Project Description

Tender for Repairs/Maintenance Of Ht/Lt Oh Lines, Ug Cables And Lt Switch Gears Installed, Transformers At Dmrl/Atc & Rcma (Mat) Hospital Area Kanchanbagh, Hyderabad.

BOQ

Name of Work:- REPAIRS/MAINTENANCE OF HT/LT OH LINES, UG CABLES AND LT SWITCH GEARS INSTALLED, TRANSFORMERS AT DMRL/ATC & RCMA (MAT) HOSPITAL AREA KANCHANBAGH, HYDERABAD.
Sl. No. Item Description
1Testing and setting the relays of VCB's/SF6s breakers of 33 KV by primary injection method of any make/model and servicing the mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all the complete to the entire satification of Engr-in-charge.
2S&F digital type volt meter suitable for Eleven KV breaker ranging (0-11KV/0 to 440 V) suitable for auxilary voltage 230 volts complete including taking down old unserviceable voltmeter complete all as directed. Make- MECCO/CONZERV
3Disconnecting and taking down the worn out jumpers in 33 KV yard and supply and fix new jumpers cutting to adequate length of ACSR conductor panther complete all as specified and directed.
4Dehydration and filtration upto 5 MVA transformer 33/11 KVA, HT OCB oil indoor/outdoor/ isolation type at different location and different size of transformer from 63 KVA to 1000 KVA or any capacity Transoformer on DMRL/ATC location with centrifuging machine, manually operated and achieve BDV 60 KV including carrying out oil testing before and after the dehydration process for each OCB complete all as directed. Note : Required oil for top up will be measured and paid separately under relevant item of schedule.
5Supply only topping up of transformer/OCB oil as per IS :335, break down voltage not less than 60 KV all as specified and directed.Make :- Power Oil/Electrol/Savita
6Supplying, installation, commissioning and testing in replacement of 33 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 400/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
7Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed
8Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE, HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 95 sqmm 3 core all as directed.Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
9Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE, HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 120 sqmm 3 core all as directed.Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
10Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductor cable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:-Make: HAVELL'S/UNIVERSAL/CCI/GLOSTER/KEI/ POLYCAB/ KEC INTERNATIONAL (RPG)
113.5 core x 120Sqmm
123.5 core x 185 Sqmm
133.5 core x 150 Sqmm
143.5 core x 300 Sqmm
153.5 core x 400 Sqmm
16M&L for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.
17S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11/33 KV control panel including associated wiring, if reqd, complete all as specified and directed.
18M & L for cutting and removing grass, vegetation bushes etc from surrounding HT installation as bushes grows during a period of contract and removing all rubbish to a distance not exceeding 50 m as directed.
19M&L for Repairs/maintenance of 11KV HT VCB/ SF6 breakers Panel including bus coupler of any type, size and capacity complete including the following :- Taking out 11KV HT VCB/OCB/SF6 breakers of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical/motorised system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and cleaning/servicing the entire motorised mechanism of VCB including all spare parts required at site, reassembling the VCB connection, testing, commissioning and putting on load to the entire satisfaction of Engr-in-charge.
20S&F Earthing complete with copper plate electrode 600x 600x 3 mm thick buried directly in ground vertically to a depth not less than 2.25 mtr deep below normal ground level with top edge of earth plate, not less than 1.5 mtr below normal ground level connected to copper strip earth lead of size 20 x 3 mm by means of bolts, nuts/check nuts and washers etc of galvanised iron, protected by galvanised iron pipe light grade 50 mm dia and connected to main switch/control board including necessary excavation earth work in any type of soil and PCC 1:3:6 type C1 for earth chamber, 40 mm thick RCC cover slab 1:2:4 type B1 with 6 mm dia TMT Bars at 140 mm cc both ways, watering pipe 20 mm dia light grade GI, funnel, wire mesh, lugs, charcoal and salt etc complete all as shown in Electrical plate No. 3 SSR Part I and testing complete including removing unserviceable any type of items all as specified and directed.Note : Copper strip and GI pipe 50 mm dia beyond 7.5 metres per earth will be measured and paid separately.
21Ditto all as per item No: 15 above but using 32 x 6 mm galvanised MS strip earthing lead and MS galvanised plate of size 600 x 600 x 6 mm as earth electrode.
22S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated location for loop earthing etc. as required of size 32x6 mm GI strip complete all as specified and directed.
23Supply & Fix Gasket inreplacement for upto 5 MVA transformer (SRC RC 70C Grade) with including all required T&P for drain out and refilling transformer oil after proper filteration,comminissioning and testing complete complete all as directed.
24Testing and re-setting and calibration of protection relay of 11 KV RMU/VCBs/SF6 breaker (indoor/outdoor) for incoming and out going feeders with control panel and control cable differential relay through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Checking the condition of transformers (Oil & winding temp and B/H relay) and taking corrective checking and operating the switchgear and trip circuit of HT panel/breakers for its proper functioning complete all as specified and directed.Note:- Reports after calibration to be submitted and the autherised techinicion should attend the malfunctioning/routine service complints as and when required for entire contract period under warrenty.
25M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm.
26M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm.
27M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm.
28M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 240 to 300 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
29M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
30M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed.
31M&L stay assembly complete with accessories as shown in electrical plate no 1 including loop type isolator stay clamps stay strands excavation work and PCC work with 20 mm dia complete all as specified and directed.
32Supply, fix and testing power pack with battery backup input 230 V AC, output 110 V DC, 1Amp suitable for existing HT 11 KV VCB panel complete all as specified and directed.
33Supply, fix, testing and commissioning of Air break gang operated switch, triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT polymeric insulators and steel channel frame, GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated including locking arrangement for operating handle with and including 7 levers Navtal lock complete suitable for current rating of 400 Amps HT 11 KV working pressure all as specified and directed.
34Supply and Fix Dropout fuse unit, horn gap type single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts washers etc, synthetic bounded fuse carrying tube complete with line taps and suitable for current carrying capacity upto 40 Amps only all as specified and directed.
35Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive on one primer coat, one under coat and one finishing coat of paint.
36Supply, Install and erect steel tubular swaged pole type 410 SP-55 of 11.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed.Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, coping of poles, cross arms, clamps shall be measured and paid separately.Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing.
37Supply, Install and erect steel tubular swaged pole type 410 SP-31 of 9.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed.Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, coping of poles, cross arms, clamps shall be measured and paid separately.Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing
38Material and Labour for PCC 1:3:6 type C2 wiring 40 mm stone aggregate for foundation of poles/transformer bed/cable duct foundation/panel base/ chain link supports etc including necessary form work etc complete all as specified and directed.
39Material and Labour for PCC 1:2:4 type B1 wiring 20 mm graded stone aggregate for coping of pole including necessary form work etc complete all as specified and directed.
40Material and Labour for Brick work with sub-class bricks straight or curved on plan exc 6m mean radious in CM (1:6) complete all as specified and directed.
41Material & Labour for 10mm thick rendering in cement motar (1:6) mixed on brick or concrete surfaces finished even & smooth w/o using extra cement complete all as specified and directed.
42Material & Labour for Providing precast cement concrete in landing cover slab type B-1 1:2:4 (20mm graded agg) set in cement 1:4 complete all as specified and directed.
43M&L for spreading the 20mm coarse aggregate in various sub stations and other locations complete all as directed.
44M&L for Preparation of old painted inner and outer surfaces of indoor/out door HT/LT panels, spray painting the same with two coat of synthetic enamel paint grey an a coat of red oxide to achive smooth finish including writing of SM/MES No complete all as directed.
45M&L for Preparation of old painted transformer upto 1000 KVA spray painting the same with two coat of synthetic enamel paint grey an a coat of red oxide to achive smooth finish including writing of SM/MES No complete all as directed.
46M&L for Preparation of old painted transformer upto 5 MVA , spray painting the same with two coat of synthetic enamel paint grey an a coat of red oxide to achive smooth finish including writing of SM/MES No complete all as directed.
47Testing and re-setting and checking connection of control cable from transformer tap changer to panel of auto tap changer relay up to 5 MVA transformer through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Tap changer panel l/breakers and tranformer control panel complete for its proper functioning complete all as specified and directed.
48M&L for maintenance servicing ,Calibration of existing APFC panel with and including repair/replacement of unsv of capacitor with existing size complete upto 500KVAR APFC Panel all as directed.
49Supply and fix in repairs of Alarm annucator 12 window of model MBAS-0600 suitable for 33/11KV HT breaker complete all specified and directed.
50Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paint complete all as specified and directed.
51All as per Item No: 45 above but four/Six pole structureMake of Paint for item No.45 & 46 : Asian/Nerolac/Berger.
52Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable for spreading the stone aggregate including disposing all the waste to a distance not exc 50M form the site all as directed by the Engr-in-Charge.
53S&F digital type Ammeter suitable for Eleven KV breaker ranging (0-400) Amps suitable for auxilary voltage 230 volts including taking down old unserviceable Ammeter complete all as directed.Make- MECCO/CONZERV
54M&L for spreading the 40mm coarse aggregate in various sub stations/Structure premises and other locations complete all as directed.
55Cutting of trees and tree branches of girth up to 20cm and to a radius of 3M all around LT/HT OH line complete all as directed. Note: The distance between two adjacent poles will be considered as one span
56M&L 11KV grade pin type, composite polymeric/ insulator insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer including all galvanised steel fittings as required at site and removing of unserviceable insulators complete all as specified and directed. Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board.
57M&L in replacement horn gap fuse assembly mounted on porcelan insulator and steel frame, D or Channel type for HT 11 KV, 400Amps rated current including base frame made with 'C' channel cross arms of suitable size shall be including removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set.
58M&L in replacement of Lightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set.
59Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating parts etc after cleaning, removing carbon deposits including testing and commissioning the same for operation complete all as directed by Engr-in-charge. Note: The repairs to three poles of AB switch will be measured as on job.
60M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm (upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., complete all as specified and testing on completion.
61S&F rust free Acrylic Danger notice plate duly marked voltage danger and conventional skull and bones in signal red colour written in one local language and english with retro reflective stickering and fixing with GI/MS. clamps, bolts and nuts of approved size, for LT 440volts all as specified.
62All as per item no 56 above but for HT 11000 volts.
63M&L for fixing the Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
64Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge.
65Supply only Male contacts suitable for 33/11 KV Air Break switch complete all as directed.
66Supply only Female contacts suitable for 33/11 KV Air Break switch complete all as directed.
67Material and Labour for cutting existing BT road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bags and removing debris to a distance not less than 50m complete all as specified and directed.
68Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at bith ends after laying the cables including taking out old GI tubing complete all as directed.
69All as per iem No 63 here-in-before but 80mm dia
70S&F in repairs MCCB 200 Amps, 4 pole 50 HZ, , complete all as directed.
71S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, complete all as directed.
72S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, complete all as directed.
73S&F in repairs MCCB 400 Amps, FP, 50HZ, complete all as directed. Please Enable Macros to View BoQ information
74S&F in repairs MCCB 400 Amps, FP, 50HZ, complete all as directed. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58361788
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 45 Lakhs
LAST DATE 24-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repairs/Maintenance Of Ht/Lt Oh Lines, Ug Cables And Lt Switch Gears Installed, Transformers At Dmrl/Atc & Rcma (Mat) Hospital Area Kanchanbagh, Hyderabad.
Basic Detail
Tender No 8327
Bidding Type Tender
Location
City Hyderabad
State Telangana
Key Dates
Publish Date 03 Nov 2026
Submission Date 24 Nov 2026
Open Date 26 Nov 2026
Finance
Tender Value 45 Lakhs
Tender Fee 500
EMD 90000
Exemption Available
Document List
7daeca03-de89-408e-930a-047ae0cd249d.html
BOQ_894058.xls
Tenderdocument.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 03, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 1 day
Nov 26, 2026

Bid Opening Date

Technical bids will be opened and evaluated.