Tender For Comprehensive Repair/Maintenance Of Water Well, Open Well And Water Filtration Plant Under Age Em No.1 Of Ge (U) Secunderabad.
Tender Value
49 Lakhs
Estimated cost
Bid Submission
24 Nov 2026
2 days left
EMD
98000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Hyderabad → Telangana
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Comprehensive Repair/Maintenance Of Water Well, Open Well And Water Filtration Plant Under Age Em No.1 Of Ge (U) Secunderabad.
BOQ
| Sl. No. | Item Description |
| 1 | Preliminary joint inspection and condition survey of existing open well, including measurement of internal diameter, depth, water level and silt depth; inspection of lining, parapet, pumping equipment, electrical installation and surroundings complete all as specified. |
| 2 | M&L for temporary safety barricading, warning signs, life line, fall-protection and safe access arrangements around the open well for the duration of cleaning and repair works complete. |
| 3 | Dewatering of open well using suitable pump sets, hoses, temporary cables and standby arrangement, including continuous pumping during cleaning/ repair and safe disposal of water complete. |
| 4 | Taking out and subsequently refixing the existing open - well submersible/ centrifugal pump set, suction/ delivery connections and cables as required for cleaning, including safe handling and temporary storage complete. |
| 5 | Removal of deposited silt, sludge, vegetation, loose stones and debris from the bottom of open well by manual/ mechanical means, including lifting to ground level complete. |
| 6 | Loading, transportation and disposal of silt, sludge and debris from open well to an approved disposal location outside the site, including all leads and lifts complete. |
| 7 | High-pressure water-jet cleaning and wire brushing of internal masonry/ concrete surfaces of open well to remove algae, slime, incrustation and loose matter, including final washing complete. |
| 8 | Repair of damaged stone/ brick masonry lining of open well, including removal of loose portions, resetting/ rebuilding with matching masonry in cement mortar, packing cavities and curing complete; measured on treated surface. |
| 9 | Raking out defective joints and pointing internal stone/ brick masonry with cement mortar 1:3, including cleaning and curing complete. |
| 10 | M&L in repair for 15 mm thick cement plaster in cement mortar 1:3 with approved waterproofing compound on repaired internal surfaces, including surface preparation and curing complete. |
| 11 | M&L in repair for applying two coats of approved potable-water-compatible cementitious waterproof coating on prepared internal masonry/ concrete surfaces, including primer and curing complete. |
| 12 | Sealing active seepage/ leakage points by pressure grouting with approved non-shrink cementitious/ chemical grout, including drilling, injection nipples, grout and making good complete. |
| 13 | Comprehensive repair of RCC/ stone coping and parapet around open well, including breaking loose concrete, reinforcement treatment, micro-concrete/ PCC repairs, plastering and finishing complete. |
| 14 | M&L in repair for masonry/ PCC surface drain around open well, including excavation, bed concrete, plastering, grating at crossings and connection to nearest safe disposal point complete. |
| 15 | Repair of 1.80 / 2 m high GI chain-link safety fencing around open well, comprising 50 x 50 mm mesh, minimum 3.15 mm wire, GI/ MS posts, struts, tension wire, foundations and protective coating complete. |
| 16 | Comprehensive repair/ overhauling of existing open-well submersible/ centrifugal pump set up to 10 HP, including motor rewinding where required, bearings, bushes, mechanical seal, impeller repairs, assembly, alignment and workshop testing complete. |
| 17 | S&F in repair of energy-efficient 10 HP, 415 V, three-phase open-well submersible pump set of approved make, suitable for required discharge and total head, complete with manufacturer's test certificate. |
| 18 | Repair/ replacement of 80 mm sluice valve/ non-return valve/ foot valve as required, including companion flanges, gaskets, nuts, bolts and testing complete. |
| 19 | Supply and replacement of 1100 V grade four-core 6 sqmm copper conductor cable of approved make from control panel to pump, including termination, glands, lugs, dressing and testing complete. |
| 20 | Repair and servicing of existing automatic/ DOL/ star-delta pump control panel up to 10 HP, including replacement of defective MCCB/ contactors, overload relay, phase-failure and dry-run protection, meters, indications and internal wiring complete. |
| 21 | Disinfection of open well and connected pumping line using approved bleaching powder/ sodium hypochlorite of prescribed concentration, including dosing, contact period, flushing and safe disposal complete. |
| 22 | Collection and testing of water samples through NABL-accredited laboratory for physical, chemical and bacteriological parameters relevant to drinking water, including sealed sampling and submission of report. |
| 23 | Conducting pumping/ yield and recovery test of open well, recording discharge, drawdown, pumping level and recovery and submitting test report complete. |
| 24 | Supply and fixing of 3 mm UV-stabilised ACP utility-awareness and well-identification sign board, size 600 x 450 mm, with weatherproof printed/ reflective vinyl, fixed on wall/ chain-link fencing complete. |
| 25 | Final integrated testing and commissioning of repaired open-well installation, including checking discharge, pressure, voltage, current, insulation resistance, earth continuity, leakages and automatic protections; submission of report. |
| 26 | Inspection, assessment and performance of the complete MBBR sewage-treatment plant up to 200 KLD including process units, pumps, blowers, filters, dosing system, electrical panel, instruments and treated - water quality; submission of condition - assessment report for repairs. |
| 27 | Isolation, dewatering and comprehensive cleaning of screen chamber, equalization tank, MBBR tank, settling tank, sludge tank and treated-water tank, including temporary pumping, washing and safe working arrangements complete. |
| 28 | Removal, lifting, loading, transportation and approved disposal of accumulated sludge, grit, scum and debris from STP tanks and chambers, including all leads and lifts complete. |
| 29 | Repair of cracks, honeycombs, damaged plaster and minor leakage points in RCC tanks/ chambers using polymer-modified repair mortar and non-shrink grout, including surface preparation and curing complete. |
| 30 | Providing two coats of approved sewage-resistant cementitious/ epoxy protective coating on repaired internal tank surfaces, including primer, surface preparation and curing complete. |
| 31 | Repair and servicing of existing manual bar screen, including removal of corrosion, replacement of damaged SS/ MS bars and supports, alignment, fasteners and protective coating complete. |
| 32 | Supply and fixing of new SS304 manual coarse bar screen with lifting handle and guide arrangement, complete as per existing channel dimensions. |
| 33 | Removal, washing, sieving and recharging of reusable existing MBBR bio-media, including temporary storage, removal of damaged media and cleaning of tank and media-retention arrangement complete. |
| 34 | Supply and filling of virgin polypropylene MBBR bio-media having protected specific surface area suitable for sewage treatment, density close to water and minimum 500 sqm/ cum effective surface area, including transportation and commissioning complete. |
| 35 | Repair/ replacement of SS304 MBBR media-retention screen at inlet/ outlet openings, including frame, supports, fasteners and sealing to prevent media escape complete. |
| 36 | Supply and replacement of fine-bubble EPDM membrane disc/ tube diffusers suitable for sewage aeration, including saddles, connectors, non-return arrangement and testing complete. |
| 37 | Supply and replacement of UPVC/ CPVC air-distribution header and drop piping of required diameter, including valves, unions, bends, supports and solvent-welded joints complete. |
| 38 | Comprehensive overhauling of existing twin/ tri-lobe roots blower up to 7.5 HP, including bearings, oil seals, timing gears, belts, pulleys, air filter, pressure-relief valve, oil, alignment, vibration check and trial run complete. |
| 39 | Repair/ replacement / Supply, installation, testing and commissioning of 7.5 HP twin/ tri-lobe roots blower suitable for continuous STP aeration duty, complete with motor, base frame, belt guard, inlet filter/ silencer, pressure gauge, NRV, relief valve and flexible connection. |
| 40 | Repair/ provision of blower accessories comprising acoustic hood/ guard, vibration-isolation pads, flexible connection, air filter and pressure gauge, complete. |
| 41 | Comprehensive repair/ overhauling of existing sewage-transfer submersible pump up to 5 HP, including motor rewinding where required, bearings, seals, impeller, cable entry, testing and commissioning complete. |
| 42 | Supply, installation, testing and commissioning of 5 HP, three-phase, non-clog sewage submersible pump of approved make, with minimum 50 mm solids passage, guide arrangement, chain and cable complete. |
| 43 | Comprehensive repair of existing sludge-transfer/ recirculation pump up to 3 HP, including motor, bearings, seals, impeller, alignment and testing complete. |
| 44 | S&F in repair of non-clog sludge-transfer pump up to 3 HP of approved make, complete with accessories and cable. |
| 45 | Comprehensive repair of existing filter-feed/ treated-water pump up to 5 HP, including motor repair, bearings, seals, impeller, alignment and testing complete. |
| 46 | S&F in repair of filter-feed/ treated-water centrifugal pump up to 5 HP of approved make, complete with base, coupling, guard and accessories. |
| 47 | Repair of damaged UPVC/ PPR process piping of required diameter, including bends, tees, reducers, flanges, unions, supports, clamps, jointing materials and pressure testing complete. |
| 48 | S&F in Repair/ replacement of butterfly/ sluice/ non-return/ ball valves of required size in sewage, air, sludge and filtered-water lines, including flanges, gaskets, fasteners and testing complete. |
| 49 | Opening, cleaning, descaling and servicing of existing pressure-sand filter vessel, including internal inspection, repair of under-drain/ strainers, replacement of gaskets, valve servicing, painting and pressure testing complete. |
| 50 | Removal and disposal of exhausted filter media and supply/ filling of washed graded pebbles, gravel, filter sand and anthracite in specified layers, including washing and commissioning complete. |
| 51 | Opening, cleaning, descaling and servicing of existing activated-carbon filter vessel, including internal inspection, under-drain/ strainer repairs, gaskets, valve servicing, painting and pressure testing complete. |
| 52 | Removal and disposal of exhausted carbon media and supply/ filling of approved granular activated carbon suitable for tertiary sewage treatment, including support media, washing, painting and commissioning complete. |
| 53 | S&F in repair chlorine dosing system comprising 6 LPH electromagnetic diaphragm dosing pump, 100 litre HDPE solution tank, agitator/ manual mixer, tubing, foot valve and injection valve complete. |
| 54 | Supply, installation and calibration of electromagnetic flow meter of required line size for treated-water outlet, with display, totalizer, flanged connections, earthing rings and signal/ power cable complete. |
| 55 | Comprehensive repair and modification of existing STP MCC/ control panel, including MCCB, contactors, overload relays, phase preventers, control transformer, auto/ manual selectors, indications, meters, timers, interlocks, internal wiring and ventilation complete. |
| 56 | Supply and replacement of damaged 1100 V grade copper power/ control cables of required size, including glands, lugs, supports, dressing, identification and testing complete. |
| 57 | Surface preparation and application of one coat anti-corrosive primer and two finishing coats of approved enamel/ epoxy paint on pipelines, filter vessels, supports and equipment complete. |
| 58 | Repair/ replacement of damaged MS/ SS handrails, gratings, access covers and equipment supports, including fabrication, welding, fasteners and protective coating complete. |
| 59 | Cleaning, disinfection and process seeding/ start-up of repaired STP, including approved bacterial culture/ seed sludge, chemicals, initial dosing and stabilization complete. |
| 60 | Collection and testing of influent and treated-effluent samples through NABL-accredited laboratory for pH, BOD, COD, TSS, oil and grease, faecal coliform and other applicable parameters, including submission of reports. |
| 61 | Operating and performance-stabilization trail of complete MBBR STP by qualified operator for seven days, including daily log sheets, process adjustments, chemical dosing and verification of treated-water parameters complete. |
| 62 | Preparation and submission of updated process flow diagram, single-line diagram, equipment schedule, operating SOP, preventive-maintenance schedule and commissioning dossier for repaired STP. |
| 63 | Supply, fabrication and fixing of utility-awareness sign board, size 600 × 450 mm, made of 3 mm thick UV-stabilised ACP sheet, with weatherproof digitally printed/ retro-reflective vinyl displaying slogans such as \\"Save Water”, “Save Electricity”, utility information, symbols and colour scheme as approved by the Engineer-in-Charge. The board shall be fixed on chain-link fencing or masonry wall using suitable GI clamps, aluminium frame, stainless-steel screws, rawl plugs, washers and all necessary accessories, complete as directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 03, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 24, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 2 daysDec 01, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender