Tender For Repairs To Electrical Installations For Improvement Of External Lighting At Fsd Ujjain.
Tender Value
11.31 Lakhs
Estimated cost
Bid Submission
16 Nov 2026
9 days left
EMD
22700
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Ujjain → Madhya Pradesh
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Repairs To Electrical Installations For Improvement Of External Lighting At Fsd Ujjain.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying and fixing of 300 mm x 300 mm size metalic frame cover fabricated with 25 mm x 25 mm x 3 mm thick angle iron welded construction frame structured and 1.6 mm thick M. S. sheet cover plate with double hinges and knobe type locking arrangement including painting, making recess in wall, masonary, plastering & finishing the good |
| 2 | Supplying and fixing of 600 mm x 600 mm size metalic frame cover fabricated with 35 mm x 35 mm x 5 mm thick angle iron welded construction frame structured and 2 mm thick M. S. sheet cover plate with double hinges and knobe type locking arrangement including painting, making recess in wall, masonary, plastering & finishing the good |
| 3 | Supplying and fixing of 1200 mm x 600 mm size metalic frame cover fabricated with 35 mm x 35 mm x 5 mm thick angle iron welded construction frame structured and 2 mm thick M. S. sheet cover plate with double hinges and knobe type locking arrangement including painting, making recess in wall, masonary, plastering & finishing the good |
| 4 | Supplying and drawing sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel / PVC conduit as required. |
| 5 | 3 x 1.5 sq. mm |
| 6 | 4 x 1.5 sq. mm |
| 7 | 5 x 1.5 sq. mm |
| 8 | 3 X 2.5 Sq mm |
| 9 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 10 | 20 mm |
| 11 | 25 mm |
| 12 | Supplying and fixing 4 way (4 + 12), Double door prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FRLS PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator) |
| 13 | Supplying and fixing 8 way, double door, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) |
| 14 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
| 15 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.. |
| 16 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 17 | Supplying of Pressure Die Cast 35/ 36 watt LED well glass with high efficacy of greater than or equal to 120 lumens / watt fitting with control gear housing, IP 66 Protection with heat resistance glass eye bolt provided for mounting purpose & wire guard 35 / 36 Watt etc. as required of make of reputed brand under MII confirming to IS and IEC codes on the platform of godown truss/ truss of the shed blocks as directed by the Engineer incharge with M. S. clamps wiring with 3 x 1.5 Sq mm PVC insulated / WP flexible copper conductor wire, painting the clamps including connections and dismantling the existing fittings etc. as reqd. |
| 18 | Supply of 70/72 Watt LED Street light made up with pressure die cast aluminium housing with weather proof conditions suitable for all weathers, toughened clear glass, high power LEDs with secondary optics and IP 66 protection. The luminaire should have the efficacy greater than or equal to 100 lumens per Watt of make of reputed brand under MII confirming to IS and IEC codes etc. as reqd. as approved by Engineer in charge. (NABL certified as per specification) |
| 19 | Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required. |
| 20 | Supplying of XLPE insulated & PVC tape innersheathed aluminium conductor armoured cable of 1.1 KV grade of following size confirming to IS:7098 (Part- I) 1988 with up to date ammendment as required. |
| 21 | 4 x 25 sqmm |
| 22 | 4 x 16 sqmm |
| 23 | 2 x 10 sqmm |
| 24 | Demolishing / cutting concrete manually/ by mechanical means with exellent finishing without making any damage to remaining road as per direction of Engineer- in-charge |
| 25 | Providing and laying in position cement concrete of specified grade and finishing the same as per direction of Engineer- in-charge 1:2:4 (1 cement : 2 coarse sand : 4 graded stone |
| 26 | Supplying and fixing of light class G.I. pipe of following dia. (nominal) along the pole or surface of wall or on the for protection of cable as required. |
| 27 | 32 mm Dia. |
| 28 | Supplying and fixing of heavy C class G.I. pipe of following dia. (nominal) for placing under the road before refill for protection of cable as required. |
| 29 | 100 mm Dia. |
| 30 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size existing masonry open duct as required. |
| 31 | up to 35sqmm |
| 32 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall or steel structure surface as required. |
| 33 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
| 34 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL / HDPE pipe as required. |
| 35 | Upto 35 sq. mm |
| 36 | Supplying and making end termination with brass compression gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 37 | 2x 10 sq. mm (19 mm) |
| 38 | Supplying and making end termination with brass compression gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 39 | 4 X 16 sq. mm (28mm) |
| 40 | Supplying and making end termination with brass compression gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 41 | 4 X 25 sq. mm (28 mm) |
| 42 | Supplying of 7m high hot dip galvanized octagonal street light pole confirming to ASTM, BSEN, ISO STANDARDS with 70 mm top dia, 130 mm bottom dia, 3mm thick and with a base plate of 200 mm x200 mm x 12 mm complete with 1 mtr hot dip galvanized single Arm bracket with maximum diameter range 40 mm at the arm end for fixing the street light, having provision of internal junction box and suitable foundation bolts etc. as required at the site of work. |
| 43 | Erection of metallic pole of Above 6.5 meter and upto 8.0 meter length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size ) foundation including excavation and refilling etc. as required. |
| 44 | Dismantling of pole/ street light standard/ strut embedded in brick ballast foundation etc. as required. |
| 45 | Supplying & Fixing busbar chamber of reputed brand under MII confirming to IEC-61439-3 / IS-8623 & IEC-60529 / IS-2147of size not less than 400X300X150 and is fabricated using sheet steel (CRCA) and epoxy powder coated to give superior & lasting finish. The bus bar sections are made of ETP grade copper & dull tin plated and the bus bar supports are made of DMC (Dough moulding compound). Left & Right side end plates are detachable. of following capacity and fixing, earthing the body etc. along with necessary connections as required |
| 46 | 100 Amp (on wall) |
| 47 | \\"Supply, Installation, testing & commissioning of cubicle canopy type totally enclosed free standing type moisture, dust and vermin proof Panel Board made out of 2.0 mm thick CRCA sheet Steel IP 42 floor mounting type and the same will be installed in ground at a height of 400 mm using MS Angle base frame suitable size of 50 mm x 50 mm x 3 mm size angles with necessary CC foundation with minimum dimension of 1000 mm(H) X 600 mm (W) X 300 mm(D) fabricated in compartmentalized design. The sheet steel shall undergo minimum 9 tank treatment followed by finishing powder coating of min 60 micron thickness. the board includes 415 V electrolytic, 200 Amp (each strip) 04 nos Aluminium Bus Bar, removable gland plates, cable glands, including connection with outgoing feeders complete in all respect. All MCCB shall have thermalmagnetic release with adjustable over current, short circuit & Earth fault protection with trip history (Faulty phase, type of fault and interupted Current). All MCCB's shall be ics = 100% Icu, with rotary handle & pad locking arrangement, with adjustable O/L & S/C trip setting as per load requirement. \\" |
| 48 | Incoming01 Nos of 80 Amp FP Moulded Case Circuit Breaker. (10 KA) (Conforms to IS/IEC 60947-2)Outgoing02 Nos of 32 Amp FP Moulded Case Circuit Breaker. (10 KA (Conforms to IS/IEC 60947-2)06 Nos of 32 Amp DP Miniature Circuit Breaker. (10 KA (Conforms to IS/IEC 60947-2) |
| 49 | Providing and Fixing weather proof loop in loop out box of size not less than 155 mm X155 mm X 100 mm, shockproof and rustproof, Cable entry from bottom and/or sides, left/right hinged door fixing, Maintenance-free, Fire retardant, can be fitted at the bottom of pole / wall / on truss of Gdn, made of PVC Sheet of reputed brand under MII confirming to IS and IEC codes with copper bus bar strip 2 nos. / cable connectors suitable for required size of aluminium armoured cable, Hinged Cover & Locking arrangement, Providing & Fixing Links for termination of Cables and SP MCB 6 amps including 1.5 Sqmm PVC sheathed PVC insulated three core cable from MCB to individual fittings and connection leads etc. complete including connections fixing of cable on pole / wall / truss with M.S. clamps etc. as required. |
| 50 | Supply of 2mtrs X 1mtrs X 2 mm corrugated rubber mat as reqd. confirming to IS specification 15652/2006 with ISI mark suitable for electrical application. |
| 51 | Supplying, Installation, Testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
| 52 | Applying priming coat: With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works |
| 53 | Painting with synthetic enamel paint of approved brand and manufacture to give an evenshade : Two or more coats on new work |
| 54 | The items are to be dismentalled where the work has to be executed and take away by the giving the credit to the work estimate |
| 55 | Conduit Pipe, old Panel Board, MS clamp, Iron material etc |
| 56 | Aluminium cables etc. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 04, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 16, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 9 daysNov 17, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 10 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender