Tender for Special Repair/ Replacement Of Feeder Pillar Boxes, Lt/Ht Equipment, Xlpe Ug Cable And Other External Electric Supply Related At Ge (A) Ahmedabad
BOQ
| Sl. No. | Item Description |
| 1 | Item Rate BoQ BoQ_Ver3.0 Item Rate Normal INR Only INR Select, Excess (+), Less (-) Less (-) Tender Inviting Authority: GE (ARMY) AHMEDABAD NAME OF WORK : SPECIAL REPAIR/ REPLACEMENT OF FEEDER PILLAR BOXES, LT/HT EQUIPMENT, XLPE UG CABLE AND OTHER EXTERNAL ELECTRIC SUPPLY RELATED AT GE (A) AHMEDABAD CONTRACT AGREEMENT: GE (A)/ABD/ OF 2026-2027 Bidder Name : PRICE SCHEDULE(This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only ) NUMBER # TEXT # TEXT # NUMBER # TEXT # NUMBER NUMBER TEXT TEXT # NUMBER # TEXT# TEXT # NUMBER # NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER NUMBER TEXT TEXT NUMBER NUMBER NUMBER # NUMBER # TEXT TEXT NUMBER # NUMBER # DATE NUMBER # NUMBER # TEXT # Sl.No. Description of Item of Work Item Code / Make Quantity Unit Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency BASIC RATE In Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT With Taxes TOTAL AMOUNT (in Words) |
| 2 | Fabrication, supply, installation, testing and commissioning electrical cubical control panel board ( KIOSK TYPE ) Double door, CPRI approved an ISO 9001 factory assembled made out door pedestal type feeder pillar box wheather and vermin proof fabricated of 3.0mm CRCA MS sheet of Suitable size,3 phase 4 wire 415 Volt ac 50 Hz complete duly painted with powder coating complete with locking arrangement, earthing terminals with suitable rating aluminium strips for incoming/outgoing MCCB's including and Mounting measuring instrument such as Volt meter, Ammeter, Selector switchs, CT's -03 Set, Phase indicator lamps with holder , toggle switches and MCBs etc including incoming and outgoing cables connections with suitable cable glands and end termination including grouting of feeder pillar box 60 cm above ground level by providing 105 cm long angle iron size 50x50x6mm welded onall four corner embedded in PCC (1:2:4) using 20mm graded upto 45cm complete all as specified and directed. ( Feeder piller box shall be consisting the following)(a) 4 Nos electrolytic aluminium bus bars high conductivity aluminium alloy proper insulated of 1 ½ times of the incoming capacity with provision of extension and mounting on porcelain support (b) MCCB FP 250 amps, 35 KA, 415 volts, 50Hz (Adjustable type) = 01 No (Incoming)(c) MCCB FP 100 amps, 25KA , 415 volts, 50Hz (Adjustable type) - 06 Nos (Outgoing) (d) Digital Panel mounted Amp meter 96 mm square type complete with selector switch complete with suitable size of CT's - 01 Set(e) Digital Panel mounted Volt meter 96 mm square type complete with selector switch - 01 Nos (f) Insulated Aluminium bus bars of suitable size shall be provided from the main bus bar to the out going MCCBs.(g) RYB indicating lamp, LED type - 01 sets.(h) Cost of PCC for foundation is deemed to be included in quoted rate by the contractor.(i) Drawing shall be approved by GE before placing the order. |
| 3 | Material and labour for servicing, repairing and welding to out door LT Panel / LT Feeder Piller box by (i) Cleaning with blower, (ii) Cleaning with CTC/Petrol (iii) Replacement of damaged copper/aluminium lugs (iv) Replacement of deteriorated copper wiring with existing sizes of cable (v) Cleaning and tightening of MCCB terminals (vi) Replacement and fixing of sheared rubber beadings (vii) Rectifying of loose connections of incoming and outgoing cables (viii) Painting two coat of smoke gray colour over one coat of primer and black paint on base channel after rubing with emery paper and making smooth finishes by using spray machine inclusive of writing SM / MES No / name of feeders etc. (not exceeding of height 5 cm each) (ix) Providing of door locking arrangement with of sliding bolts on panel door (x) Proper welding of Panel door/roof as required (xi) Connecting / cleaning of earth wire /earth strip (x) Two coat of white distemper on foundation. |
| 4 | S&F MCCB Four pole 250 Amp, 36/35kA, 415 V, Fixed Thermal-Magnetic type complete all as specified and directed |
| 5 | All as above item 3.00 but rating FP 200 Amp, 36 kA, 415 volt complete all as specified and directed |
| 6 | All as above item 3.00 but rating FP 160 Amp, 36 kA ,415 volt complete all as specified and directed |
| 7 | All as above item 3.00 but rating FP 125 Amp, 25 kA, 415 volt complete all as specified and directed |
| 8 | All as above item 3.00 but rating FP 100 Amp, 16 kA, 415 volt complete all as specified and directed |
| 9 | All as above item 3.00 but rating FP 63 Amp, 16 kA, 415 volt complete all as specified and directed |
| 10 | All as above item 3.00 but rating TP 100 Amp , 16 kA. 415 volt complete all as specified and directed |
| 11 | S&F MCCB Four pole 630 Amp, 50kA Adjustable Thermal-Magnitc adjustable type complete all as specified and directed |
| 12 | All as above item 10.00 but MCCB Four pole 400 Amp, 36/35kA, Adjustable Thermal-Magnitc adjustable type complete all as specified and directed |
| 13 | Supply and fixing in replacement of following accessories installed in existing panel (Indoor/Outdoor) including making in coming / out going electric connections complete all as specified and directed with suitable size of copper wire:- |
| 14 | Digital Voltmeter of rating 0-500 V , size 96mm square type |
| 15 | Digital Ammeter of rating upto 0-600 Amp, size 96mm square type |
| 16 | Selector switch rotary type as per existing size and Make. |
| 17 | LED Indicator assy with colour red/ yellow/ blue. (Set of 3) |
| 18 | Current transformer (CT) Copper wound ratio 100/5 Amp (Set of 3 Nos). |
| 19 | All as above item 12.05 but ratio 200/5 Amp. (Set of 3 Nos). |
| 20 | Material and labour for replacement of existing old unserviceable alluminium tube terminals (Thimbles) of size 150 sqmm to 300 sqmm complete all as specified and as directed. |
| 21 | All as per Item no-13 above but of size 95 sqmm to 120 sqmm complete all as specified and directed |
| 22 | All as per Item no-13 above but of size 50 sqmm to 70 sqmm complete all as specified and directed |
| 23 | All as per Item no-13 above but of size 35 sqmm complete all as specified and directed |
| 24 | All as per Item no-13 above but of size 25 sqmm complete all as specified and directed |
| 25 | All as per Item no-13 above but of size 6 sqmm to 16 sqmm complete all as specified and directed |
| 26 | Supply and fixing Onload Change over switch of capacity 400 A, 4 Pole, 415 Vols, 50 Hz, with Panel Mounted rotating handle, including dismantling old unserviceable change over switch by disconnection all incoming and outgoing electrical connection from existing indoor LT Panel complete all as specified and directed. |
| 27 | All as per item No- 19 but of capacity 250 A, 4 Pole, 415 Volts complete all as specified and directed |
| 28 | All as per item No- 19 but of capacity 125 A, 4 Pole, 415 Volts complete all as specified and directed |
| 29 | All as per item No- 19 but of capacity 100 A, 4 Pole, 415 Volts complete all as specified and directed |
| 30 | S&F Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed |
| 31 | All as per item No 23 but of size HT, 25x20cm size complete all as specified and directed |
| 32 | M&L in replacement of unserviceable Bus-bar chamber made out of sheet metal enclosure 200 Amps power coated independent for five connections, copper busbar suitable for 200 amps current rating mounted on wall, including disconnecting all incoming and out going electrical connections complete all as specified and directed. Make: : HAvells Cat No. IHBC020006 or equivalent in Legrand/Simens/C&S/ABB |
| 33 | Supply, Installed & fix maintenance free earthing copper bonded steel earth rod of 10 feet long having diameter of 17.2mm with copper bonding thickness of 250 micron with universal clamp made of SS earth enhancing compound shall be of 30kg/pit (resistivity is less than 0.12 Ohm meter).The bove arrangements shall be provided with heavy duty earth poly plastic pit cover of 4000 kg load bearing capacity complete all as specified and directed. |
| 34 | M&L for replacement of unserviceable/ damaged PVC / XLPE insulated ACSR/AAAC single core 11KV of Size 50Sqmm/Dog ACSR for making connection from transformer to DO fuse / GOD of HT pole with suitable size of lugs complete all as specified and directed. |
| 35 | Supply and laying PVC electric cable with insulated Copper conductor (stranded) with inner sheathing of PVC tape and overall PVC sheathed 1100 volts grade, heavy duty, 10 sqmm twin core, weather proof flat/round complete all as specified and directed. |
| 36 | Taking out unserviceable 11 KV (RMU & VCB set combination) (01 Nos RMU as incoming & 04 Nos VCB as out going) of any make, capacity and type (Fixed / Withdrawable) complete with Isolation, withdrawal (for withdrawable type) or de-energising & earthing (for fixed type) of the VCB truck and shifted to authorized/Local work for repair and spliting/dismantling of the breaker pole assembly for visual inspection of vacuum interrupter bottles, insulation, operating rod and contact travel and carried out contact-resistance test across each pole; vacuum-integrity test on each interrupter bottle (HV withstand / lightning-impulse type test surrogate as per OEM procedure and overhaul of spring-charging/operating mechanism (i.e.springs, cams, bearings, linkage, gear-train), lubrication and checking closing/tripping-time measurement including contact-travel, contact-wipe and simultaneity (phase-to-phase closing/opening time difference and do the adjustment as per OEM tolerance limit and repair to leakage vacuum tank complete and filling the SF6 gas upto desired level and then carried out Insulation Resistance test and functional test of all inter-locking between (earth-switch / breaker / door), mimic diagram and indication lamps / flags after that re-assembly, racking-in (withdrawable type) and functional trial operation (local & remote) including return back the RMU & VCB from workshop to MES golf view sub station and connecting all the incoming & outgoing cable propely and testing the same uoto satisfaction of Enge-in-charge complete all as specified and directed.Note :- (i) Necessary Transportation to shift the VCB from site to workshop & back will be in the scope of contractor and demed to be included in quotated Rate.(ii) Spare part required for replacement shall be measured and paid for separately under supply only item in respective item of this schedule. |
| 37 | All as per item No 29 above but only for single 11 KV VCB complete all as specified and directed |
| 38 | Supply only item as follows: - (Component of VCB's & RMU ) |
| 39 | Vacuum Interrupter Bottle, 11kV, 630A (VCB pole unit) complete all as specified and directed |
| 40 | VCB Spring-Charging / Operating Mechanism spares (springs, cams, bearings, linkages) complete all as specified and directed |
| 41 | Trip Coil, DC 24/110/220V complete all as specified and directed |
| 42 | Closing Coil, DC 24/110/220V complete all as specified and directed |
| 43 | Auxiliary Switch / Contact Block (52a/52b) complete all as specified and directed |
| 44 | HRC Fuse any capacity & Amps suitable for 11 KV RMU complete all as specified and directed |
| 45 | Fixed & Moving Contact Assembly, per pole (set of 3 poles) complete all as specified and directed |
| 46 | Epoxy/Insulating Bushing, per pole (RMU/VCB) complete all as specified and directed |
| 47 | RMU Gasket & 'O'-ring Set (SF6/Vacuum type) complete all as specified and directed |
| 48 | Load Break Switch (LBS) Contact & Arc-Chute Spares complete all as specified and directed |
| 49 | SF6 Gas (Top up filling or complete filling in 11 KV RMU to Maintain the Pressure upto 0.3 bar to 0.5 bar as per requirment) |
| 50 | Multifunction Numerical Protection Relay (Handel IDMT Over Current Protection, Earth Fault, Over/Under Voltage protection & Differential, Digital Trip circuit supervision (TCS) 24 volt to 110 volt of any capacity, & Make |
| 51 | Master Trip Relay |
| 52 | Auxiliary Current Transformer (CT), 11kV class |
| 53 | Auxiliary Potential Transformer (PT), 11kV class |
| 54 | Float cum Boost charger (DC Battery Charger Panel) complete |
| 55 | Multicore Control Cable, 2.5 sqmm (for panel wiring) |
| 56 | Anti-Pumping Relay / 94 relay / Control relay for 11 KV VCB |
| 57 | Limit Switch for 11 KV VCB |
| 58 | Hold on catch assembly for 11KV VCB |
| 59 | Motor Rectifier Module (with heatsink & DIN rail mount) for 11KV VCB |
| 60 | Supply only Electrical Contact cleaner / anti rusting spray ( CRC-2-26) |
| 61 | Supply only Electrical Contact industrial grade cleaner spray ( 3M Cleaning Agent SCOTCH 1625/200) |
| 62 | Aluminium Space Heater ( Panel - Anti condensation Heater) of capacity 80 to100 operating voltage 110V AC/DC or 230 Volt for 11 KV VCB |
| 63 | HT Bushing any type for 11 KV, (Interface C (630A-Bolt-on/M16 or any interface) RMU |
| 64 | Spout Bushing 11 KV, (630A/1250A) VCB ( for Incoming / Out going ) |
| 65 | TNC Switch for 11 KV VCB |
| 66 | Annanunciator 6 to 8 window for 11 KV VCB |
| 67 | Emergency stop switch for 11 KV VCB |
| 68 | Hooter for 11 KV VCB |
| 69 | LED/Neon indicator Lamp (R,Y,B) (set of Three) |
| 70 | DC supply control unit / SMPS Unit complete |
| 71 | Sealed Maintenance Free (SMF) Battery of capacity (26 Ah to 42 Ah) and suitable for 24V / 30V /110V DC complete as per site requirement |
| 72 | Terminal protector Boots suitable for 11 KV RMU & VCB |
| 73 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 185 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 74 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 150 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 75 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 120 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 76 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 95 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 77 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 70 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 78 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 50 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 79 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 3.5 core 35 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 80 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 4 core 25 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 81 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 4 core 16 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 82 | Supply, laying and testing of LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of 4 core 10 sq.mm complete all as specified and directed.Note: Earth work ( Excavation, Returning & refilling and removal), cable protection HDPE pipe, GI protection pipe shall be measured and paid for seperately under respective item of Sch 'A'. |
| 83 | Material and labour for Double wall corrugated HDPE pipe, ISI marked of outer dia 50mm, inner dia 38mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts complete all as specified and directed. |
| 84 | All as per Item no-42 above but of size outer dia 77 mm and inner dia 63 mm complete all as specified and directed |
| 85 | All as per Item no-42 above but of size outer dia 120 mm and inner dia 103 mm complete all as specified and directed |
| 86 | Taking down old rusted galvanized iron pipe including supply & Fix galvanized pipe 100 mm bore light grade in trenches / road / nallah or fixed along wall/ pole including mild steel clamps, screws etc, complete all as specified and directed. |
| 87 | All as per Item no-45 above but of size 80 mm complete all as specified and directed |
| 88 | All as per Item no-45 above but of size 40 mm complete all as specified and directed |
| 89 | All as per Item no-45 above but of size 32 mm complete all as specified and directed |
| 90 | Supply, Fix and testing straight through jointing kit suitable for 1100V, 16-50 sqmm x 3.5/4 core LT XLPE cable heat shrinkable joint complete with jointing material & assessories complete all as specified and directed |
| 91 | All as per item no -49 but of size 70 sqmm to 120 sqmm complete all as specified and directed |
| 92 | All as per item no -49 but of size 185 sqmm to 400 sqmm complete all as specified and directed |
| 93 | Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, of size 95 Sqmm 3 core including taking out old unserviceable HT cable complete all as specified and directed. |
| 94 | All as per item No - 52 but of size 120 Sqmm 3 core complete all as specified and directed |
| 95 | Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for laying of cable /pipes and for poles/stay/ struts not exceeding 10 Sqm on plan and getting out, excavated earth, forming bottom surfaces to required level complete all as specified. |
| 96 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick in soft/loose soil complete all as specified and directed. |
| 97 | Removing surplus soil to a distance not exceeding 50 meter and depositing where directed at a level not exc. 1.5 meter above the starting point complete all as specified and directed. |
| 98 | Supply and laying sand river for cushioning with layers of sand 8 cm before lying of cable and 15 cm after lying of cable (total 23 cm) in trenches complete all as specified & directed.(Note: Thickness of 18cm after punning shall be measured for payment ) |
| 99 | Supply and laying unreinforced precast concrete cable cover, class HVP, type- 1 with peak, size 300mmx180mmx40mm laid flat adjacent and abutting to each other across the length of cable laid dry complete all as specified & directed. |
| 100 | Supplying and erecting cast iron cable indicator plate of 150 mm dia 6 mm thick bolted to 40 mm x 40 mm x 4 mm angle iron grouted in PCC 1:3:6 type C1 concrete block of size 150 mm x 150 mm x 300 mm deep including two coats of aluminium paint on metal work over a coat of red oxide primer burried along with route of cable complete all as directed. |
| 101 | Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 11 kv for electrical purpose suitable for electrical shock safety of sizes 2m x 1m. Complete all as specified and directed |
| 102 | Supply and fix in replacement of MCCB / MCB distribution board, Vertical TPN, 4 way, 415 V, 3 phase, AC with MCCB as incomer and MCBs as outgoing in sheet steel powder painted enclosure double door type with minimum IP 43 degree of protection with built in copper bus bar, neutral link and earth link complete including cutting the wall surfaces for flush mounting of DB and making good with cement plaster, putty and paint to match with the existing surface including taking down existing unserviceable MCB DB of any description complete all as specified and directed. Note: MCCB / MCBs shall be measured and paid separately. |
| 103 | Supply and fix MCCB 160A, 16 KA, 4 Pole, 415 V, 50 Hz with fixed thermal magnetic release fixed in Vertical TPN complete all as specified and directed. |
| 104 | S & F in replacement of U/S MCB Four Pole 100 Amp, 415 Volt, 'c' curve including necessary connection complete all as specified and directed. |
| 105 | S & F in replacement of U/S MCB SP 6 to 32 Amp, 415 Volt,'c' curve including necessary connection complete all as specified and directed. |
| 106 | Supply and Fix in replacement of service cable PVC insulated aluminium conductor (stranded) with inner sheathing of PVC tape and overall PVC sheathed 1100 volts grade, heavy duty, 6 sqmm twin core, weather proof flat complete all as specified and directed. |
| 107 | All as per item No 65 above but 4 Sqmm, Twin core complete all as specified and directed |
| 108 | S&F cable jointing kit 11 KV (earthed) grade cable for straight through termination (Heat shrinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120 - 185sqmm complete all as specified and directed. |
| 109 | All as per Item No- 67 above but of size 3 core 95 Sqmm complete all as specified and directed |
| 110 | Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for indoor Terminal with long sleeves (Heat shinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm sqmm complete all as specified and directed. |
| 111 | All as per Item No- 69 above but of size 3 core 95 Sqmm complete all as specified and directed |
| 112 | Supply and fixing of cable jointing kit 11 KV (earthed) grade cable for Out door Termination (heat shrinkable) type joint complete with jointing material and all accessories for 3 core XLPE armoured aluminium conductor cable of size 120Sqmm to 185 Sqmm complete all as specified and directed. |
| 113 | All as per Item No- 71 above but of size 3 core 95 Sqmm complete all as specified and directed |
| 114 | S&F in replacement of unserviceable lightning arrestors with new 11 KV Lightning arrestors explusion type complete with all fittings and necessary connection,transmission class, discharge capcity 65 kilo amps complete all as specified. (Set of three) |
| 115 | M & L in replacement of unserviceable cross arms with new cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including removing of existing any type of conductor a coat of red oxide primer one underand & one finishing coat complete all as specified and directed. |
| 116 | M & L for Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, length of bolt exc 5cm but n exc 10cm long and diameter of neck 10mm complete all as specified and directed. |
| 117 | Supply and fix vertical type air break gang operated Device of capacity 200 Amps, tripple pole, mechanically operated, outdoor type with all fittings, accessories, mounted on and including HT 11 KV porcelain insulators 09 Nos and steel channel frame, GI operating rod 25 mm dia of suitable length worked from ground including locking arrangements, with 7 livers Naval brass lock, complete all as specified and directed. (set of three) |
| 118 | Supply and fix in replacement of drop out fuse unit explusion type for out door air break gang oprated switch single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts, and washer etc. synthetic bounded fuse camng tube complete with line fap suitable for current carry capcity upto 200 Amps complete as secified and directed. (Set of Three) |
| 119 | Supplying, install and errect in true vertical position steel tubular swaged welded pole complete with cast iron/MS base plate 6mm thick and of size 300x300mm, final taper, pole cap, bolts, nuts, washers & screws etc. pole made out of ERW M.S. tubing conforming to IS-2713 part-II type 410 SP-55 (11.0 metre long) including of holes of reqd Nos and size for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embedded in concrete, painting three signal yeliow colour bends at lower portion of exposed pole starting from plinth block , each band of 300mm height at 300mm spacing, painting pole No the black paint by stenciled letters/figures of 8cm height complete all as specified and directed. (Note: (1) Excavation and PCC works will be measured and paid separatly in respected items.(2) Cost of dismantling existing damaged PCC pole is deemed to be included in the quoted rate. |
| 120 | M&L for PCC work type D-2 (1:4:8) with 40mm graded aggregate for foundation to poles / stays / strutus / floor or making basements etc complete all as specified and directed. |
| 121 | M & L for PCC work type B-1(1:2:4) with 20 mm graded aggregate for coping ( new and old damage coping) to poles / strutus etc complete all as specified and directed. |
| 122 | M & L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required using 32x5mm galvanised iron strip complete with fixing arrangement on wall / foundation / passing through protection pipe complete all as specified and directed. |
| 123 | M&L for cleaning away all grass, vegetation, saplings, shrubs, undergrowth, roots and trees up to 50 cm girth from the area surrounding of E/M installations, 4/2 pole structures, transformer, installations, yards, surrounding valve chamers and removing the rubbish upto a distance 50 mtr outside the periphery of the area under clearance and dressing the area etc complete all as specified and directed. |
| 124 | Supply and spreading graded coarse aggregate of size 40 mm at electrical outdoor installation yard 11 KV Substations/ Near Two/Four Pole structures etc including leveling of uneven surface, removing vegetation, grass etc complete all as specified and directed. |
| 125 | M & L for findout fault in HT/Low underground power cable using cable fault Locating Equipment / Machine complete after disconnection of HT/LT cable from both end terminations at sending & receiving ends and pin-pointing of exact fault location on the cable route complete all as specified and directed. |
| 126 | Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for rerouting and finding of the HT/LT cable fault in underground cable and returning filling the same after rectification of the cable fault in any type of soil complete all as specified and directed.Note : 1. New HDPE Pipe of suitable size to be wraped over the cable at repair portion for protection approx 2 Mtr. |
| 127 | M & L for Cutting through existing bituminous road / PCC / floor / approx size width 50cm X 60cm depth along cross section of the road for laying of GI tubing / RCC / HDPE pipe for encasing of UG cable and repairing the road to match with the original finish by PCC 1:3:6 type C-2 using 40mm graded aggrigate complete all as specified and directed. |
| 128 | Material and labour for construction of brick masonary platform in cement mortar 1:4 of size 2400mm x 1800mm x 1200mm for outdoor type transformer having sides finished with brick work with plaster complete with plain cement concrete foundation of 1:5:10 type E2 (using 40mm graded stone aggregate) and plain cement concrete platform at top with 30 cm thick of plain cement concrete 1:5:10 type E2 (using 40mm graded stone aggregate) and 10cm thick of plain cement concrete 1:2:4 type B1 (using 20mm graded stone aggregate) and having brick steps at one side, complete with XPM jali duty welded with angle iron of size 50mm x 50mm x 6mm all around upto 0.6meter, including excavation and earth work in any type soil, returning filling in and removal of surplus soil upto 50 metre complete all as shown on drawing, as specified and as directed. |
| 129 | M&L surface dressing n.exc 150mm deep in soft/loose soil complete all as specified and directed. |
| 130 | M&L Hard core of gauge n.exe.63mm with broken stone boulders, deposited spread and levelled in layers not exe 15 cm thick watered and rolled rammed to a true surfaces complete all as specified and directed. |
| 131 | M&L for 75mm thick cement concrete type D2 1:4:8 (40mm graded stone aggregate) incl necessary form work as in sub base of path complete all as specified and directed. |
| 132 | M & L for sand filling under floors or in foundations including watering and consolidation complete all as specified and directed. |
| 133 | M&L Machine pressed precast conctete interlocking paver block any shape and size confirming to IS 15658-2006 of 80 mm thickness, M-40 Grade with grey cement and pigment, set, jointed complete all as specified and as directed. |
| 134 | Removal of surplus material to a distance exc 250 m but n.exc 500 mtr and deposited where directred at a level not exc 1.50 m above starting point complete all as specified and as directed. |
| 135 | Excavation in post hole for similar holes each n exc 0.50Cum getting out returning filling in and ramming earth around in layers nexc 25 cm watering and removed surplus soil to a distance nexc 50m and making good surface in soft/loose soil complete all as specified and as directed.. |
| 136 | M & L for cement concrete 1:3:6 type C2 using (40mm graded stone aggregate) as in foundation filling mass concrete complete all as specified |
| 137 | S&F mild steel posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire etc; flat iron fillets (for securing wire mesh/welded steel wire fabric etc) including all necessary drilling, bolting or riveting etc, and similar work conforming to Fe-290 Gde E-165 complete all as specified and as directed.. |
| 138 | Supply only chainlink fencing of any size any type/height as per site requirement complete all as specified and directed. |
| 139 | Fixing only chain link fencing including line wires, any mesh size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire. complete all as specified and directed. |
| 140 | M&L for mild steel such as flat iron, round bars fixed independently as fillets for securing chain link fencing including all necessary drilling for bolting etc confirming to Fe 410-0 or Fe310-0 complete all as specified and directed. |
| 141 | S & F of mild steel screw bolt (machine made with hexagonal or square head at one end and screwed the other or screwed both ends each screw and to be fitted with washer and one hexagonal or square nut length of bolt n exc 5cm and dia of shank 5 to 10 cm complete all as specified and directed. |
| 142 | M&L for two coat of synthetic enamel paint over a coat of red oxide priimer on newly untreated surface of steel over 10cm in width or grith not otherwise described complete all as specified and directed. |
| 143 | M&L for feeder pillar bus bar panle outdoor type, double door, both side openable, locking arrangement, kiosk type, powder coated, 3.00mm thick MS sheet water proof hinged, having 4 Nos aluminium bus bar of 400 Amp duly colour coded mounted on porcelain insulator, with provn of 06 Nos outgoings including MCCB 250 Amps, 4 pole, 36 kA,= 01 No, LED indicator (RYB), 08 Nos, holes in bottom for inlet and outlet cable with suitable size of cable gland and mild steel stand for mounting of panel board made of angle iron of size 50 mm X 50 mm X 6 mm, 1.05 metre high (450mm below ground level and 600mm above ground) along with necessary cement concrete for grouting of panel stand and connecting the panel with earthing complete all as specified and directed by Engineer-in-Charge.Note : (a) Feeder pillar box shall be got fabricated from CPRI approved and shall be from approved list of manufaturer only (b) Electric connection between MCCB and Busbar shall be with aluminium strip links duly colour coded.(c) MCCB shall be of Make-Havells/Legrand/ABB/C&S/L&T Total in Figures 0.0 23 INR Zero Only 4.0 Construction of chamber for 100mm sluice plates item5 10.0 Nos Quoted Rate in Figures Select 0.0 0.0 Zero Only Quoted Rate in Words INR Zero Only Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 23, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 5 daysNov 26, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender