Tender For Upgradation/Replacement Of Existing Substation Automation System At 220Kv Jawaharnagar Gis Aegcl
Tender Value
2.06 Crore
Estimated cost
Bid Submission
25 Nov 2026
16 days left
EMD
4.13 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Kamrup Metro → Assam
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Upgradation/Replacement Of Existing Substation Automation System At 220Kv Jawaharnagar Gis Aegcl
BOQ
| Sl. No. | Item Description |
| 1 | Supply: SOFTWARE |
| 2 | Supply of SAS software with minimum 5,000 tags/data points, including minimum 2,000 archive tags, supporting IEC 61850 Edition 1 and Edition 2, along with all necessary software licenses, communication drivers, engineering/configuration tools and associated software required for complete monitoring, control, alarm/event management, trending, reporting and historical data management of the substation.The SAS should be able to run in Hot-Hot mode and Hot-Standby mode. (BOTH MACHINES SHOULD HAVE \\"HOT/MAIN SERVER\\" MODES IN THE LICENSE.SNMP license should be present in the SCADA. Dynamic SLD provision should be included in the SCADA license. |
| 3 | Gateway software |
| 4 | DR/IED analysing Softwares |
| 5 | Supply including F&I: Hardware |
| 6 | HMI-1 (Main-I)Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro /server latest edition , 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent) |
| 7 | HMI-2 (Main-II)Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro /server latest edition , 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent) |
| 8 | DR PC:Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro, 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent) |
| 9 | Metering Workstation:Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro, 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent) |
| 10 | Gateway (Main-I)Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro/server latest edition , 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent)ORWall mounted hardware based Gateway/RTU Panel shall be provided as per specification |
| 11 | Gateway (Main-II)Industrial grade Computer with minimum following specifications:Based on Intel Core i7, 12th Gen CPU, 32GB DDR4 Memory, 1*1TB 2.5” SSD, DVD-Drive, 2*10/ 100/1000 mbps LAN Ethernet Ports onboard, 2*Seriai, 4*USB 3.0, 1*VGA and 1*HDMI Port onboard, 1*USB Keyboard and Optical Mouse, 1*400-Watt Single Power Supply,. OS - Windows 11 Pro/server latest edition , 64-bit OS, MS Office 2021, Antivirus (Make: Advantech/Technics or Equivalent)ORWall mounted hardware based Gateway/RTU Panel shall be provided as per specification |
| 12 | 32\\" LED Monitor, resolution 1920*1080 (make: Dell/Samsung or Equivalent) |
| 13 | A4 Color Laser printer (Make: HP/Canon/Xerox or Equivalent) |
| 14 | Time synchronization clock with antenna and 50 mtr antenna cable (Make: MASIBUS or Equivalent) Time synchronization clock with multiband antenna and 100 mtr antenna cable. Time synchronization clock shall be MTCTE compliant and display unit shall be provided. |
| 15 | 3 kVA 1:1 Phase On Line UPS (with Isolated Transformer) with Battery & Battery rack (Make: Digiline or Equivalent) |
| 16 | 2 Port RS485 to 1 port ethernet convertor, metal enlosure 24V DC Power input (Make: Databridge or Equivalent) |
| 17 | Single Feeder BCU for 220 kV Lines, Transformer (HV and LV side), 220 kV Bus Coupler compatible with existing/offered SCADA (Make: Hitchi/GE/Siemens) |
| 18 | Dual Feeder BCU for 33 kV Feeders and 33 kV Bus Coupler compatible with existing/offered SCADA (Make: Hitchi/GE/Siemens) |
| 19 | Numerical Backup Relay for 33 kV Feeders and 33 kV Bus Coupler |
| 20 | SERVICES |
| 21 | Engineering and confuguration of complete Substation Automation System alongwith Factory acceptance test |
| 22 | Installation, testing and commissioning, training and handover of complete Substation Automation System including installation and commissioning of supplied equipments along with configuration and integration of new and existing IEDs with the offered SAS as per Bid specification and scope |
| 23 | SPARE EQUIPMENT (PART - B) |
| 24 | Industrial managed Ethernet Switches (with both ST port and RJ45 Port) (Make: Ruggedcon, Hirschmann, Cisco) |
| 25 | Single Feeder BCU for 220 kV Lines, Transformer (HV and LV side), 220 kV Bus Coupler as spare (compatible with existing SCADA, Make: Hitchi/GE/Siemens) |
| 26 | Dual Feeder BCU for 33 kV Feeders and 33 kV Bus Coupler as spare (compatible with existing SCADA, Make: Hitchi/GE/Siemens) |
| 27 | Numerical Backup Relay for 33 kV Feeders and 33 kV Bus Coupler as spare |
| 28 | Annual Maintenance Contract for Maintenance of SAS at 220KV Jawaharnagar GIS for next 7 Years after completion of warranty period as per bid specification. AMC will be of non-comprehensive type Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 25, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 16 daysNov 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 17 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender