systems. |
| 339 | Switch yard & Building illumination (Lighting) System: |
| 340 | Switchyard lighting with complete cabling. |
| 341 | Street lighting with complete cabling & light posts. |
| 342 | Diesel Generating Set 100 kVA, 415 Volt with control Panel. |
| 343 | Station Transformer: |
| 344 | 3- Ph, 400 kVA, 33/0.433 kV, transformer. |
| 345 | 120 sqmm, 3.5 core XLPE cable for Station DT to LT ACDB panel. |
| 346 | LT Switchgear System: |
| 347 | 415 Volts main switchboard with panel, Fuse-switch combined unit for LT feeders. |
| 348 | 415 V ACDB. |
| 349 | Civil Works: |
| 350 | Civil works associated with equipment foundation: |
| 351 | Excavation works: |
| 352 | All kind of soil except the following classification. |
| 353 | Fissured Rock with mixed soil. |
| 354 | Hard soil with fissured rock. |
| 355 | Design & Concreting of equipment footing work on 100% full rate (i.e. Supply & erection of RCC works with cement & concrete) excluding cost of reinforcement steel: |
| 356 | Normal mix Ratio1:2:4 for M15 compressive strength. |
| 357 | Plain Cement Concrete (PCC) work at base of equipment footings on 100 % full rate at nominal ratio of 1:3:6 or minimum M10 Compressive strength. |
| 358 | Supply & erection of steel rods of all sizes for RCC works as per design. |
| 359 | Brick Work with best available local bricks in foundation and plinth in cement mortar 1:4 (1 Cement: 4 Sand). |
| 360 | Civil works for masonry enclosure for equipment earthing: |
| 361 | Half Brick masonry with best available local brick in cement mortar 1:4 (1 Cement: 4 Coarse Sand) in foundation and plinth. |
| 362 | 12 mm Cement Plaster 1:3 (1 Cement: 3 Fine Sand). |
| 363 | Cast iron cover of size 650x650 mm along with base for masonry enclosure. |
| 364 | Cable Trenches: |
| 365 | Cable trenches with 1:2:4 PCC work including supply and fabrication of 4 mm steel cover as per design of following sections:- |
| 366 | Section 75cm x 75cm x 10cm (depth x width x thickness). |
| 367 | Section 75cm x 100cm x 10cm (depth x width x thickness). |
| 368 | Section 100cm x 150cm x 10cm (depth x width x thickness). |
| 369 | Other Allied Civil Works: |
| 370 | Design, Engineering and construction of approach road and foot path on 100% full rate i/c T&P, Labour, cement, reinforcement steel, bricks, stone, sand, single earth bitumen and form work, excavation compaction, etc. all complete as per approved design and drawing or as may be required:- |
| 371 | Roads 3.75 m wide (including all crossings) Black topped with broken as aggregate with Hot or Cold bitumen (8cm thick) over RBM base of 10 Cm (Within Substation Premises). |
| 372 | 1:2:4 ratio M 15 compression strength PCC path in switch yard (Thickness of cement concrete 8 cm and of RBM base 10 cm). |
| 373 | 1:3:6 M 10 compression strength Water Drainage as per design in PCC works. |
| 374 | Security wall around the sub station (Brick wall with M15 RCC pillar) on 100% full rate base. |
| 375 | Reinforced cement concrete in retaining wall (any thickness) including attached pillasters, buttresses, plinth and string courses, fillets etc from top of foundation up to floor two level excluding cost of centring, shuttering and reinforcement in: |
| 376 | M20 (1 cement : 1.5 Coarse Sand : 3 stone aggregate 20 mm nominal size). |
| 377 | Power Transformer Fire protection CC Wall: |
| 378 | Design and concreting of CC wall of 1:2:4 (M15) compression strength. |
| 379 | Supply & Erection of steel reinforcement of appropriate size. |
| 380 | Sub-Station Land Development: |
| 381 | Jungle clearance, earth cutting/benching, levelling and removal of debris. |
| 382 | Gravel filling two layer of 100 mm with 10 mm (minimum 100 mm thick) upgraded normal size pebbles and one layer of 100 mm sand filling in switchyard area as per technical specification. |
| 383 | Building Works: |
| 384 | Control Room: |
| 385 | Design, Engineering and construction of RCC structured, Control Room with glass panels on aluminium frames i/c glazing, false ceiling, tiled floors Electrification ( Conceal Conduit), Water supply, Air Conditioning, Battery Room, Office Room, One bed room with toilet and kitchen fully fitted and furnished with fitting furniture, complete as per approved drawing for the estimate area of 150 to 300 sqm. or as per approved design and plinth area for direct use (Details as per TS) on 100% full rate basis. |
| 386 | RCC structure, DG set room with brick wall & rolling shutters annexed to the control room with cable connections to the systems (Approx.- 20 sqm.) on 100% full rate basis. |
| 387 | Residential Building: |
| 388 | Design, Engineering and Construction of RCC structure, tiled floors, brick walled, ceiling, steel trusses and Durashine zinc-aluminium alloy coated sheet roofing/ridges residential building complete in all respect including electrification, water supply with all fitting and fixtures, furnished for direct move in:- |
| 389 | Type-IV, 1 No. as per plinth area (Single Unit). |
| 390 | Type-III, 2 Nos. as per plinth area (Single Unit). |
| 391 | Type-II, 4 Nos. as per plinth area (G+1, 1 No.). |
| 392 | Type-I, 10 Nos. as per plinth area (G+2, 2 Nos). |
| 393 | Hill Road Transportation & Head Loading: |
| 394 | Transportation from Designated Bare store (DBS) at Assam-Arunachal boarders to the last road head. (250 MT x 140 Km). Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 05, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 27, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 11 daysNov 27, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 11 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender