Tender For General-Ngo Quarters - G Block-Repair Works To G3 Quarters And Other Maintenance Works In The Compound-Rewiring To El At G3 Quarters And Replacement Of Faulty Fittings In Other Quarters-General Electrical Work
Tender Overview
Project Description
Tender for General-Ngo Quarters - G Block-Repair Works To G3 Quarters And Other Maintenance Works In The Compound-Rewiring To El At G3 Quarters And Replacement Of Faulty Fittings In Other Quarters-General Electrical Work
BOQ
| Sl. No. | Item Description |
| 1 | Electrification |
| 2 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVCinsulated copper conductor single core cable in surface / recessed medium class PVC conduit,with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 3 | 90.3.21.3:Supply & installation of light fittings on 'C/U' shaped flat iron bracket Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture |
| 4 | 1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required. |
| 5 | OD49139/2026-2027:Supply and providing the 9W LED lamp in the existing fittings as required |
| 6 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. |
| 7 | 1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 8 | 90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply |
| 9 | 90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required. |
| 10 | OD49130/2026-2027:Supply, Conveyance, installation , testing and commissioning of 300/305 mm sweep light duty exhaust fans in metal frame in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan. |
| 11 | OD146421/2026-2027:Supply Conveyance, installation, testing and commissioning of 50W LED Flood light output greater than 120lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer) |
| 12 | 90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell |
| 13 | 1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm) |
| 14 | 1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) |
| 15 | 1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm) |
| 16 | 1.23.1:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.5/6 amps switch |
| 17 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch |
| 18 | 1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch |
| 19 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet |
| 20 | 1.23.4:Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet |
| 21 | 1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet |
| 22 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm |
| 23 | 1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm |
| 24 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 25 | 1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm |
| 26 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm |
| 27 | 2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCBdistribution board, 240 volts, on surface/ recess, complete with tinned copperbus bar, neutral bus bar, earth bar, din bar, interconnections, powder paintedincluding earthing etc. as required. (But without MCB/RCCB/Isolator)12 way, Double door |
| 28 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, \\"\\"C\\"\\" curve, miniaturecircuit breaker suitable for inductive load of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required.Single pole |
| 29 | 2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 30 | 2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps |
| 31 | 2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \\"C\\" curve DP MCB complete with connections, testing and commissioning etc. as required. |
| 32 | 90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame) |
| 33 | 90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc. |
| 34 | 90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet |
| 35 | 90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required. |
| 36 | 90.14.7:Supply and providing copper earth bus in the panel board |
| 37 | 90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board |
| 38 | 2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N |
| 39 | 90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL |
| 40 | 90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A |
| 41 | OD50772/2026-2027:S & F 63 A, 415 V, 2 way neutral link mounted on DMC/ SMC base. in the existing meter board and giving connections etc |
| 42 | OD49280/2026-2027:Supplying and fixing 63A HRC Fuse with HRC Fuse link with connections, in existing meter board |
| 43 | OD142491/2026-2027:Supplying and fixing 32A HRC Fuse with HRC Fuse link with connections, in existing meter board |
| 44 | OD142492/2026-2027:S & F 32 A, 415 V, 2 way neutral link mounted on DMC/ SMC base. in the existing meter board and giving connections etc. |
| 45 | OD50787/2026-2027:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipment's including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 1.50sq mm wire single run |
| 46 | OD50788/2026-2027:Supplying and fixing 2 A rating, 240/415 volts, single pole , miniature circuit breaker suitable for control circuit and provide in the existing channel with connections, testing and commissioning etc. as required. |
| 47 | OD50789/2026-2027:Supply and providing Red, Green, Black, Yellow, Orange colors LED indicators, AC/DC 22.5mm cut out dia |
| 48 | 90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG) |
| 49 | 90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG) |
| 50 | OD50815/2026-2027: Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height |
| 51 | OD50825/2026-2027:Danger 415 V, 150 x 100 mm aluminium anodised legend plates |
| 52 | OD50826/2026-2027:Bus bar chamber, 100 x 40 mm aluminium anodised legend plates |
| 53 | OD50827/2026-2027: Cable alley, 100 x 40 mm aluminium anodised legend plates. |
| 54 | 5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 55 | 90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG) |
| 56 | 90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG) |
| 57 | 90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG) |
| 58 | OD49129/2026-2027:Supply and providing 25x3mm brass nut and bolt etc. as required |
| 59 | OD49134/2026-2027:Supply and providing 12x3mm brass nut and bolt etc. as required |
| 60 | OD146375/2026-2027:Supply and drawing Aerial Bunched Cable LT 5x35sqmmcables over existing RCC/GI poles including binding etc. as required. |
| 61 | OD146370/2026-2027:Supply and fixing axis piercing connector for ABC 16-95sqmm |
| 62 | OD146371/2026-2027:Supply and fixing SS Buckle for LT 5x35sqmm AB cable |
| 63 | OD146372/2026-2027:Supply and fixing SS Trap for LT 5x35sqmm AB cable |
| 64 | OD146373/2026-2027:Supply and fixing axis suspension clamp for LT 5x35sqmm AB cable with pole bracket |
| 65 | OD146374/2026-2027:Supply and fixing Dead end clamp for LT 5x35sqmm AB cable with pole bracket |
| 66 | OD146418/2026-2027:Supply and fixing 50 mm dia 6Kgff/cm2 PVC pipe including fixing the pipe with clamp/clips at 60cm spacing. etc as required (For Service Pipe) Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender