Tender For Annual Maintenance Of Electrical System At Purbachal Minister Quarters, Salt Lake , Kolkata-700106-----Replacement Of Different Type Old Light Fittings, Pvc Fans, Switch Board And Addition Alteration Of Dist. Wiring And Allied electrical i
Tender Overview
Project Description
Tender for Annual Maintenance Of Electrical System At Purbachal Minister Quarters, Salt Lake , Kolkata-700106-----Replacement Of Different Type Old Light Fittings, Pvc Fans, Switch Board And Addition Alteration Of Dist. Wiring And Allied electrical installation Works.-----As And When Required.
BOQ
| Sl. No. | Item Description |
| 1 | Dismantling charges for existing old dist. Wiring, Different type distribution board, computer board, Switch board, fittings, fixture etc. as per direction of EIC. |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required.Group C |
| 3 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C |
| 4 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
| 5 | 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 6 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
| 7 | 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
| 8 | 4 X 16 sq. mm + 2 X 6 sq. mm earth wire |
| 9 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator).8 way (4 + 24), Double door |
| 10 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)12 way , Double door |
| 11 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, \\"C\\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole |
| 12 | Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 A |
| 13 | Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 A |
| 14 | Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required For 8 way, Double door TPN MCBDB |
| 15 | Supply and fixing of 15watt round shape recessed mounted LED Luminaries with Aluminium diffuser & housing (CCT- 4000 K/6500 K, CRI- ≥ 70%, Minimum Lumen Out of Luminaries ≥ 105 lm/watt) for false ceiling application, complete with all accessories having following Model/Cat No.Model/Cat No.-Philips-SM 251/261 LED 20S 6500 PSU WH As per choice of EIC] |
| 16 | Supply and fixing of 4 Ft. Single LED Fitting with 1 no 20 Watt MAS LED tubelight (CCT- 6500 K, CRI- ≥ 70%, Minimum Lumen Out of Luminaries:- 100 lm/watt) for indoor application,complete with all accessories having following Model / Cat No. [Make- Crompton-IGP161LT8-16 1xT8 & -LGT8-20-865-2 /Philips-TMC 502 1X T-LED 22W & Mas LEDTube18W, 2100lm 865 T8 As per choice of EIC] |
| 17 | Supply and fixing of 4 Ft. Double LED Fitting & 2 nos 20 Watt MAS LED Tube light (CCT- 6500 K, CRI- ≥ 70%, Minimum Lumen Out of Luminaries:- 100 lm/watt) for indoor application, for indoor application, complete with all accessories having following Model / Cat No. [Make- Crompton-IGP161LT8-16 2xT8 & -LGT8-20-865-2 /Philips- TMC 502 2X T-LED 22W & Mas LEDTube18W, 2100lm 865 T8 As per choice of EIC] |
| 18 | Supply of LED T8 20watt 1200 mm LED Tube . (Colour Temparature - 6500 K) (Make - Philips, cat No. - Steller Bright TLED ) |
| 19 | S & F of electronics 22-42 Watt, 950 mA LED driver suitable for 36/38 watt 2ft x 2ft LED light fittings. (Philips- 441537014080) /wipro/crompton) |
| 20 | S & F of 12-18 watt LED driver for square and round fittings as per direction of EIC. (Make- Philips/) |
| 21 | Finishing of the PVC insulated wire ends by socketing with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.1.5 sq.mm |
| 22 | 2.5 sq.mm |
| 23 | 4 sq.mm |
| 24 | 6 sq.mm |
| 25 | 16 sq.mm |
| 26 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. |
| 27 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 28 | Supply & Fixtng of Computer board (Modular typel:- Supply & Fixing 240 V, 3 nos.6A, & 1 no.20A Modular type plug socket with separate 3 nos. 6 A & 1 no. 20A Modular type switch, indicator & 20A Modular type SP MCB 25A on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl.S&Fswitch board and cover plate and maling necy. connections with PVC Cu wire and earth continuity wire etc.(Legrand Myrius/ Crabtree/ Siemens3 x 6 A + 1 x 16 A Computer Board |
| 29 | Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board as per GS.25 A, 3 pin Modular type plug socket |
| 30 | Supply and fixing of OLP3+ 25A single phase AC starter on 4 module GI box with supply & fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), with 25A modular type plug top with indicator and switch with 2 Module GI Modular type switch board widl top cover ptate flushed in wall and making necy.connection wire PVC Cu wire and earth continuity wire as per direction of EIC. |
| 31 | S & F Timer Control unit with 12-way SPN DB Box(Mk.- L&T/ Crabtree / Legrand/Siemens/ABB) (For Exhaust Fans of Toilet Block)12 way SPN DB or Timer DB- 1 no40A DP MCB Isolator-1 noDigital 24 hrs.Time switch- I no32A 2-pole power contactor-1noCentre off 2-way toggle switch-1 no32A Barrier type Terminal -1 noLED indicating lamp-1 no6 Amp SP-MCB- 3 nos2x4+1x2.5 Sq.mm Cu wire(Gloster /KEI/RR Kabel) |
| 32 | Supply & Fixing of 250V. 50 Hz. Metal Body wall bracket fan having 40 cm (400 mm) sweep, Air Displacement In M3/Hour-6030, Speed 1420 rpm non-oscillating type aerody.namically balanced, full metal body & Blade and a Strong base for stability,on wall with all accessories (Make : EPC) |
| 33 | Supply & Delivery of Exhaust fans complete with all accessories having the following Model / Cat No. (Make & Model approved by EIC)9\\"(230mm) Sweep, Speed- 1370 RPM, [Make- EPC] |
| 34 | Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length |
| 35 | Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:For 23 cm (9\\") Exhaust fan |
| 36 | Supply & Fixing louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long)For 23 cm (9\\") Exhaust fanNote:-i) Suitable quantity of Common / Regular EI materials like wires, Pipes, piano key type & modular type switches, sockets, MCB of different ratings, modular type switch boards, light fittings etc. should be stored at site by the Agency in advance with his own responsibility to overcome emergency situations.ii) Works through requisition (i.e, Regular work) should be started within 16 hrs & the emergency breakdown works should be started within 4 hrs with requisite manpower after getting the information either from site or from office. Each individual work must be completed with minimum executing time as per site requirement.iii) The Agency must submit the details of communicating person in this regard along with his Mobile number & Email id. |
| 37 | Note:- Rate should be quoted inclusive of all taxes and duties including GST. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 5 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender