Defence Statutory Bodies & Commissions/Committees Closing in 11 days TDR #58361757

Tender For Repair/Maint Of Central Ac Plant, Cooling Appliances And Repair/Replacement Of Faulty Unsv Ug Cables, Various Type Of Light Fittings, Switch Gear Systems With Connected External Electrification Works At Dgqa Area And Repair/Maint Of Coolin

Issued by Statutory Bodies & Commissions/Committees · New Delhi, Delhi
Tender Value
35 Lakhs
Estimated cost
Bid Submission
24 Nov 2026
11 days left
EMD
70000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
New Delhi → Delhi
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for Repair/Maint Of Central Ac Plant, Cooling Appliances And Repair/Replacement Of Faulty Unsv Ug Cables, Various Type Of Light Fittings, Switch Gear Systems With Connected External Electrification Works At Dgqa Area And Repair/Maint Of Cooling Appliances With Connected Misc Items At Anand Parbat Mil Stn Under Ge (North) Delhi Cantt-10.

BOQ

Name of Work:- REPAIR/MAINT OF CENTRAL AC PLANT, COOLING APPLIANCES AND REPAIR/REPLACEMENT OF FAULTY UNSV UG CABLES, VARIOUS TYPE OF LIGHT FITTINGS, SWITCH GEAR SYSTEMS WITH CONNECTED EXTERNAL ELECTRIFICATION WORKS AT DGQA AREA AND REPAIR/MAINT OF COOLING APPLIANCES WITH CONNECTED MISC ITEMS AT ANAND PARBAT MIL STN UNDER GE (NORTH) DELHI CANTT-10.
Sl. No. Item Description
1M&L for disconnecting electrical connections of motor located at the top of cooling tower,keep cables at safe custody for reconnection and dismantling and taking out fan blade assembly along with motor mounted on base frame at the top of cooling tower after cutting/dismentaling all nuts, bolts and fixtures from the mounting frameand removing whole assembly including motor and base frame from the top of cooling tower with the help of T&P for servicing of cooling tower suitable for 225 TR capacity including following complete :-(i) Cleaning the cooling tower by applying wire brush, washing powder and other solvent by removing the deposited impurities sush as silt, dust particles mud/ sand inside the dume and around the fins, cleaning of base tray and grills, pot stainer. (ii) servicing cooling tower plant through cleaning re-agent complete pipe line,including servicing of cooling tower motor and fan and make the necessary alignment with motor. (iii) Replacement of bearing if any of suitable cap if any after necessory work including gressing and replacement of nut bolts and preventing leakage if any by means of suitable adetives etc all as directed andspecified. (iv) Taking out PVC fills blocks, cleaning , refixing and replacing if unserviceable as per existing location and channel direction. (v) Servicing of spray header and sprinkler assy complete. (vi) Cleaning of water strainer complete.
2Supply and fixing PVC Fills in colums of size 60 x 30 x 15 cm or next higher size, honey comb/LPS pvc fills with tie rod and turn buckle of suitable size to match the system as per existing specification and requirement complete all as directed.
3S& F in replacment of Float valve (brass) 25MM Ball brass valves, high pressure, with polythene float and flynut complete, screwed for iron pipe or brass ferrule and fixedcomplete all as directed.
4Taking out the existing unserviceable sprinkler of cooling tower and supply, installation, testing and commissioning of new sprinkler assembly complete with header nozzle made out of galvanised iron for cooling tower size of 225 TR (as required on existing site) as specified and as directed by Engr-in-Charge. Make- DELTA/ MIHIR/ UNIVERSAL.
5S&F in replacement of refrigeration filter dryer fixed in Liquid line suitable for R- 134a refrigerant ,water cooled chiller complete all as specified and directed.
6Supply and fix in replacement Safety valve thread as per existing size ,water cooled central type AC plant for 180TR Capacity as per sample complete all as directed.
7M&L for bailing out the water from the PVC water tanks of capacity 5000 ltr with out causing any interruption to regular water supply system and cleaning the same inside of tank thoroughly by using wire brush/scrapper for removal of deposited scales/sludge/silt etc and removing the materials out of site cleaning thoroughly with water and bleaching powder and then by chlorine solution for complete anti bacterial disinfections including writing date of cleaning on the black board with white paint all as specified and directed. (Note:- 1.Rates quoted deemed to be inclusive of T&P and safety equipments required at site 2. Water tank shall be cleaned every 3 month of interval)
8Material and labour for de-scaling and complete servicing of condenser units for central type water cooled AC plants for 180 TR capacities by means of adding descaling chemical solution (HCL) into the cooling tower sump as per requirements, and running the plant pump continuously till all the scale of pipes/ shell are removed including removing side covers of condenser and cleaning the water tubes by means of nylon brushes till the scaling is removed and re-fixing of covers including replacement of neoprene rubber gasket and refixing pipe connection etc., complete all as specified and as directed by Engr-in-charge.
9Material and labour for of machine and filling up R -134a refrigerant for suitable to existing compressor in HVAC water cooled central AC plants complete all as specified and as directed by Engr-in-charge.
10Material and Labour for dismantling of existing Air Handling Unit of 4000 to 14800 CFM capacity , cleaning, servicing, overhauling all component of AHU, with and including cleaning of heating & cooling coil with caustic soda solution, including welding / brazing, wherever required to arrest leakages, cleaning of Pre-Micro Filters, replacing of vertical GI sheet supports, replacement of U/S foam insulation of best quality using adhesive substance to avoid cold air leakages, fabrication of bottom GI tray of existing size with drain pan made out of 16 guage thick GI Sheets duly painted over interior surface of tray, re-assembling all the dismantled components to its original position using new nut, bolt, washer and other packing material etc, with and including testing, commissioning of Air handling Unit at optimum efficiency, complete all as specified and directed by Engineer-in Charge.
11Material and Labour for opening of existing Hot water Generator of 285KW capacity for cleaning, servicing, overhauling all component of Hot water Generator, with and including cleaning of heating element coil with descaler solution, and using non metallic scouring pad/soft nylon brush, re-assembling all the dismantled components to its original position using new nut, bolt, washer and other packing material etc, with and including testing, commissioning of HWG Unit at optimum efficiency, complete all as specified and directed by Engineer-in Charge.
12S&F for replacement of strip/coil heating element of capacity 25 KW, complete all as specified and directed.
13Supply and fix in repair power contactor of AC3 rating, 03 pole, with 1NO+1NC , 415V , type MO25, 25 A including making all electric connection, complete all as directed.
14Material and Labour for dismantling of blower shaft of AHU of 4000 to 14800 CFM capacity upto 15 HP , induction motors , by removing the belt and pulley, blower drum, and remetaling the shaft and filling of metal at decayed portions including all welding, turning, polishing and other machine works required to make the shaft of required shape and size, as original, balancing the shaft and refitting in AHU including re-assembling the blower, pulley etc with and including replacement of new bearing of existing size, testing the AHU for satisfactory operation, complete all as specified and directed by Engineer-in Charge.
15M&L for servicing of Pre-filters / bag type filters /Hepa filters fixed in AHUs located in differents locations with ideal pressure through pressure pump , water mixed with antirust chemical solution , sizes 610x610x50mm , 305x610x25mm ,305x305x25mm,610x450x25mm, 310x550x25, 610x305x25 , filters drag out smoothly from AHU's channel (floor mounted /ceiling fixed) and wash /clean , dry out properly and re-fixed at their previous location without damage all as specified and directed by Engr-in-Charge .
16Supply and fix in replacement Pre - filter box type- 102/16 (Size 610 x 305 x 50 mm) (MERV-10)complete all as specified and as directed by Engr-in-charge.
17Supply and fix in replacement Pre - filter box type- 102/16 (Size 610 x 450 x 25 mm) as suitable for existing on site complete all as specified and as directed by Engr-in-charge.
18Supply and fix in replacement Pre - filter box type- 102/16 (Size 305 x 305 x 25 mm) as suitable for existing on site complete all as specified and as directed by Engr-in-charge.
19Material and labour for rewinding of, 3 phase, 50 Hz, 415 volt of CTs fan motor, Chiiler motor and condenser motor , comprising of the following activities for induction motor of following capacities complete all as specified and as directed by Engr-in-charge.(i) Disconnecting and removing the electric motor from installed position and loading, unloading, transporting to authorised /approved work shop.(ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc., complete for class 'F' insulation and including shaft metalising, bearing cover slieving, necessary replacement of cooling fan, nuts and bolts etc.,(iii) Loading, unloading and transporting motor and reinstalling in position and in alignment including electric connection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-charge all as specified and directed .
20(a) Induction Motor of Capacity 5/5.5 HP
21(b) Induction Motor of Capacity 7.5 HP
22Material and labour for repair of condenser motor and pump / chiller motor and pump any type including replacement of impeller and bearings both sides, mech seals , polishing , grinding of the pump up to 7.5 HP capacity complete all as specified and as directed by Engr-in-charge.
23M& L for surface excavation at E/M installations and store yards not exceeding 30 cm deep and averaging 15 cm deep and getting out soft / loose soil removing shrubs, small trees height up to 1.0 Mtrs , removing the grass from route and spray chemical for prevention of growth of weed and grass at surrounding of ACs plant area with spray gun as per the manufacturer instruction complete.(Make : GLYCEL 41% SL or equivallent as approved by Engr-in-Charge) all as specied and directed. Note : (i) Rate includes removing all waste material and grass not excceding 50 Mtrs distance from installation ,depositing where directed at a level not exceeding 1.5 Mtrs above the starting point and cleaning of yard , Complete all as specified and directed by EIC. (ii) Cleaning should repeat in same installation in every three months
24S&F in repair heavy duty M.S. ERW pipe 80 mm dia including all fittings laid in trench/duct for chilled water pipe line of central AC plant with cutting ,welding ,bending complete all as specified and directed.
25S&F in repair insulation of M.S. pipeline 80 mm dia with PUF slab 40 mm thick with and including applying bituminuous compound and GI sheet cladding with 26 gauge sheet complete to avoid heat dissipation of chilled water pipe line of central AC plant complete all as specified and directed.
26Cleaning of existing duct through high power vaccum cleaner ,high pressure compressor air using special nozzle,brush ,scrubblers,imported' hepa aire' equipment & technology complete all as specified and directed
27Material & Labour for Painting to condensor motor , Condensor Water Pump , AHU motor and Cooling Tower-03Nos and vice versa as per existing colors code with all supporting materials with one coat of synthetic enamel paint from ground level to bottom of the dome complete all as specified and directed (DGQA 3X180 TR)Note :- Special type of tools & tackles, swings, scaffolding and safety accessories etc required for the work shall be arranged by the contractor and rate quoted shall deemed to include for the same.
28Material & Labour for Painting to GI/MS pipe line 150/100/80 mm dia for Condensor Water Pump to Cooling Tower and vice versa as per existing colors code with all supporting materials with one coat of synthetic enamel paint from ground level to bottom of the dome of themake up tank complete all as directed.Note :- Special type of tools & tackles, swings, scaffolding and safety accessories etc required for the work shall be arranged by the contractor and rate quoted shall deemed to be included for the same.
29Supply and fixing of thermal insulation on the sheet metal duct any shape and any size of existing duct wrapped with semi -rigid glass fiber board(standard fiberglass Acoustic/Insulation board) for 50mm thickness with aluminium sheet 0.8 thick (20 gauge) core thikness on ducts cladding and ensure the all safety measure protected aganist all weather condition for ducts installed outside the SQAE Complex complete all as specified and directed.
30M&L for taking down carefully window type,Split type, Caseete type AC of capacity 1.5 Ton/2 Ton of any type/make from window/wall in various locations, removing front grills, air filters and cleaning, removing dust, washing and servicing with chemical wash of cooling and condenser coil and re-assembling the dismantled components and fixing to its original position with writing letters mentioning the MES Ser No complete all as specified and directed. (Note: Rates deemed to be included for deep cleaning/jet cleaning with pressure pump and arrest the water leakage from indoor units complete)
31M&L for taking down carefully and shifting of any other location (i.e.AOR) any type of AC units complete unit of capacity 1.5 Ton/2 Ton incl making of required size core cutting hole complete all as specified and directed.
32S&F in replacement of starting capacitor 80 to 100 MFD, 240 volt including making connection incl taking down UNSV complete all as directed.
33S&F in replacement of running capacitor 30 to 60 MFD, 240 volt including making connection incl taking down UNSV complete all as specified and directed .
34S&F in replacement of relays suitable for air conditioner of any type1.5/2 Ton incl taking down UNSV complete all as directed . Makes as per sample
35S&F in repairs for overload protection coil 230 Volts for any type AC 1.5 Ton/2.0 Ton capacity ISI marked complete all as specified and directed.
36S&F in replacement of thermostate switch of temperature range of 18C°to 30 C° ISI marked suitable for window/split air conditioner of any make/type of capacity 1.5 Ton/2 Ton all as directed.
37M&L for fan blower motor copper wound of window type air conditoner 1.5/2 Ton capacity with same rating 220/230 volts incl taking down UNSV complete. Makes as per sample
38S&F for swinging/Oscillation motor with louvers (horizontal and vertical) as per existing make for any type AC 1.5 ton/2.0 ton capacity including taking out old unserviceable swinging motor ISI marked complete all as specified and directed.
39S&F for fan blade for any type AC of any capacity including taking down old unserviceable fan blade all as specified and directed by Engr-in-charge.
40M&L for charging/top up of refrigerant R-22 / R-410A/R 32 or any other as per maufacturer recommended refrigerant gas in 1.5/2 Ton window/split Air conditioner up to required pressure including detecting leakage and rectify the leakage with proper brazing and testing on full load complete all as directed.
41S&F for replacement of PVC air filter for any type AC of 1.5 ton/2.0 ton capacity including taking out old unserviceable air filter ISI marked complete all as specified and directed.
42S&F in repairs suitable capacity/model condensing coil unit copper for any type AC 1.5 Ton/2 Ton capacities, ISI marked, incl taking down UNSV complete all as specified and directed by Engr-in-Charge.
43S&F for replacement of capillary tube and stainer for any type AC of 1.5 ton/2.0 ton capacity incl taking down UNSV complete
44M&L for replacement of copper tubing 1/4\\" / 3/8\\" / 1/2\\" / 5/8\\" dia with existing gauge for suction/discharge line of split type air conditioner of 1.5 Ton/2Ton capacity including high quality puf insulation complete all as specified.
45M&L for replacement of high quality puf insulation of suitabel size of around the copper tubings complete all as specified.
46S&F in repairs for PVC cable tray casing caping type (nor less than to 150 x 50 mm) including bends and other accessories as required to accommodate AC units copper tubings from indoor to out door units complete all as specified and directed.
47M&L for replacement of hermatically sealed reciprocating/rotary type (as per existing) compressor unit complete for split/Window AC 1.5/2Ton with charging of refrigerant incl taking down UNSV complete (Make as per sample)
48S&F in repairs for Printed Circuit Board for control unit for any type and any model of Ac 1.5 ton /2.0 ton capacity as per existing and same make ISI marked complete all as specified and directed.
49S&F in replacement of front grill of window type air condition 1.5/2 Ton any make/type with LCD/LED display panel, incl taking down UNSV complete all as directed.
50S&F in replacement of LCD / LED display unit for split type AC 1.5 / 2.0 ton capacity, incl taking down UNSV complete all as specified and directed.
51Taking out complete unserviceable wiring for AC outdoor/indoor any type 1.0 ton/1.5 ton/2.0 ton capacity and rewiring with suitable size multi stranded copper cable including testing, checking etc complete.
52S&F in repairs for 15/20 mm bore PVC flexible conduit with necessary clamping
53S&F in repairs for split AC indoor unit mounting plate suitable for 1.5/2 ton capacity complete.
54S&F in repairs for liquid/gas shut-off /receiver valve suitable for any type of AC s complete.
55S&F in repairs for split AC out door unit mounting bracket (set of 2) suitable for 1.5/2 ton capacity complete.
56M&L for removing the unserviceable Voltage Stabilizer from position ,open the outer covers , remove the burnt out winding from the transformer , rewind with super enameled copper winding wire ,insulate properly , setting / testing of buck / boost relay , replacement of U/S electronic parts , assemble back & fixing in its original position including testing for proper functioning for capacity of up to 4 KVA 1 ph , 230 V , 50 HZ complete all as specified and directed.
57S&F in repairs for Volt meter single phase up to 250 Volt range
58S&F in repairs for Ammeter single phase upto 40 Amps range.
59S&F in repairs for over load protection relay
60S&F in repairs for PCB for capacity 1 KV to 4 KV
61Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5m depth for laying under ground cable/pipes in loose/soft soil all as specified and directed.
62All as per above item but Hard/dense soil.
63All as per above item but Soft/disintegrated rock.
64Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm all as specified and directed.
65Removal of surplus soil obtained from excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as specified and directed.
66M&L for sand cushioning for protection of cables with screen wash river sand and punning to proper required cover all as specified and directed.
67M&L for bricks of sub class ‘B’ bricks, for cable protection in trenches laid dry and flat all as specified and directed.
68Supplying and laying un-reinforced precast concrete cable cover class HV, Type 1, flat, size 300mmx l80mm x 40mm , as specified and directed
69Supplying, laying, jointing testing and connecting in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked,size of 185 sqmm 3 core suitable for HT 11 KV(E) system, laid in trenches,fixed to pole/wall incl taking down unsv complete all as specified nd directed. Note :- Earth work,cable protection,sand fillings,cable joint shall be measured and paid separately.
70All as per above item but size 120 sqmm 3 core
71All as per above item but size 95 sqmm 3 core
72Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors 10 sqmm 2 core laid in trenches, fixed to pole/wall incl taking down unsv complete any size,type&core complete all as specified and directed. Note:- Earth work,cable protection,sand fillings,cable joint shall be measured and paid separately.
73All as per above item but 16 Sqmm 3.5/4 Core.
74All as per above item but 25 Sqmm 3.5 Core.
75All as per above item but 35 Sqmm 3.5 Core.
76All as per above item but 50 Sqmm 3.5 Core.
77All as per above item but 70 Sqmm 3.5 Core.
78All as per above item but 95 Sqmm 3.5 Core.
79All as per above item but 185 Sqmm 3.5 Core.
80Laying only (Re routing) serviceable any type of cable up to 185 sqmm 2/3/ 3 ½ /4 core size all as specified and directed. (Note:- Excavation, sand, bricks and connected items shell be measured and paid separately).
81Laying only old bricks over the sand cushioning dry and flat for cable protection. (Note:- Bricks obtained from the removing of UNSV cable and re routing cable)
82Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed.Note: (a) Excavation,earth work,cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable cable cover/bricks will be laid in trenches for cable protection. If extra PCC cover/bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (d) Material and labour for emergency maintenance work of HT/LT cable line during breakdown by deploying skilled labour and electricians at faulty site having gang of minimum 4 persons including transportation and other tools and plant required at site for fault rectification.(e) Contractor or his rep shall come to the site of breakdown within two hours of notification of breakdown. In case the contractor or his rep shall not come to the site of breakdown and start attending breakdown within two hours, a penalty of Rs 600 per fault per hour shall be imposed over contractor and shall be deduct from his dues.
83All as per above item but 1100 Volt LT cables
84Taking out faulty underground 1100 Volt LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable bricks will be laid in trenches for cable protection. If extra bricks/PCC cable cover and sand required at site shall be measured and paid separately under respective items of BOQs.(c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
85All as per above item but 11000 Volt HT cables
86S&F, testing and commissioning of air break switch gang operated tripple pole mechanically operated mechanism 400 Amps, switch air break gang operated mounted on 15 Nos insulators and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements, flat iron clamp 50mm x 6mm incl MS channels of suitable size and length for fixing of gang operatimg device incl bolts,nuts and eashers incl jumper connection with copper flexible strip designed jumper incl taking down unsv complete all as specified and directed.
87S&F, testing and commissioning of HT lightening arrester metal oxide type (gap less) for out door use complete with all fittings and fixing arrangements, transmission class discharge capacity 65 kilo amps suitable for 11000 volts including brackets, clamps, nuts, bolts, washers and connecting to earth wire 4mm dia GI with manufacturers test certificate, incl taking down unsv complete all as specified & directed.
88Material and labour for disconnecting faulty/burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work, relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals with suitable size of aluminium cable terminal ends in Panel Boards/Loop boxes for 16 Sqmm 3.5/4 core to 185 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch complete and restore electrical connection complete all as directed.
89Supply, fixing and testing straight through joint heat shrinkable type with jointing kit suitable for cable 50 to 95 sqmm x 3.5 core XLPE insulated armoured heavy duty aluminium conductor 11000 Volts grade incl taking down unsv complete all as directed.
90All as per above item but 120 to 185 sqmm x 3.5 core
91Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 95 to 300 sqmm XLPE armoured aluminium conductor cable incl taking down unsv complete all as specified and directed.
92All as per above item but out door termination complete.
93M & L for two coats of synthetic enamel paint as per existing colour on steel/MS/GI surfaces over a coat of red oxide primer including preparation of surfaces complete all as specified.
94Labour for cutting and removing grass, vegetation bushes etc from surrounding HT installation/LT Panel/Four Pole structure/Sub Stations and removing all rubbish to a distance not exceeding 50 m as directed.
95M&L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique with out disturbing top surface of the road and necessary machine including HDPE pipe of 100 mm dia suitable for 0.6 mpa working pressure complete all as specified and directed. Note : Necessary infrastructure reqd for boring shall be arranged by the Contractor at his own cost.
96M & L for Cutting of road/path for laying of GI tubing and making the good to disturbed road/ path including provision of PCC 1:2:4 type B-1 using 20mm graded stone aggregate thickness 50 mm all as specified and directed.
97M & L for steel tubes, light grade galvanised 100 mm bore laid in trenches/walls and spreading for cable cushioning/protection all as specified and directed incl taking down old unsv complete.
98All as per above item but 80 mm bore complete.
99All as per above item but 50 mm bore complete.
100S & F in replacement of MCCB, 4 pole, 415V AC, fixed type of following capacity:
10163Amps with breaking capacity 16kA
102100 Amps with breaking capacity 16kA
103125Amps with breaking capacity 16kA
104160 Amps with breaking capacity 36kA
105200Amps with breaking capacity 25kA
106250 Amps with breaking capacity 35kA
107400Amps with breaking capacity 36kA
108S & F in replacement of onload changeover switch, four pole, 415V AC,of following capacity;
109200Amps
110250Amps
111M&L for repairs in PVC, sheathed copper cable of 2.5 sqmm, 3 core for street light connection including taking down unserviceable PVC insulated aluminium conductor cable from steel pole /PCC pole /Jn box all as specified and directed.
112S&F in repairs for street light LED luminaries with low wattage with heat resistant thoughened glass and 35 Watt including taking down old unserviceable one all specified and directed.
113All as per above item but 45 Watt complete.
114All as per above item but 60 Watt complete.
115S&F in repairs for large area flood lighting system LED type with heat resistant tempered glass for protection120 Watt including taking down old unserviceable one all specified and directed.
116Supply and fix Sintex SMC (Sheet Molding Compound) Pole Mounted Junction Boxof size 300x200x105mm (In side diamension ) including MCB SP 6 Amps, 4 nos aluminium bus bar of 25mmx3mm thick fixed on porcelain post insulators with hinged cover and locking arrangement fixed to electric pole by means of MS flate iron 25x6mm with bolts and nuts complete.
117S&F in repairs for decorative LED post top fittings 25W Ruby Clear/Coral opal type including with all accessories complete along with after taking down old unserviceable one all specified and directed. (Note: light grade GI pipe and necessary PCC works shall be measured and paid separately under relevant items)
118S&F in repairs for garden/pollard light fitting 10 watts, IP65 rated Inverted Pyramid Tripod type LED Bollard with soft 360 deg light distribution including taking down old fitting, demoliton of brick/PCC work all as specified and directed. (Make :Crompton LBLSN 10 CDL or equivallant in Philips) (Note: Necessary PCC works rate deemed to be included in above item)
119Taking down defective street light fitting/flood lights any wattage, make,model from pole and repair the same including replacement of defective/faulty LED driver and re-fixing the same incl connection complete all as directed
120S&F in repairs for LED type IP 66, bush light with die cast aluminium having with toughened glass 9 W incl fixing arrangements complete all as specified and directed.
121M&L for painting of LT electric pole, steel tubular swaged pole (9 mtr long) of any size, any pattern with one coat of aluminium paint over a coat of red oxide primer in full length of the pole and marking the pole with black and yellow strip (upto to 1.50 mtr length, 1.50 mtr height of PCC coping) alternatively including numbering the pole serially all as directed .
122Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts & washer complete all as specified & directed
123Material & labour for earthing with Galvanised Steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using Galvanised Iron strip of size 25 X 4mm as earthing lead (upto the body of the equipment) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel , wire mesh , RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil , returning , filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 5 of SSR 1991(Part-I) complete all as specified and as directed. Note: On testing after completion if the desired earth resistance is not obtained the earthing will be be redone without any extra cost.
124All as per above item but using copper earth plate electrode 60cmx60cmx2mm thick and copper strip of size 20x3mm complete.
125Supply and fixing earth continuity conductor or main earth lead fixed to wall on batten or recess or chess or buried in ground drawn in conduit/pipe or fixed to the pole or any other situation for loop earthing etc as required 20x3mm copper strip all as specified and directed.
126Supply and fixing earth continuity conductor or main earth lead fixed to wall on batten or recess or chess or buried in ground drawn in conduit/pipe or fixed to the pole or any other situation for loop earthing etc as required 25x4mm GI strip all as specified and directed.
127Material and labour for Providing tripod maintenance free earth pits using Ground enhancing compound of 25 Kg (Min) ,earth electrode of copper rod /copper bonded steel rod of 2 mtr length (min) & 17.2mm dia complete with test links for cable connection/disconnection,inspection chamber,top cover including excavation,refilling etc complete all as specified and directed.
128Supply and fixing of new glow sign board of size 1.5M x50CMx20CM wide made out of MS sheet 16 gauge with front of the board made out of transparent perspex sheet/flex sheet.Three Nos 20 watts led tube light fittings fitted inside the board and three core wire of size 40/0.0076 mm,5 m long with one no 5A,three pin plug top with letter writing (sample of letter writing will be provided by Engineer-in-charge) including point wiring and paint of with two coats of synthetic enamel paint complete all as specified and directed.
129Supply and laying copper cable 1100 volt 4 sqmm single core (double run) unshethed copper conductor,stranded in earth alongwith PVC pipe 20 mm dia and connected with light fittings all as specified and directed including excavation,earth work removal.returning filling all as specified and diorected
130Supply and fixing of High reflective sign board made from hardened aluminium alloy sheet 2 mm thick aluminium pop riveted to frame of size 1300mm x840mm made out of stainless steel square pipe 40mmx40mm of 16 gauge wall thickness,frame fixed to 50mm dia 2.7m long stainless steel pipe.All stainless steel parts polished,sign board sheet reflective on one side with white HIP sheet and overlay film of blue colour with computer cut letter,sign and border all as specified,back side of the sign sheet stove enameled and baked to 120 C to make all weather resistant fixed in position as per manufacturer's instructions complete all as specified and directed including PCC Work Make :- Greens/Greenlite,Sun Eyez,Dark eye.Tata BP Solar,Sinor,Redeen or equivalent as spproved by GE
131Supply, fixing of Notice Board with cloth green Blaize surface including glass shutters of size 1830 mm x 1220mm complete all as specified and directed
132Supply ,fixing of Notice Board pre laminated surface with steel frame size 900mm x 600mm complete with writing letters (Sample of writing letter will be provided by Engineer-in -charge
133Supply ,fixing of display charts (Electric shock treatment,standing order,fire order )making with high class paper materials including laminated all as specified and directed (literature of charts will be provided by Engineer-in - charge)
134Supply and installed First Aid Box Made of Mild steel of size 1feet x .50 feet with locking arrangement complete with following items with expiry date of next 2 to 3 years :- (i)Tab PCM = 15 Nos (ii) Tab Brigen = 15 Nos (iii) Soframycin Solution = 01 Nos (iv) Roller Bandage = 02 Nos (v) Medicated Plaster = 02 Nos (vi) Savlon = 01 Bottle (vii) Tab Digene = 15 Nos (viii) ORS = 05 Packet (ix) Microposs = 01 Nos (x) Cotton = 03 Packet
135Supply and fixing in repair of desert/Air cooler of body size 25\\"x25\\"x32\\", made out of corrosion resistant, 18 SWG GI sheet duly powder coated paint with 500mm sweep copper wound fan motor kit 180 watt with metallic blade, ISI marked, 1400 RPM, 230 volt AC, tank capacity not less than 100 ltr, incl plastic submersible pumps, electronis fan regulator with P/switch, desert cooler to be fitted with 6mm thick plywood to cover the gap as required size at existing window and old unsv desert cooler depositing in E/M Store yard complete all as directed (Make : JK Classic/Decool/Supreme/Kapsun)
136S&F in replacement fan motor kit of steel body desert cooler of flow capacity upto 4000 Cum/Hr complete all as directed (Make :- Khaitan/CG/Bajaj)
137M&L fan blade (PVC type) suitable for desert cooler up to 450mm sweep fan complete all as directed (Make as per sample)
138S&F in repair plastic submersible pump suitable for desert cooler any size complete all as directed (Make : Khaitan/CG/Bajaj
139Supply and fixing 6mm thick plywood sheet (ISI marked) waterproof fixed in window including cutting as desired size for passing air of desert cooler.
140S&F desert cooler pad (set of three) made out of wood wool etc suitable for desert cooler of any size.
141S&F in repair PVC flexible pipe of high density for 15 mm bore for desert cooler of any size complete
142S&F in replacement of voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170V to 250V with out put voltage stabilized at 230V with accuracy of +/- 2.5% and of capacity 2 KVA complete.
143M&L for cooler fan blade (metal body) suitable for 500mm sweep for cooler fan complete all as directed. (Make as per sample)
144M&L for painting of desert coolers with synthetic enamel paint of approved colour, with spraying machine, after cleaning, scrabing, preparation of cooler body with set of blades,inner/outer surface area complete all as specified and directed.
145M&L in replacement of Plug top, 3 pin, 05 amps, 230 volt.
146M&L in replacement of Plug top, 3 pin, 15 amps, 230 volt.
147S&F in replacement desert coolers side panels of size suitable of cooler body size (25\\"x25\\"x32\\") made out of 20 SWG MS sheet with wiremesh frame complete and grill duly painted with two coat synthetic enameled paint over one coat of red oxide inside complete all as directed.
148Rewinding of burnt winding of the cooler fan up to 500 mm dia with matching gauge and turns of superenamelled copper wire leathenic paper, glass sleeves etc including varnishing,heating the windings as per manufacturer design and reassembling the same complete testing all as specified and as directed.
149M&L for taking down carefully storge type water cooler of any type/make, capacity (40/80 ltrs, 60/120 ltrs) incl disconnection of electric/water supply connections from various locations, servicing with washing, removing of dust particles,cleaning of condenser coil by blower,painting the outer body (including replacement of corroded sheet with new one) writing letters mentioning the MES Ser No,checking of complete wiring , tightening of loose wire connections with proper Lugs / clips. renewal of defective wiring and connector terminal , proper setting of the thermostat and other electrical / Refrigerant controls and refixing to its original position, testing for proper functioning / cooling effect complete all as specified and directed.
150M&L for taking down carefully Refrigerator/Deep freezer of any type/make, capacity (165/185/310/320 Ltrs) incl discoonection of electric supply connections from various locations, servicing with washing, removing of dust particles,cleaning of condenser coil by blower,painting the outer body (including replacement of corroded sheet with new one) writing letters mentioning the MES Ser No,checking of complete wiring , tightening of loose wire connections with proper Lugs / clips. renewal of defective wiring and connector terminal , proper setting of the thermostat and other electrical / Refrigerant controls and refixing to its original position, testing for proper functioning / cooling effect complete all as specified and directed.
151S&F in replacement of starting capacitor/running capacitor, suitable range for any type water cooler/freezer including making connection complete all as directed.
152S&F in replacement of relays suitable for water cooler/freezer all as directed .
153S&F in repairs for overload protection coil 230 Volts for any type water cooler/freezer, ISI marked complete all as specified and directed.
154S&F in replacement of thermostate switch of suitable temperature range ISI marked suitable for water cooler/freezer of any make/type complete.
155M&L for charging of refrigerant R-134A or any other recommended refrigerant gas in water cooler/freezer/Refrigerator including detecting leakage and rectify the leakage with proper brazing and testing on full load complete all as directed.
156S&F for replacement of capillary tube and stainer for any type freezer/water cooler of capacity.
157M&L for replacement of hermatically sealed reciprocating/rotary type (as per existing) compressor unit, incl taking down UNSV complete for watercooler/freezer with charging of refrigerant.
158S&F in repairs for Printed Circuit Board for control unit for any type,Model suitable for water cooler/ freezer /Refrigerator as per existing and same make ISI marked, incl taking down UNSV complete all as specified and directed.
159M&L for replacement of fan blower motor copper wound for water cooler/freezer with same rating 220/230 volts,incl taking down UNSV complete.
160S&F for push type water tap made of CP brass suitable for water cooler capacity 80/150 ltrs capacity including taking out old unserviceable tap.
161S&F for 60 cm long PVC connector including taking out old unserviceable PVC connector.
162S&F for CP angular stop cock with wall flange including taking out old unserviceable stop cock.
163S&F for drain tray for water cooler of any capacity including taking out unserviceable drain tray.
164S&F for drain pipe flexible type of existing dia meter for water cooler of any capacity including taking out unserviceable drain pipe. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58361757
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 35 Lakhs
LAST DATE 24-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for Repair/Maint Of Central Ac Plant, Cooling Appliances And Repair/Replacement Of Faulty Unsv Ug Cables, Various Type Of Light Fittings, Switch Gear Systems With Connected External Electrification Works At Dgqa Area And Repair/Maint Of Cooling Appliances With Connected Misc Items At Anand Parbat Mil Stn Under Ge (North) Delhi Cantt-10.
Basic Detail
Tender No GE/NORTH-165/2026-27
Bidding Type Tender
Location
City New Delhi
State Delhi
Key Dates
Publish Date 04 Nov 2026
Submission Date 24 Nov 2026
Open Date 26 Nov 2026
Finance
Tender Value 35 Lakhs
Tender Fee 500
EMD 70000
Exemption Available
Document List
1365a48a-1aae-4db3-aa79-ed8780fd6e61.html
BOQ_894161.xls
Gen165.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 04, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 24, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 11 days
Nov 26, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 13 days