Drinking Water Supply and Sanitation Government Departments Closing in 26 days TDR #58352493

Tender For Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Rajapur Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Chitrakoot Under Amrut 2.0 Program

Issued by Government Departments · Chitrakoot, Uttar Pradesh
Tender Value
42.62 Crore
Estimated cost
Bid Submission
30 Nov 2026
26 days left
EMD
42.63 Lakhs
Bank guarantee accepted
Document Fee
23600
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Chitrakoot → Uttar Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Tender for Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Rajapur Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Chitrakoot Under Amrut 2.0 Programme On Turn-Key Basis

BOQ

Name of Work:- Surveying,Soil investigation, Engineering, Design, Supply of all materials, labour, T&P etc. required for completion of following works of Rajapur Nagar Panchayat Re-organisation Water Supply Scheme Dist. Chitrakoot under AMRUT 2.0 Programme on turn-key basis
Sl. No. Item Description
1CIVIL WORKS
2INTAKE WELL
3Detailed hydrological and geological survey, Site Survey, Testing for bearing capacity of soil, Design, obtaining necessary approvals and Construction of INTAKE structure / well (Capacity 17 MLD) Cum Pump House and Approach bridge ,Dewatering arregement, well sinking, Approach Channel Shoring for Coffer Dam including removal of coffer dam. Cost includes all material, Tools & Plants and labour complete for construction of said intake well. Cost includes all necessary river protection works and all necessary arrangements to ensure required raw water intake in all seasons (especially for Dry weather flow) complete in all respect as directed by Engineer –in-charge.
4WATER TREATMENT PLANT
5Detailed Geographical and hydrological Survey, Site investigation, Testing for bearing capacity of soil, Designing, obtaining necessary approvals with Supply of all materials labour ,Tools & plants for Construction of Water Treatment Plant of 8 MLD capacity (Net out-put capacity i.e. excluding overloading,add 20 % overloading i.e 9.6 MLD) water treatment plant with PLC-SCADA based automation with space saver/ compact and efficient modern treatment technology with construction of MCWR 650 KL capacity. The Treatment Plant as per approved hydraulics essentially consists of the units for : Inlet Chamber, Pre-Sedimentation Unit, Settling Tank ,Venturi Flume ,Flash Mixer, Alum Solution, Tank Chemical House, high to ultra highrate clarifiers, Clarifloculator, high rate filtration unit, Rapid Graity Filters Back Wash Tank Air Blower Post Chlorination Inlet, Outlet , Back Wash Gutter , Troughs , Weirs Reuse of Back Wash Water Thickened Sludge Sump & Pump House Filterate Sump & Pump House Clear Water Sump for Backwash,Clear Water Outlet Chamber Sludge Drying Beds. All other required units. Cost includes all necessary Civil , E&M and SCADA works as per approved by competent authority complete in all respect as directed by Engineer –in-charge.
6OVER HEAD TANK
7Design, Supply of all materials, labour, T&P etc required for construction of Intz type RCC Over Head Tank including various works like - soil testing, Ventilator and Water level indicator, Lightening conductor, C.I. D/F Verticle pipes (Inlet Pipe, Outlet Pipe, Overflow Pipe & Washout Pipe), duck foot bend, puddle collers and bell mouths, Sluice valve on inlet, outlet & washout pipe and Valve Chamber, Bye-pass arrangement of OHT, Flooring, Apran & Drain (100 mm thick PCC of 1:2:4 & 100 mm thick RCC of 1:1.5:3), Floor shall be 30 cm above the finished ground level of Campus, Two coat apex painting over one coat primer of approved colour after finishing of RCC surface with grinder, repair of pin holes, unevenness., Railings - G.I. Pipe railing around stair case (both sides), balcony & top dome periphery, S.S ladder from opening of top dome to bottom dome, Stair case (Seperate two column based RCC staircase and 1 m wide balcony with arrangement of M.S Gate and Jali), Food grade epoxy coating of FOSROC / Ciba-Geigy or reputated brand on inside surface area of water container after testing for water tightness, of capacity and staging mentioned as under: For bidding purpose, bearing capacity of soil shall be considered as 8t/sq.m. Working design shall be based on the SBC determind after soil investigation / 8 tonne/sqm whichever is less complete in all respect as directed by Engineer –in-charge.Note :- The bid price of Over Head Tanks is to be submitted considering net safe allowablebearing capacity as 8 t/m2, keeping the minimum foundation depth to be 2.5 m below existing ground level at the site of work.The successful bidder will be required to investigate the soil bearing capacity. If net safe allowable bearing capacity is found to be equivalent or more than 8 t/m2, the design of OHT will be based on 8 t/m2 capacity. However, in case the net safe allowable bearing capacity is found to be below 8 t/m2, then the design of OHT will be based on the actual bearing capacity.To accommodate for the additional cost required, in the eventuality of net safe allowable bearing capacity falling below 8 t/m2, the payment shall be made as extra item of work.
8OHT of 1200 KL Capacity, 24 m staging (Zone 2) Inlet 250mm, Outlet 350mm, Over flow 250mm, Washout 100mm
9OHT of 1100 KL Capacity, 24 m staging (Zone 3) Inlet 200mm, Outlet 250mm, Over flow 200mm, Washout 100mm
10Repairing and maintenance of Existing 1200 KL/18M Staging OHT including work of Sepage free, painting with water titeness testing & commissioning, restoration of railing with railing post, re-fixing of water level indicator and lightning conductor all etc. complete in all respect as directed by Engineer –in-charge.
11COMMON CLEAR WATER RESERVOIR CUM PUMP HOUSE
12Design, supply of all material, labour, T&P etc. required for construction of Circular, R.C.C Clear Water Reservoir cum pump house including various works like soil testing, 1 m wide stair case with stainless steel hand railing to go inside reservoir, sump below the pump house area, stainless steel railing over the R.C.C slab of reservoir, Granular texture finish on exterior surface of pump house, gantry beam, food grade epoxy coating of FOSROC / Ciba-Geigy or reputated brand on inside surface area of water container after testing for water tightness, of capacity complete in all respect as directed by Engineer –in-charge.Note : The bid prices of Clear Water Reservoir / Pumping Stations are to be submitted considering the depth of excavation may extend up to 6 m BGL.
13900 KL Capacity.
14Construction of Master Control Room as per type design (Size - 8.0m x 5.0m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
15Construction of HT panel Room as per type design (Size - 5.0m x 4.5m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
16Construction of LT panel Room as per type design (Size - 5.0m x 4.5m x 4.0m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
17Construction of Meter Room as per type design (Size - 4.0m x 3m x 3m) including supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in- charge.
18Supply of ISI mark DI K-9 and K-7 S&S pipes (push on joints) of following class and Rubber gasket of EPDM Quality and including Supply of D.I. S/S or flanged Specials conforming to I.S. 8329/2000 Suitable for above D.I. S/S F.O.R. destination and all statutary duties and taxes, third party inspection charges, transit insurance, freight, transportation to store/ site of work, unloading, stacking etc. complete as directed by Engineer –in-charge.
19D.I. Pipe Class-K9
20400mm dia
21250mm dia
22D.I. Pipe Class-K7
23200mm dia
24250mm dia
25300mm dia
26350mm dia
27Supply of High Density Polyethelene Pipes (HDPE (PN-6)/PE-100), conforming to IS 4984 / 14151 / 12786 / 13488 in coils/ standard lengths and inluding Supply of HDPE Specials & jointing material like electro-fusion coupler, flanged joint, conforming to I.S.- 4984/2016 with solvent cement suitable for above HDPE pipe F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation chaloading & stacking the same etc. complete as directed by Engineer –in-charge.
28160 mm dia HDPE Pipe PN-6
29140 mm dia HDPE Pipe PN-6
30110 mm dia HDPE Pipe PN-6
3190 mm dia HDPE Pipe PN-6
32Excavation for pipe line in ordinary soil (loam, clay, sand) with lift up to 1.5 m and lead up to 50 m and including filling back, watering and ramming of excavated earth into the trenches and removal and disposal of surplus earth within 50 meters.(Dia+0.5)
33In ordinary soil
340 - 1.5
35Carting, lowering, laying and jointing with SBR ruber gaskets D.I. K-7/ D.I. K-9 pipes of following dia & pressure including all specials, to site of work, lowering them into trenches, laying true to alignment and gradient, in proper position, cutting of pipes, making of joints including cost of jointing materials and rubber rings, labour, T&P, including hydraulic testing etc. complete as directed by Engineer in-charge. It includes provision for making of alignment on city roads, making trial pits to investigate location of various under grounds services like telephone cables, electric cable, existing pipe lines and sewer lines etc. arrangements for diversion of traffic and associated works etc. with supply of all necessary equipment, materials, labour and T&P etc. complete required for completion of work. The trenches shall be properly barricaded and fenced off wherever necessary. Red flags and caution boards during day and red lights during night shall be displayed so as to avoid any accidents and updating survey of laid pipe on Gati Shakti Portal and or directed by Engineer-in-Charge.Note : Only SBR Rubber gaskets to be used as per IS-5382 and IS- 12820.
36D.I. Pipe Class-K9
37250mm dia
38400mm dia
39D.I. Pipe Class-K7
40200mm dia
41250mm dia
42300mm dia
43350mm dia
44Lowering, laying and jointing of HDPE pipe in proper position using electrofusion specials including supply of all Electrofusion specials & hydraulic testing as per relevent IS Code complete with all accessories like Electrofusion machine, power arrangements, hydraulic testing arrangements, labours, material etc. complete and updating survey of laid pipe on Gati Shakti Portal and or directed by Engineer-in-Charge.
45160 mm dia HDPE Pipe PN-6
46140 mm dia HDPE Pipe PN-6
47110 mm dia HDPE Pipe PN-6
4890 mm dia HDPE Pipe PN-6
49Supply of following types of C.I. valves confirming to the I.S. specification inclusive cost of jointing materials (Rubber gasket of EPDM Quality) including all statutary duties and taxes, third party inspection charges, transit insurance, freight, transportation to store/ site of work, unloading, stacking etc. complete as directed by Engineer –in-charge.
50400 mm dia
51350 mm dia
52300 mm dia
53250 mm dia
54200 mm dia
55150 mm dia
56100 mm dia
57Carting of CI Sluice valves of Following sizes to the site of works Lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete
58400 mm dia
59350 mm dia
60300 mm dia
61250 mm dia
62200 mm dia
63150 mm dia
64100 mm dia
65Supply of all materials, labour, T & P etc. required and construct thrust blocks at the bends and below the Valves.
66Supply of the following sizes of C.I. Double flanged scour valves as per I.S. 780 class-1 working pressure 10 kg/Sqcm F.O.R Destination including all taxes and insurance.complete in all respect as directed by Engineer –in-charge.
6780 mm dia
68Carting of scour valves to the site of works lowering them into already Prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
6980 mm dia
70Supply of 25 mm dia screwed down type air valve with gun metal seat at site stone including all taxes in all respect as directed by Engineer –in-charge.
71Carting of 25 mm dia screwed down air valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
72Supply of underground sluice valves type fire hydrant consisting of 80 mm dia tail pieces, 80 mm dia duck foot band and 63 mm dia standard make iron coupling with cap and chain etc. complete to ISS 909 at site including all taxes in all respect as directed by Engineer –in-charge.
73Carting of 80 mm dia flanges fire hydrant of the site of works lowering them into already prepared trenches and fixing them In position including supply of Jointing materials such as bolt nut, Rubber insertion white lead complete with Excluding values and specials Required but including the testing etc. complete Excluding values and specials required but including the testing etc. complete in all respect as directed by Engineer –in-charge.
74Dismantling of following type of road surfaces for laying of pipe line and house connection work including sorting out of serviceable materials and disposal of unserviceable materials including supply of all materials, labour, T&P etc. required for proper completion of the work.
75B.O.E. ROAD
76BITUMINOUS ROAD
77C.C. ROAD
78INTERLOCKING TILES
79Permanent re-instatement of following type of road surfaces after laying of pipe line including supply of all materials, labour, T&P etc. required for completion of work. It also includes necessary excavation required for preparation of trench for reinstatement of road, disposal of surplus unserviceable material, watering, ramming, cleaning of surface for proper completion of the work as per directions of engineer-in-charge.
80BOE (Brick on Edge) RoadConstruction of BOE road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-Ist class brick shall be used for reinstatement of BOE road. Sand = 25mm thick local sand layer for preparation of surface
81Bitumen road TYPE AConstruction of bitumen road as per UPPWD specification including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-GSB G-1 (One coat) (90-40 mm) = 12.5 cm G -2 (one coat) (45-63 mm) = 7.5 cmG - 3 (one coat) (22.5 - 53 mm) = 7.5 cm BM (One coat) = 7.5 cmSDBC (One coat) = 2.5 cm
82Cement Concrete RoadConstruction of Cement Concrete road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm)CC =100 mm, 1:2:4 (cement, coarse sand & stone ballast of 16-20 mm)
83C.C. Interlocking Tiles Road Type AConstruction of C.C. Interlocking Tile road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm) Sand = 50 mm thick local sand lair for preparation of surfaceNote : 100 mm thick rubber moulded interlocking tile shall be used for construction of interlocking tile road.
84Supply of all materials, labour T&P etc. required and construct surface box/masonry type sluice / scour valve chamber as per type design including supply and materials labour, T&P etc. complete in all respect as directed by Engineer –in-charge.
85Surface box type
86Masonry type
87Supply of all materials, labour T&P Etc. required and construct 350 x 350 x 500 mm size air valve chamber as per type design including supply and fixing the 500 mm dia CI manhole cover complete in all respect as directed by Engineer –in-charge.
88Supply of all materials, labour T&P Etc. required and construct 750 x 450 mm size fire hydrant chamber as per type design including supply and fixing the 500 mm dia CI manhole cover complete in all respect as directed by Engineer –in-charge.
89Provision for crossing of Nalas (0.5m to 2.0 m width) for laying of pipe line including necessary specials, T&P and arrangement of diversion of water, baricatings etc required, with dismantelling of drains and reconstruction of same as per type design of the existing drain complete in all respect as directed by Engineer –in-charge.
900.0 - 3.5 m
913.5 - 7.0 m
923.5 Culvert Crossing
93Providing and making NEW water supply house connection from distribution pipe line of following diameters using 20 mm dia pipe (HDPE pipe (PE 100/ PN 12.5) below ground and medium class GI pipe above ground), saddle (electro-fusion tapping saddle for making connection with HDPE distribution pipeline, DI strap saddle, ferrule, for making connection with distribution pipeline other than HDPE), compression fittings (FTA, MTA etc.), ball valve, specials, including supply of all materials, labour, T&P etc. required for proper completion of the work. It also includes excavation, refilling of pit required for making house connection and updating data on Gati Shakti Portal as per direction Engineer-in-charge.
94for 90 mm - 110 mm dia.
95for 125 mm -160 mm dia.
96for 180 mm -250 mm dia.
97for 300 mm dia.
98for 350mm-500 mm dia.
99Providing and shifting EXISTING water supply house connections from newly laid distribution pipe line of following diameters using 20 mm dia pipe (HDPE pipe (PE 100/ PN 12.5) below ground and medium class GI pipe above ground), saddle (electro-fusion tapping saddle for making connection with HDPE distribution pipeline, DI strap saddle, ferrule, for making connection with distribution pipeline other than HDPE), compression fittings (FTA, MTA etc.), ball valve, specials, including supply of all materials, labour, T&P etc. required for proper completion of the work. It also includes excavation, refilling of pit required for making house connection and updating data on Gati Shakti Portal as per direction Engineer-in-charge.
100for 90 mm - 110 mm dia.
101for 125 mm -160 mm dia.
102for 180 mm -250 mm dia.
103for 300 mm dia.
104for 350mm-500 mm dia.
105Construction of compound wall comprising of RCC Columns @ 3.0m c/c distance with beam at plinth and top, brick work in 1:4 of as per type design including supply of all material, labour, T& P etc complete.
106Supply and fixing 3.60 m wide MS main gate & 1.0 m wide a wicket gate with RCC Columns as per type design & drawing including primer and painting, meterial, labour, T&P etc all complete as per direction Engineer-in-charge.
107Providing and laying in position reinforced cement concrete (mix 1:2:4) for construction of Square drain, size 250 mm x 250 mm, over PCC 1:4:8, including batching, mixing, placing, vibrating, curing, formwork, finishing, including cost of all material and labor, tools and plants required with transportation, steel, loading, unloading, etc., complete for all leads and lifts and as per specifications etc required for proper completion of the work as per direction Engineer-in-charge.
108Construction of following types of Road/ flooring for development of CWR / OHT campus and Provide all materials, labour T&P etc. required for proper completion of work and construct Interlocking Road approach road in water works campous at WTP, Intake well to WTP and Zone 2 & 3 required as per site condition as per direction Engineer-in-charge.
109Aproch C.C. Interlocking Tiles RoadConstruction of C.C. Interlocking Tile road including supply of all materials, labour, T&P etc. required for proper completion of work as per following thickness:-PCC = 100 mm,1:4:8 (cement, coarse sand & stone ballast of 20-40 mm) Sand = 50 mm thick local sand lair for preparation of surfaceTiles = 100% newNote : 100 mm thick rubber moulded interlocking tile shall be used for construction of interlocking tile road.
110Aproch Bitumin Road from main Road to New WTP
111Providing and laying in position reinforced cement concrete (Mix 1:1.5:3) for construction of thurst block at bends of feeder main, rising main & distribution system including batching, mixing, placing, vibrating, curing, formwork, finishing, including cost of all material and labor, tools and plants required with transportation, loading, unloading, etc., complete for all leads andlifts etc required for proper completion of the work.
112Providing H.Y.S.D steel reinforcement for reinforced cement concrete work including straightening, cutting, bending, hooking, placing in position, lapping and/ or welding wherever required, tying with binding wire and anchoring to the adjoining member wherever necessary as per design, including cost of materials and labor complete as per drawings.
113Ist class brick work in 1:6 cement, coarse sand mortar in foundation and plinth in requirement places as per site condition including supply of all material and labour T&P etc required for proper completion of the work as per the directions of Engineer-in-charge.
114Construction of Staff Quarter (RCC framed structure), as per type design and drawing each for pump operators & other staff including structural design and drawing, supply of all materials, labour, T&P etc. required for proper completion of the work as per the directions of Engineer-in-charge.
115Staff Quarter Full Set
116E&M WORK
117PUMPING PLANT AND ACCESSORIES FOR INTAKE WELL
118Supply of Vertical type oil lubricated statically, dynamically, hydraulically balanced turbine pump for raw water at intek well capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump and motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 24 mtr/suitable length column assembly, with vertical solid shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) IE3 suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-
1193230 LPM / 35 Mtr. HEAD / 40 HP MOTOR (2w+1s)
120MAIN PIPING :-Supply of 200mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 250mm common Header upto 1 m. outside the pump house along with 250 x 200 x 250 mm A/F Tee (3 Nos), 250 mm bend (01 Nos), 250 mm blind flange (01 Nos), D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04 Nos) etc. complete in all respect as per site conditions.
121Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
122Actuator with Sluice Valve of size :- 200mm for pumps
123Actuator with Sluice Valve of size :- 250mm for common header
124Non return valve :- DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
125200 mm Dia for pumps
126250 mm Dia for common header
127CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
128Size 250mm for common header
129Supplying of cubicall type LT/ MCC panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half,with all protection relay, i/c providing following switch gears :-(I) Incoming : 2 Nos 320 Amps 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB.(a) Independent manual spring closing mechanism- 1 No.B10(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set.(c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II)Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.
130(III) Interlocking :Interlocking should be provided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(V) Outgoing :-(A) 3 Nos. 125Amp 3 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 (B) 3 Nos.32Amp 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993
131Supply of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
132400Amp Rating
133Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 40 HP / 30 KW
134CE/UL Certified level transmitter for Intake Well :- CE/UL cirtified of Radar type level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
135CE/UL Certified Pressure transmitter for pumps & common header :- CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
136Supply of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 50 KVAR
137ELECTRICAL ITEMS:-
138Supply of 1100 volt grade 120 sq mm 3½ core PVC XLPE insulated Armoured Aluminium cable from transformer to L.T / MCC Panel (2x3½x120 sq mm)
139Supply of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 25 sq.mm from MCC Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
140Control cable 1*10C, 1.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc.(30m. For each) X 3 Nos.pumps
141Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
1423Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
143Rubber mats for electrical purpose as per IS:5424- 1969, plain/chequered (1mX2m) - 10mm thickness
144Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc
145Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
146Installation , Testing and Commissioning of all above equipment Pumping Plants , Piping valves, LT Panel etc complete
147Testing at Manufacturing Works
148Testing of pumps , panels, etc at manufacturer works .
149PAINTING
150Painting of all pumps piping and valves with two coat anti corosive enamel paint.
151Internal & External electrification of pumping station :-
152Indoor Lighting
153Surface Mounting
154Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
155Suspended Mounting / Surface Mounting
156High Power LED Flood Light 100W
157Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
1581200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
159Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
160450mm sweep (900/1400 RPM)
161Outdoor Lighting
162Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system. ( For MCWR )
163Compact Solar LED Street Light- 90W(MONO) 18V / 12.8V 42Ah /60W
164Supply installation tesling & Commissioning of IS0 certiftedcompany made high mast lighting system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 - 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, S.S. ropes (AISI 316, 7 / 19 costruction), EPR insulated PCP sheathed trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation and CC foundation of M - 25 grade complete as required as per IS 456/IS 2911. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal (Octogonal) section, telescopic jointed and welding as per BS 5135 and also provide test certificate for wind tunnel test for High mast fixtures. complete in all respect.
16512.5 Mtr. HM (in 2 Section)
166Providing & Fixing of IK07 IP-66 protected high power LED flood light system with Pressure diecast aluminium housing LM6/ ADC12 material, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps . Integrated driver must be potted & has a unique BIS R number shall be high efficiency having efficiency more than 85 % and in compliance to BIS certified and T.C. certificate. The System level Luminaire efficacy >=120 Im/ wt with High Power LEDs is to be used . LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety . Input Frequency 50Hz‡3%, Power Factor >0.95 ,driver Efficiency >85% . THD(I) <10% , driver current <1000mA shown in LM79 report. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector Must be provided, Surge Protection Min >=4KV internal and 10KV external, System life of 30000 Burning hours with 70% of Initial Lumens maintained, color Rendering Index >70 and CCT 5700K + 1355K, Driver current <1000mA shown in LM79 report. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture -shall be IS 10322 Complianced and also provide test Certificate/ report with liable warranty of product/accessories.
167High Power LED Flood Light 200W
168Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
169160 KVA SUB STATION AT INTAKE WELL
170Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1000Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.
171d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
172Supply of 70 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
173Supplying of 160 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & +7.5% to -15%, having cable end boxes on HV side suitable for 3x70sqmm XLPE cable of 11 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
174Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
175Installation and commissioning of 11 KV/0.4 KV substations including HT control panel with all labor T&P complete in all respect.
176Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
177Supply and making of outdoor cable end termination joint kit for size 70 sq mm 3 core for 11 KV H.T. XLPE cable
178Provision for routine testing of equipments such as transformer, HT Panels at manufacturer’s works.
17919 mm Thickness Electrical resistance sheet (1mx2.0m)
180Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc.
181Fire fighting equipments such as four nos. fire extinguishers CO2 type and fire bucket with stand
182NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
183PUMPING PLANT AND ACCESSORIES AT MCWR
184supply of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical Solid shaft Squirrel cage induction motor (IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump.Capacity as follows :-
1853200 LPM / 20 Mtr. HEAD / 25 HP MOTOR (2w+1s)
186MAIN PIPING :-Supply of 200mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 250mm common Header upto 1 m. outside the pump house along with 250 x 200 x 250 mm A/F Tee (3 Nos), 250 mm bend (01 Nos), 250 mm blind flange (01 Nos), D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04 Nos) etc. complete in all respect as per site conditions.
187Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
188Actuator with Sluice Valve of size :- 200mm for pumps
189Actuator with Sluice Valve of size :- 250mm for common header
190Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
191200 mm Dia for pumps
192250 mm Dia for common header
193CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
194Size 250mm for common header
195Supplying of cubicall type LT / MCC panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, with all protection relay i/c providing following switch gears :-(I) Incoming : 2 Nos 400 Amps 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB.(a) Independent manual spring closing mechanism- 1 No.B10
196(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set (c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II) Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.
197(III) Interlocking :Electrical ly and mechanically through advance contacts interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(IV) Outgoing :- (A) 3 Nos. 100Amp 3 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 (B) 2 Nos.63Amp 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 (C) 2 Nos.32Amp 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993
198Supply of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
199320Amp Rating
200Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection suitable to SCADA operation with RS485 Port rating capacity 25 HP / 22 KW
201CE/UL Certified level transmitter for MCWR :- SITC of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Range- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
202CE/UL Certified Pressure transmitter for pumps & common header :- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
203Supply of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication ofswitching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 75 KVAR
204ELECTRICAL ITEMS:-
205Supply and laying of 650/1100 volt grade 185sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T / MCC panel (2x3½x185 sq mm)
206Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
207Control cable 1*10C, 1.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc.(30m. For each) X 3 Nos.pumps
208Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
2093Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
210Supply &fixing of Rubber mats for electrical purpose as per IS:5424- 1969, plain/chequered (1mX2m) - 10mm thickness
211Cable trench Chequerred plate
212Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
213Installation , Testing and Commissioning of all above equipment Pumping Plants , Piping valves, LT Panel etc complete
214Testing at Manufacturing Works
215Testing of pumps , panels, etc at manufacturer works .
216PAINTING
217Painting of all pumps piping and valves with two coat anti corosive enamel paint.
218Internal & External electrification of pumping station :-
219Indoor Lighting
220Surface Mounting
221Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
222Suspended Mounting / Surface Mounting
22336W LED light fixture 2'×2' with acrylic / prismatic front cover.
224Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
2251200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
226Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
227450mm sweep (900/1400 RPM)
228Outdoor Lighting
229Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system. ( For MCWR )
230Compact Solar LED Street Light- 60W(MONO) 18V / 12.8V 27Ah /40W
231Supply installation tesling & Commissioning of IS0 certiftedcompany made high mast lighting system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 - 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, S.S. ropes (AISI 316, 7 / 19 costruction), EPR insulated PCP sheathed trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation and CC foundation of M - 25 grade complete as required as per IS 456/IS 2911. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal (Octogonal) section, telescopic jointed and welding as per BS 5135 and also provide test certificate for wind tunnel test for High mast fixtures. complete in all respect.
23212.5 Mtr. HM (in 2 Section)
233Providing & Fixing of IK07 IP-66 protected high power LED flood light system with Pressure diecast aluminium housing LM6/ ADC12 material, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps .Integrated driver must be potted & has a unique BIS R number shall be high efficiency having efficiency more than 85 % and in compliance to BIS certified and T.C. certificate. The System level Luminaire efficacy >=120 Im/ wt with High Power LEDs is to be used . LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety . Input Frequency 50Hz‡3%, Power Factor >0.95 ,driver Efficiency >85% .THD(I) <10% , driver current <1000mA shown in LM79 report. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector Must be provided, Surge Protection Min >=4KV internal and 10KV external, System life of 30000 Burning hours with 70% of Initial Lumens maintained, color Rendering Index >70 and CCT 5700K + 1355K, Driver current <1000mA shown in LM79 report. Manufactures Word Mark/Name Engraved/Embossing/Screenprinting on die cast housing to allow traceability/authenticity. Fixture-shall be IS 10322 Complianced and also provide test Certificate/ report with liable warranty of product/accessories.
234High Power LED Flood Light 200W
235Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
236200 KVA SUB STATION AT MCWR ( WTP )
237Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.(d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
238Supply of 70 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
239Supplying of 200 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & +7.5% to -15%, having cable end boxes on HV side suitable for 3x150sqmm XLPE cable of 33 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
240Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
241Installation and commissioning of 11 KV/0.4 KV substations including HT Panels with all labor T&P complete in all respect.
242Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
243Supply and making of outdoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
244Provision for routine testing of equipments such as transformer, HT Panels at manufacturer’s works.
24519 mm Thickness Electrical resistance sheet (1mx2.0m)
246Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc.
247Fire fighting equipments such as four nos. fire extinguishers CO2 type and fire bucket with stand
248NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
249PUMPING PLANT AND ACCESSORIES FOR CCWR TO ZONE-1
250Supply of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220- 260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical Solid shaft Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump.Capacity as follows :-
2511500 LPM / 32 Mtr. HEAD / 20 HP MOTOR (2w+1s)
252MAIN PIPING :-Supply of 150mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 200mm common Header upto 1 m. outside the pump house along with 200 x 150 x 200 mm A/F Tee (3Nos), 200 mm bend (01 Nos), 200 mm blind flange (01 Nos), D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04 Nos) etc. complete in all respect as per site conditions.
253Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP- 67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches withS. S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
254Actuator with Sluice Valve of size :- 150mm for pumps
255Actuator with Sluice Valve of size :- 200mm for common header
256Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
257150 mm Dia for pumps
258200 mm Dia for common header
259CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
260Size 200mm for common header
261Supplying of cubicall type LT / MCC panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half,with all protection relay i/c providing following switch gears :-(I) Incoming : 2 Nos 500 Amps 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB.
262(a) Independent manual spring closing mechanism- 1 No.B10(b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set.(c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set.(d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required.(f) Shunt trip coil 220 V A.C.(II) Bus Bars :TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.
263(III) Interlocking :Electrically and mechanically interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section.(IV) Outgoing :-(A) 9 Nos. 100Amp 3 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 for pumping plant zone -1,2&3. (B) 2 Nos. 80Amp 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 (C) 2 Nos. 63Amp and 2 Nos. 32 Amp 4 Pole MCCB Microprocessor based of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993
264Supply of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)
265500Amp Rating
266Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection suitable to SCADA operation with RS485 Port rating capacity 20 HP / 15 KW for zone -1
267Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection suitable to SCADA operation with RS485 Port rating capacity 30 HP / 22 KW for zone -2
268Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection suitable to SCADA operation with RS485 Port rating capacity 25 HP / 22 KW for zone-3
269CE/UL Certified level transmitter for CCWR :- supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Range- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
270CE/UL Certified Pressure transmitter for pumps & common header :- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
271microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication ofswitching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 100 KVAR
272ELECTRICAL ITEMS:-
273Supply and laying of 650/1100 volt grade 185sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T / MCC panel (1x3½x185 sq mm)
274Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 10 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
275Control cable 1*10C, 1.5 mm2 PVC insulated PVC sheathed copper conductor cable for moisture sensor, level sensor, Reverse protection thermistor relay etc.(30m. For each) X 9 Nos.pumps for zone 1,2&3
276Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
2773Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder
278Supply & fixing of Rubber mats for electrical purpose as per IS:5424- 1969, plain/chequered (1mX2m) - 10mm thickness
279Cable trench Chequerred plate
280Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.
281Installation , Testing and Commissioning of all above equipment Pumping Plants , Piping valves, LT Panel etc complete
282Testing at Manufacturing Works
283Testing of pumps , panels, etc at manufacturer works .
284PAINTING
285Painting of all pumps piping and valves with two coat anti corosive enamel paint.
286Internal & External electrification of pumping station :-
287Indoor Lighting
288Surface Mounting
289Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency > 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD < 10 % , p. f.≥ 0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard
290Suspended Mounting / Surface Mounting
291High Power LED Flood Light 100W
292Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.
2931200 mm Sweep BEE 3 Star rated (service value >=5.0 to< 5.5 )
294Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.
295450mm sweep (900/1400 RPM)
296Outdoor Lighting
297Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of > 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system. ( For MCWR )
298Compact Solar LED Street Light- 90W(MONO) 18V / 12.8V 42Ah /60W
299Supply installation tesling & Commissioning of IS0 certiftedcompany made high mast lighting system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 - 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, S.S. ropes (AISI 316, 7 / 19 costruction), EPR insulated PCP sheathed trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation and CC foundation of M - 25 grade complete as required as per IS 456/IS 2911. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal (Octogonal) section, telescopic jointed and welding as per BS 5135 and also provide test certificate for wind tunnel test for High mast fixtures. complete in all respect.
30012.5 Mtr. HM (in 2 Section)
301Providing & Fixing of IK07 IP-66 protected high power LED flood light system with Pressure diecast aluminium housing LM6/ ADC12 material, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps . Integrated driver must be potted & has a unique BIS R number shall be high efficiency having efficiency more than 85 % and in compliance to BIS certified and T.C. certificate. The System level Luminaire efficacy >=120 Im/ wt with High Power LEDs is to be used . LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety . Input Frequency 50Hz‡3%, Power Factor >0.95 ,driver Efficiency >85% . THD(I) <10% , driver current <1000mA shown in LM79 report. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector Must be provided, Surge Protection Min >=4KV internal and 10KV external, System life of 30000 Burning hours with 70% of Initial Lumens maintained, color Rendering Index >70 and CCT 5700K + 1355K, Driver current <1000mA shown in LM79 report. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture -shall be IS 10322 Complianced and also provide test Certificate/ report with liable warranty of product/accessories.
302High Power LED Flood Light 200W
303Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.
304PUMPING PLANT AND ACCESSORIES FOR CCWR TO OHT ZONE-2
305Supply of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220- 260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical Solid shaft Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump.Capacity as follows :-
3061500 LPM / 49 Mtr. HEAD / 30 HP MOTOR (2w+1s)
307MAIN PIPING :-supply of 150mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 200mm common Header upto 1 m. outside the pump house along with 200 x 150 x 200 mm A/F Tee (3Nos), 200 mm bend (01 Nos), 200 mm blind flange (01 Nos), D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04 Nos) etc. complete in all respect as per site conditions.
308Motor operated actuator with sluice valve :- supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP- 67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches withS. S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
309Actuator with Sluice Valve of size :- 150mm for pumps
310Actuator with Sluice Valve of size :- 200mm for common header
311Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
312150 mm Dia for pumps
313200 mm Dia for common header
314CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
315Size 200mm for common header
316ELECTRICAL ITEMS:-
317Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
318CE/UL Certified level transmitter for CWR :- supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Range- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
319CE/UL Certified Pressure transmitter for pumps & common header :- SITC of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
320Installation , Testing and Commissioning of all above equipment Pumping Plants , Piping valves, etc complete
321Testing at Manufacturing Works
322Testing of pumps ,valves,flowmeter etc at manufacturer works .
323PAINTING
324Painting of all pumps piping and valves with two coat anti corosive enamel paint.
325PUMPING PLANT AND ACCESSORIES FOR CCWR TO Z-3 OHT-3
326Supply of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon < 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220- 260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 06 mtr/suitable length column assembly, with vertical Solid shaft Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump.Capacity as follows :-
3271350 LPM / 49 Mtr. HEAD / 25 HP MOTOR (2w+1s)
328MAIN PIPING :-Supply of 150mm Main piping & valves complete of suitable size and quantity required for delivery side, bye pass arrangement and 200mm common Header upto 1 m. outside the pump house along with 200 x 150 x 200 mm A/F Tee (3Nos), 200 mm bend (01 Nos), 200 mm blind flange (01 Nos), D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe,mechanical joints (04 Nos) etc. complete in all respect as per site conditions.
329Motor operated actuator with sluice valve :- supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP- 67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches withS. S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
330Actuator with Sluice Valve of size :- 150mm for pumps
331Actuator with Sluice Valve of size :- 200mm for common header
332Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .
333150 mm Dia for pumps
334200 mm Dia for common header
335CE/UL Certified Electromagnetic flow meter :- supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
336Size 200mm for common header
337ELECTRICAL ITEMS:-
338Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity >99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)
339CE/UL Certified level transmitter for CWR :- supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Range- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
340CE/UL Certified Pressure transmitter for pumps & common header :- supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
341Installation , Testing and Commissioning of all above equipment Pumping Plants , Piping valves,etc complete
342Testing at Manufacturing Works
343Testing of pumps ,valves,flowmeter etc at manufacturer works .
344PAINTING
345Painting of all pumps piping and valves with two coat anti corosive enamel paint.
346250 KVA SUB STATION AT CCWR FOR ZONE 1.2&3
347Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item)(a) Incoming – ½* No 800Amp. VCB(b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer.(c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters.(d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection.
348(e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection.(a) Outgoing – 2Nos. 800Amp. VCB(b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters.(c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections.(d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection.1. Supply of power pack 24 volts complete with battery and charging device.
349Supplying of 250 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & +7.5% to -15%, having cable end boxes on HV side suitable for 3x70sqmm XLPE cable of 11 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.
350Supply of 70 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.
351Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.
352Installation and commissioning of 11 KV/0.4 KV substations including HT Panels with all labour T&P complete in all respect.
353Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
354Supply and making of outdoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable
355Provision for routine testing of equipments such as transformer, HT Panels at manufacturer’s works.
35619 mm Thickness Electrical resistance sheet (1mx2.0m)
357Cable trench Chequerred plate 6 mm thickness, angle and C Chanel etc.
358Fire fighting equipments such as four nos. fire extinguishers CO2 type and fire bucket with stand
359NOC from Electrical safety department for all field installations such as pumping plants, substation etc.
360Instrumentation and Automation Works
361ESTIMATE FOR INSTRUMENTATION AGAINST ZONE-1 OHT 1,ZONE-2 OHT-2 AND ZONE-3 OHT-3
362Supply of Motor operated actuator with sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater with sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes
363350 mm dia for zone-1 OHT-1
364350 mm dia for zone-2 OHT-2
365350 mm dia for zone-3 OHT-3
366Supply of DI/DF mechanical joint as per requirement and departments approved drawing and specifications, including machining and rubber ring and suitable for 16 kg/cm2 working pressure with required flanges of suitable side with nut and bolt etc. complete. The joint should have long bolts so that during normal working pressure there should be no sliding movement of sliding flanges LOF (length over flange) should not be less than 75% of dia at DMA inlet.
367350mm dia for zone-1,zone-2 &zone-3
368Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement.Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDRange- 0 to …30... mtrsAccuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68
369For zone-1,zone-2 &zone-3
370Supply of CE/UL Certified Electromagnetic flow meter at OHT outlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp:- 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.
371350 mm for zone-1,zone-2 & zone-3
372Supply of CE/UL Certified Pressure transmitter at outlet of OHT :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel includingmounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4\\" LEDAccuracy - +/- 0.1 % of full scale or better Enclosure- IP 68
373For zone-1,zone-2 & zone-3
374Supply of Dosing System outlet of OHT:-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )
375For zone-1,zone-2 & zone-3
376Supply of Residual chlorine analyser / meter outlet of OHT :- Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator andgives 2 outputs one to Local display & other to PLC including Mounting arrangement.Overall Range : 0 - 8 mg/l (ppm)Accuracy : 2% of full scaleSupply Voltage : 230 V acOutput : 4-20 mAMembrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.
377For zone-1,zone-2 & zone-3
37810 KVA 3/1:1 Phase Rack Mountable Easy On_x0002_Line UPS HSN/SAC Code: -85049090 , SMF BATTERIES 12V-18 AH (EP Series) HSN/SAC Code: -85072000 Battery Rack for 20 Nos 12 V-17/18 AH Batteries HSN/SAC Code: -73269099 , interlink Connector for 10 KVA UPS - 240 V DC HSN/SAC Code: -85366990
379For zone-1,zone-2 & zone-3
380Installation of cabling of OHT including all equipments with all power and control cable,testing and commissioning complete in all respect.
381Master Control Station ( MCS )
382CE & BIS approved manufacturer's industrial grade LCD monitor with latest configuration as per specification of size 65\\"
383Desktop/PC as per spec. mentioned
384CE/UL approved manufacturer's 5 KVA UPS with batteries as spec. mentioned for Computer as per requirement
385Full development version of required TAGS SCADA Software with customization of software for MCS as per requirement as per specification mentioned.
386CE & UL approved manufacturer's control room PLC with CPU & power supply at MCS in IP65 enclosure as per spec. mentioned
387CE/UL certified field gateway agent for transfering data from MCS to control room
388GSM based wireless / broadband/Equipment communication system for PLC capable to transfer and gather data from remote sites to control stations, including all accessories complete
389CE/UL approved manufacturer's Firewall for network protection
390Lightning surge protector for ethernet communication protection
391CE/UL approved manufacturer's industrial grade ethernet switch
392Mobile App facility system architecture complete.
393Canon/HP 1018/equivalent Laser printer
394Security Survelliance IP camera
395Installation, testing and commissioning with required furniture,Air Conditioner etc
396Bought out Item :-
397AUTOMATION FOR INTAKE WELL
398CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
399GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
400CE/UL Certified Intelligent energy meters
401CE/UL Certified Surge protector for control panel
402CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
403CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
404Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
405Cable
406(i) Complete cabling upto 3 Pumps
407Security Survelliance IP Camera with recorder (optional)
408Installation, commissioning & testing complete
409AUTOMATION FOR MCWR ( WTP )
410CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
411GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
412CE/UL Certified Intelligent energy meters
413CE/UL Certified Surge protector for control panel
414CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
415CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
416Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
417Turbidity Analyzer at CWR
418PH Analyzer
419Chlorine Analyzer
420Cable
421(i) Complete cabling upto 3 Pumps
422Security Survelliance IP Camera with recorder (optional)
423Installation, commissioning & testing
424AUTOMATION FOR CCWR
425CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
426GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
427CE/UL Certified Intelligent energy meters
428CE/UL Certified Surge protector for control panel
429CE/UL Certified 3 KVA UPS with batteries as per technical bid documents
430CE/UL Certified 10\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
431Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
432Turbidity Analyzer at CWR
433PH Analyzer
434Chlorine Analyzer
435Cable
436(i) Complete cabling upto 3 Pumps
437Security Survelliance IP Camera with recorder (optional)
438Installation, commissioning & testing
439ESTIMATE FOR AUTOMATION OF OHT OF ZONE-1,2 & 3
440CE & UL Certified PLC/RTU in IP 54 enclosure suitable to Communicate with GSM based modem unit with CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.
441GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.
442CE/UL Certified Intelligent energy meters
443CE/UL Certified Surge protector for control panel
444CE/UL Certified 7\\" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.
445Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments
446Cable
447(i) Complete cabling
448Security Survelliance IP Camera with recorder (optional)
449Installation, commissioning & testing
450Trail & Run
4513 Month Trail & Run of Intakewell , WTP, MCWR, CCWR and CWR including operating staff and chemical wtihout electricity charges Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58352493
AUTHORITY Government Departments
TENDER VALUE 42.62 Crore
LAST DATE 30-11-2026
Authority
Authority Name Uttar Pradesh Jal Nigam
Work Description Tender for Surveying,Soil Investigation, Engineering, Design, Supply Of All Materials, Labour, T&P Etc. Required For Completion Of Following Works Of Rajapur Nagar Panchayat Re-Organisation Water Supply Scheme Dist. Chitrakoot Under Amrut 2.0 Programme On Turn-Key Basis
Basic Detail
Tender No 1536/F-03/237 Dated 28/10/2026
Bidding Type Tender
Location
City Chitrakoot
State Uttar Pradesh
Key Dates
Publish Date 03 Nov 2026
Submission Date 30 Nov 2026
Open Date 30 Nov 2026
Finance
Tender Value 42.62 Crore
Tender Fee 23600
EMD 42.63 Lakhs
Exemption Not Available
Document List
61457c8a-7711-4f59-9a4e-e25bb5548226.html
BOQ_2281916.xls
RajapurTD.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Nov 03, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 30, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 26 days
Nov 30, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 26 days

Tender Documents

Download All (ZIP) ↓
html

61457c8a-7711-4f59-9a4e-e25bb5548226.html

xls

BOQ_2281916.xls

pdf

RajapurTD.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender