Tender For Augmentation Of Ht Supply Along With Rmu And Connected Accessories For Cg Enclave Chicolna Goa Under Ge (I) (Cg) Goa
Tender Overview
Project Description
Tender for Augmentation Of Ht Supply Along With Rmu And Connected Accessories For Cg Enclave Chicolna Goa Under Ge (I) (Cg) Goa
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Nov-2026 | CORRIGENDUM | Other | 25-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Supply, installation, testing and commissioning of 11KV, 630 Amps having short circuit capacity 21kA/3-sec, outdoor (IP-54 type). RMU (Ring main unit) 3 x way outdoor, extensible motorised SCADA compatible RMU consisting of two incoming with load break switch and 2 Nos feeder with VCB (LBS 2 Nos + 02 VCB), outdoor use self powered relay Air Insulated metering PT module, copper bus bar of suitable capacity all inside single, gas filled, robotically welded stainless steel 304 (Non ferrite Non Magnetic Grade) tank with minimum thickness 2mm, IP67 Degree of protection, internal arc classified 21kA/1 sec as per IEC62271-200. The enclosure shall have pad lockable with anti theft hinges, fully covering the front facia and cable boxes to ensure fail-safe anti theft protection complete all as specified and as directed with following specifications :- |
| 2 | (a) Two No. 630 Amps capacity triple pole metal clad HT control panel totally enclosed extended pattern air insulated metal clad housing, floor mounting vertically isolated, vermin proof, fully interlocked horizontal draw out type having double isolation features & control devices with grounded neutral system and equipped with the following equipment :-(i) One set of 3 phase 630 Amps air insulated, tinned copper bus bar with insulated colour coating(ii) One set of side frame for housing for circuit breaker carriage.(iii) 3 Nos 630 amps isolators plugs(iv) One Set of mechanical interlock and automatic shutter system.(v) Three 630 Amp triple pole 350 MVA rupturing capacity VCB with automatic drop out and manually charged and motor operated spring closed mechanism complete with auxiliary switches, track mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication, mechanical indication \\"ON\\" push button for emergency trip and 30 Volts DC trip coil.(vi) One cable box suitable for reception for 95/185/300 sqmm HT XLPE 3 core under ground cable 11000 volts pressure.vii) 03 Nos double wound current transformer dual ration 150/100 5-5 amps for protection and metering having adequate VA burden and accuracy(viii) One Set of 4 Nos LED lamp for indicates ON/OFF/Trip/Charging. |
| 3 | (ix) One 3 phase horizontal draw out type voltage transformer 100 VA burden and accuracy mounted on the draw able housing for 11000 volts/110 volts with protection fuse.(x) 144mm square type CT operated flush pattern digitals amps meter scaled with dual range 0-200 amps with there way on/off rotary selectors switch(xi) Scada compatible, one set of 3 pole micro process relay 3 phase over current, earth fault relay with high set & RS 485 Port (xii) One 144mmm square PT operated flush pattern analog volt meter 0-15 KV scaled operated with and including three way rotary type selector switch(xiii) One No volt coil to trip the VCB on failure of electric supply(xiv) One set of mechanical interlock and automatic shutter gear(xv) 230 volts AC single phase 80 watt rated strip heater with switch and thermostat space heating.(xvi) Provision of 30 volts DC tripping system with suitable power pack including, siren/horn alarm and accept switch and over voltage protecting relay(xvii) Provision of motor charging with AC motor operated on 230 V(xviii) Inbuilt Power pack 30V DC to be provided with panel at least for 30 minute Back up. |
| 4 | (xix) Annunciator complete with showing type of fault, accept/reset button with minimum 12 windows and suitable for auxiliary supply voltage 30 volt-1No(xx) Under voltage single phase/over voltage relay - 5 No. (xxi) Trip Circuit supervision Relay (VAX) - 1 No |
| 5 | Supply and laying in trenches/ duct of HT under ground XLPE insulated screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor suitable for 11 KV grade (Earthed) cross sectional area 95 sqmm, 3 core complete all as specified and as directed.Note : Necessary earthwork, cable protection items shall be measured & paid separately. |
| 6 | Supply and laying un re-inforced precast concrete cable cover, class HV, type-I, flat size 300 mm x 180 mm x 50 mm in trenches over and across the cable complete all as specified and as directed. |
| 7 | Material and labour for cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 11 KV UG aluminium conductor armoured XLPE cable of size 50 to 95 sqmm 3 core complete all as specified and as directed. |
| 8 | Material and labour for cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 11 KV UG aluminium conductor armoured XLPE cable of size 50 to 95 sqmm 3 core complete all as specified and as directed. |
| 9 | Material and labour for cable jointing kit for 11 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core 11 KV UG aluminium conductor armoured XLPE cable of size 70 to 95 sqmm 3 core complete all as specified and as directed. |
| 10 | Supply, lay and testing cable XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core complete all as specified and as directed.Note : Necessary earthwork, cable protection items shall be measured & paid separately. |
| 11 | Supply, lay and testing cable XLPE Insulated screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core including taking down complete all as specified and as directed.Note : Necessary earthwork, cable protection items shall be measured & paid separately. |
| 12 | Material and labour for cable jointing kit for 11KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core 11 KV UG aluminium conductor armoured XLPE cable of size 70 to 120 sqmm 3.5 core complete all as specified and as directed. |
| 13 | Material and labour for cable jointing kit for 11KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core 11 KV UG aluminium conductor armoured XLPE cable of size 25 to 50 sqmm 3.5 core complete all as specified and as directed. |
| 14 | Supply and lay cable cover LV type 1 flat size 250 x 150 x 40 mm for cable protection including taking down complete all as specified and as directed. |
| 15 | Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in soft/ disintegrated rock for taking up/ relaying LT UG cable/ pipe complete all as specified and as directed. |
| 16 | Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in hard/ dense soil for taking up/ relaying LT UG cable/ complete all as specified and as directed. |
| 17 | Returning filling in excavated earth work including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any strata complete all as specified and as directed. |
| 18 | Removing excavated soil to a distance not exceeding 50m, depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. |
| 19 | Supply and lay dry riddled sand in trenches for cable protection complete all as specified and as directed. Note: Punned thickness only will be measured and paid separately. |
| 20 | Material and labour for factory made precast cement concrete cable route Indicator made out of cement concrete 1:2:4 type B1, using (20mm graded stone aggregate) of size 900 x 400 x 60mm casted and grouted into PCC 1:2:4, type B1, 35cm below ground level as per site requirement including embossed with \\"HT 11000 V/ LT 1100 V cable\\" and also painting in synthetic enamel paint and necessary excavation and earth work in any type of soil complete all as specified and as directed. |
| 21 | Shifting of existing of LT electrical panel from its present location to the designated new location including disconnection of incoming and outgoing cables, dismantling safe handling, transportation, reinstallation, reconnection of cables, glands, and lugs as required, complete with testing and commissioning, ensuring proper functioning of the panel as per site requirement complete all as specified and as directed. |
| 22 | Supply and lay pipe galvanized, \\"Medium class\\", 80 mm (2\\") dia for cable protection etc complete all as specified and as directed. |
| 23 | Dismantling and shifting of existing distribution Transformer 11/0.433KV upto 100KVA (Earthed) by using hydra crane arrangement from existing plinth/ present location to the new location not exceeding 500 mtr by arrangement of suitable transportation with complete isolation of transformer from HT/LT system including disconnecting all HT/LT cable, earthing lead and other accessories and installation, commissioning as per IE standard with full safety precautions at installation site recommissioning of transformer with necessary dehydration and filtration of existing transformer oil/top-up of new oil with high pressure vacuum filtration plant to improve dielectric strength of insulating oil including testing for BDV of the filtration oil not to be less than BDV 60KV lugs change, replacing of existing breather with new as per existing capacity complete all as specified and as directed.Note: (a) Rates includes the requirement of tools/plants at site where transformer oil to be filtered.(b) Transformer shall be kept in OFF position during filtration.(c) Temperature of oil should be kept below 75 C during |
| 24 | Material and labour for construction of plinth platform of size 2m x 2m x 1.2m for Transformer, using 100mm thick PCC 1:4.8 type D2 as in lean concrete foundation, 230mm thick fly ash brick masonry wall built in CM 1:6 upto 1.00m height and the top of the plinth shall consist of 100mm thick PCC 1:2:4, type B-1 using 20mm graded stone aggregates over 75mm thick PCC 1:4.8 type D2 over compacted soil/disintegrated rock filling, 10mm thick rendering in CM 1.4 on brick surface with and including 25cm thick stone aggregates of size 12.5 mm all around upto and including 1.5m from the edge of the plinth including provision of cable duct HT/ LT site with pipe provision etccomplete all as specified and as directed by Engineer-in-Charge. |
| 25 | Material and labour for Earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 m below ground level and connected to GI earth strip of size 32 x 6mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC pit & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection (upto 7.5m long) & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 and testing on completion complete all as specified and as directed.Note: On completion of the work/job the Contractor is to perform earth resistance tests for each earthing job in the presence of the Engineer-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Department till the results are satisfactory. |
| 26 | Material and labour for Earthing complete with Galvanised steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (in vertical position) earth pit not less than 2.25 mtr below normal ground level with the top edge of the earth plate not less than 1.5 m below ground level and connected to GI earth strip of size 25 x 4mm by means of bolts, nuts, check nuts, and washers of galvanized iron including PCC pit & cover with suitable handle, including necessary excavation and earth work in any type of soil, 20 mm dia med grade galvanized steel tube for watering with one end fixed with suitable funnel and wire mesh, 40 mm bore medium grade galvanized steel tubing for drawing earth lead GI strip protection (upto 7.5m long) & common salt, charcoal in alternate layers etc. complete all as shown in EP No 3 of SSR Part 1 and testing on completion complete all as specified and as directed.Note: On completion of the work/job the Contractor is to perform earth resistance tests for each earthing job in the presence of the Engineer-In-Charge or his rep & submit test certificates duly signed & certified. If the test results are not satisfactory or not within the permissible limits of relevant Standards/IS then the job is to be redone without any extra cost to the Department till the results are satisfactory. |
| 27 | Material and labour for graded coarse aggregate (broken stone or boulders) of size 20-40 mm in substation yard for laying and removal of grass, levelling/ dressing of site before laying complete all as specified and as directed. |
| 28 | Dismantling concrete four poles structure of any size and demolition of concrete base including all accessories like M.S Channel, stay assembly, insulators any type, earthing cross arm, GOD and ACSR or AAC conductors etc complete all as specified and as directed. |
| 29 | Dismantling concrete two poles structure of any size and demolition of concrete base including all accessories like M.S Channel, stay assembly, insulators any type, earthing cross arm, GOD and ACSR or AAC conductors etc complete all as specified and as directed. |
| 30 | Demolition of existing transformer PCC/ RCC work foundation/ base complete, including breaking, cutting of reinforcement, dismantled material/ debris from site to outside premises and complete site clearance/ dressing complete all as specified and as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 2 daysBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender