Tender For Procurement Of 0.5 Class Accuracy Electrical Transducers For Generator Tavt Panels, 6.6Kv /11Kv Switchgears (Swgr), And 400Kv / 220Kv Feeders At 1X500mw Unit Sgtps,Mppgcl ,Birsinghpur.
Tender Overview
Project Description
Tender for Procurement Of 0.5 Class Accuracy Electrical Transducers For Generator Tavt Panels, 6.6Kv /11Kv Switchgears (Swgr), And 400Kv / 220Kv Feeders At 1X500mw Unit Sgtps,Mppgcl ,Birsinghpur. , Watt Transducer , Range - 0- 600-1200 Mw ,Input- 0 -165 W Ptr- 400Kv/√3/110V/√3 ,Ctr- 2000-1000- 500/1A, O/P- 4-20Ma Dual O/P At 750Ω,, Sr. No. - 07/06/146185/3 (Complete Details Mentioned Under Tender Schedule) , Range 600-0-600 / 1200-0-1200 Mw Input- (165 - 0 -165) W ,Ptr- 400Kv/√3/110V/√3, Ctr- 2000-1000- 500/1A ,O/P- 4-12-20Ma Dual O/P At 750Ω, Sr. No. - 07/06/146185/61. (Complete Details Mentioned Under Tender Schedule) , Range - 0- 600 Mw ,Input (0- 785.7) W Ptr- 21Kv/√3/110V/√3, Ctr- 20000/5A, O/P- 4-20Ma Dual O/P At 500Ω, Sr. No. - 12/04/132462/10., (Complete Details Mentioned Under Tender Schedule) , Range - 0-25 Mw ,Input- (0- 166.6) W Ptr- 6.6 Kv/110V, Ctr- 2500/1A, O/P- 4-20Ma Dual O/P At 500Ω, Sr. No. - 10/06/147857/8. (Complete Details Mentioned Under Tender Schedule) , Range - 0 - 35 Mw ,Input- (0- 194.4) W Ptr- 6.6 Kv/110V, Ctr- 3000/1A, O/P- 4-20Ma Dual ,O/P At 500Ω, Sr. No. - 10/06/147857/10. (Complete Details Mentioned Under Tender Schedule) , Range - 0-28 Mw , Input- (0- 175) W Ptr- 11 Kv/110V, Ctr- 1600/1 O/P- 4-20Ma Dual O/P At 500Ω, Sr. No. - 10/06/147857/11. (Complete Details Mentioned Under Tender Schedule) , Range - (-)100- 0- (+) 100Mw Input- (-) 55- 0- (+) 55) W Ptr- 400Kv/√3/110V/√3 , Ctr- 2000-1000- 500/1A, O/P- 4-12-20Ma Dual O/P At 750Ω Sr. No. - 09/15/025313/02. (Complete Details Mentioned Under Tender Schedule) , Input - (-166.66-0 + 166.66W) Range- (-100 -0- +100Mw) Ptr- 220Kv/√3/110V/√3, Ctr- 300/1A, O/P - 4-12-20 Ma Dual O/P At 750Ω Sr. No. - 09/15/02351303. (Complete Details Mentioned Under Tender Schedule) , Range - (-600)-0- (+600) Mw Input- (-187.5 -0- +187.5) W Ptr- 220Kv/110V, Ctr- 1600/1 O/P- 4-12-20Ma Dc Dual O/P At 750Ω Sr. No. - 05/06/145223/22. (Complete Details Mentioned Under Tender Schedule) , Voltage Transducer , I/P Voltage- (0-150) V Ac, Range- 0-300 Kvac Ptr- 220Kv/√3/110 V/√3 ,O/P- 4-20Ma Dc Dual O/P At 500Ω Sr. No. - 12/04/132462/17. (Complete Details Mentioned Under Tender Schedule) , I/P Voltage- (0-137.5) V Ac, Range- 0-500 Kvac Ptr - 400Kv/√3/110 V/√3 ,O/P- 4-20Ma Dc Dual O/P At 750Ω Sr. No. - 07/06/146185/10. (Complete Details Mentioned Under Tender Schedule) , I/P Voltage- 0-150V Ac, Range- 0-150 V Ac, Ptr- 220 Kv √3 / 110 V √3 O/P- 4 -20 Ma Dc Dual O/P At 500 Ω Sr. No. - 12/04/132462/7. (Complete Details Mentioned Under Tender Schedule) , I/P Voltage- 0-130.90 V Ac, Range- 0-25K Vac Ptr- 21 Kv √3 / 110 V √3 O/P- 4 -20 Ma Dc Dual O/P At 500Ω special repair No.- 12/04/132462/20. (Complete Details Mentioned Under Tender Schedule) , I/P Voltage- 0-125 V Ac, Range- 0-250K V Ac Ptr - 220Kv √3 / 110 V √3 O/P- 4 -20 Ma Dc Dual O/P At 750Ω Sr. No. - 05/06/145223/5. (Complete Details Mentioned Under Tender Schedule) , Mvar Transducer , Range - 600-0-600 Mvar Input- (-187.5 -0- +187.5) Var Ptr- 220Kv/110V, Ctr- 1600/1A O/P- 4-12-20Ma Dc (Dual O/P) At 750Ω, Sr. No. - 05/06/145223/23 (Complete Details Mentioned Under Tender Schedule) , Range - 50-0-50 Mvar Input- (-83.33) -0- (+83.33) Var Ptr- 220Kv/√3 /110V/√3, Ctr- 300/1A O/P- 4-12-20Ma Dc (Dual O/P) At 750Ω Sr. No. - 09/15/025313/10. (Complete Details Mentioned Under Tender Schedule) , Range - 500-0- 500/1000-0-1000 Mvar Input- (137.5 -0 - 137.5) Var Ptr- 400Kv/√3/110 V/√3 Ctr- 2000-1000- 500/1A, O/P - 4-12-20Ma Dc (Dual O/P) At 750Ω Sr. No. - 07/06/146185/8. (Complete Details Mentioned Under Tender Schedule) , Range - 50-0-50 Mvar Input- 27.50 -0- 27.50 Var Ptr- 400Kv/√3/110V/√3, Ctr- 1000-500 /1A, O/P- 4-12-20Ma Dc (Dual O/P) At 750Ω Sr. No. - 07/06/146185/62. (Complete Details Mentioned Under Tender Schedule) , Range- 600-0-600 Mvar. I/P - (-785.7) -0- (+785.7) Var Ptr- 21√3 Kv/ 110√3V Ctr- 20000/5A Din Rail Mounting O/P- 4-12-20 Ma. Dc (Dual O/P) At 500Ω Sr. No. - 12/04/132462/15. (Complete Details Mentioned Under Tender Schedule) , Power Factor Transducer , I/P Voltage- 0-110 V Ac, 5A Range- (-0.5 Lag) - 1 - (+0.5) Lead Ptr- 21 Kv √3 / 110 V √3 Ctr- 20000/5A Din Rail Mounting O/P- 4-12-20 Ma Dc (Dual O/P) At 500Ω, Sr. No. - 08/15/025450/01. (Complete Details Mentioned Under Tender Schedule) , Frequency Transducer , Input - 0-110V Ac Range- 45-50-55Hz ,Ptr- 400 Kv/110V, O/P- 4-12-20Ma Dc (Dual O/P) At 500Ω Sr. No. - 12/04/132462/4. (Complete Details Mentioned Under Tender Schedule) , Ac Current Transducer , Input - 0-5Amp Ac Range- 0-5 annual periodical maintenance O/P- 4-20 Ma Dc Dual Output At 500Ω , Sr. No. - 12/04/132462/13 (Complete Details Mentioned Under Tender Schedule) .
BOQ
| Sl. No. | Item Description |
| 1 | WATT Transducer |
| 2 | Range - 0- 600-1200 MW ,INPUT- 0 -165 W PTR- 400KV/√3/110V/√3 ,CTR- 2000-1000- 500/1A, O/P- 4-20mA dual O/P at 750Ω,, Sr. No. - 07/06/146185/3 (complete details mentioned under tender schedule) |
| 3 | Range 600-0-600 / 1200-0-1200 MW Input- (165 - 0 -165) W ,PTR- 400KV/√3/110V/√3, CTR- 2000-1000- 500/1A ,O/P- 4-12-20mA dual O/P at 750Ω,Sr. No. - 07/06/146185/61. (complete details mentioned under tender schedule) |
| 4 | Range - 0- 600 MW ,Input (0- 785.7) W PTR- 21KV/√3/110V/√3, CTR- 20000/5A, O/P- 4-20mA dual O/P at 500Ω,Sr. No. - 12/04/132462/10., (complete details mentioned under tender schedule) |
| 5 | Range - 0-25 MW ,Input- (0- 166.6) WPTR- 6.6 KV/110V, CTR- 2500/1A,O/P- 4-20mA dual O/P at 500Ω,Sr. No. - 10/06/147857/8. (complete details mentioned under tender schedule) |
| 6 | Range - 0 - 35 MW ,Input- (0- 194.4) WPTR- 6.6 KV/110V, CTR- 3000/1A,O/P- 4-20mA dual ,O/P at 500Ω,Sr. No. - 10/06/147857/10. (complete details mentioned under tender schedule) |
| 7 | Range - 0-28 MW , Input- (0- 175) WPTR- 11 KV/110V, CTR- 1600/1O/P- 4-20mA dual O/P at 500Ω,Sr. No. - 10/06/147857/11. (complete details mentioned under tender schedule) |
| 8 | Range - (-)100- 0- (+) 100MWInput- (-) 55- 0- (+) 55) W PTR- 400KV/√3/110V/√3 , CTR- 2000-1000- 500/1A,O/P- 4-12-20mA dual O/P at 750ΩSr. No. - 09/15/025313/02. (complete details mentioned under tender schedule) |
| 9 | Input - (-166.66-0 + 166.66W)Range- (-100 -0- +100MW)PTR- 220KV/√3/110V/√3, CTR- 300/1A,O/P - 4-12-20 mA dual O/P at 750ΩSr. No. - 09/15/02351303. (complete details mentioned under tender schedule) |
| 10 | Range - (-600)-0- (+600) MWInput- (-187.5 -0- +187.5) W PTR- 220KV/110V, CTR- 1600/1O/P- 4-12-20mA DC dual O/P at 750ΩSr. No. - 05/06/145223/22. (complete details mentioned under tender schedule) |
| 11 | Voltage Transducer |
| 12 | I/P Voltage- (0-150) V AC, Range- 0-300 KVACPTR- 220KV/√3/110 V/√3 ,O/P- 4-20mA DC dual o/p at 500ΩSr. No. - 12/04/132462/17. (complete details mentioned under tender schedule) |
| 13 | I/P Voltage- (0-137.5) V AC, Range- 0-500 KVACPTR - 400KV/√3/110 V/√3 ,O/P- 4-20mA DC dual o/p at 750ΩSr. No. - 07/06/146185/10. (complete details mentioned under tender schedule) |
| 14 | I/P Voltage- 0-150V AC, Range- 0-150 V AC, PTR- 220 KV √3 / 110 V √3O/P- 4 -20 mA DC dual o/p at 500 ΩSr. No. - 12/04/132462/7. (complete details mentioned under tender schedule) |
| 15 | I/P Voltage- 0-130.90 V AC, Range- 0-25K VACPTR- 21 KV √3 / 110 V √3O/P- 4 -20 mA DC dual o/p at 500ΩSr No.- 12/04/132462/20. (complete details mentioned under tender schedule) |
| 16 | I/P Voltage- 0-125 V AC, Range- 0-250K V ACPTR - 220KV √3 / 110 V √3O/P- 4 -20 mA DC dual o/p at 750ΩSr. No. - 05/06/145223/5. (complete details mentioned under tender schedule) |
| 17 | MVAR Transducer |
| 18 | Range - 600-0-600 MVAR INPUT- (-187.5 -0- +187.5) VAR PTR- 220KV/110V,CTR- 1600/1AO/P- 4-12-20mA DC (dual o/p) at 750Ω,Sr. No. - 05/06/145223/23 (complete details mentioned under tender schedule) |
| 19 | Range - 50-0-50 MVARINPUT- (-83.33) -0- (+83.33) VAR PTR- 220KV/√3 /110V/√3,CTR- 300/1AO/P- 4-12-20mA DC (dual o/p) at 750ΩSr. No. - 09/15/025313/10. (complete details mentioned under tender schedule) |
| 20 | Range - 500-0- 500/1000-0-1000 MVAR INPUT- (137.5 -0 - 137.5) VARPTR- 400KV/√3/110 V/√3CTR- 2000-1000- 500/1A,O/P - 4-12-20mA DC (dual o/p) at 750ΩSr. No. - 07/06/146185/8. (complete details mentioned under tender schedule) |
| 21 | Range - 50-0-50 MVAR INPUT- 27.50 -0- 27.50 VAR PTR- 400KV/√3/110V/√3, CTR- 1000-500 /1A,O/P- 4-12-20mA DC (dual o/p) at 750ΩSr. No. - 07/06/146185/62. (complete details mentioned under tender schedule) |
| 22 | Range- 600-0-600 MVAR.I/P - (-785.7) -0- (+785.7) VAR PTR- 21√3 KV/ 110√3VCTR- 20000/5A Din Rail MountingO/P- 4-12-20 mA. DC (dual o/p) at 500ΩSr. No. - 12/04/132462/15. (complete details mentioned under tender schedule) |
| 23 | Power Factor Transducer |
| 24 | I/P voltage- 0-110 V AC, 5A Range- (-0.5 Lag) - 1 – (+0.5) Lead PTR- 21 KV √3 / 110 V √3 CTR- 20000/5A Din Rail MountingO/P- 4-12-20 mA DC (dual o/p) at 500Ω, Sr. No. - 08/15/025450/01. (complete details mentioned under tender schedule) |
| 25 | Frequency Transducer |
| 26 | Input - 0-110V AC Range- 45-50-55HZ ,PTR- 400 kV/110V,O/P- 4-12-20mA DC (dual o/p) at 500Ω Sr. No. - 12/04/132462/4. (complete details mentioned under tender schedule) |
| 27 | AC Current Transducer |
| 28 | Input - 0-5Amp AC Range- 0-5 Amp O/P- 4-20 mA DC Dual output at 500Ω , Sr. No. - 12/04/132462/13 (complete details mentioned under tender schedule) . Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 4 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender