Tender For Servicing And Maintenance Works For 11 Kv Ht Vcb With Replacing Damaged Spare Parts At Electrical Sub-Stations Of Iiser-Kolkata, Mohanpur Campus
Tender Overview
Project Description
Tender for Servicing And Maintenance Works For 11 Kv Ht Vcb With Replacing Damaged Spare Parts At Electrical Sub-Stations Of Iiser-Kolkata, Mohanpur Campus
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Nov-2026 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 23-Nov-2026 |
BOQ
| Sl. No. | Item Description |
| 1 | Servicing, contact-resistance measurement (micro-ohmmeter) and open/close timing test of HT VCBs and Isolator — 800A, SIEMENS Make 11 KV HT VCB including checking of vacuum-interrupter integrity as applicable, Cleaning, greasing and torque-checking of all bolted HT connections at the double-pole, gantry, bus links, VCB terminals to eliminate loose-connection hot-spots. with submission of test report as per the scope of work |
| 2 | Servicing, testing and calibration check-up of CT/PT and Protection Relays for Siemens 7SR1206/7SR1002 Numerical Protection Relays / Schneider make Mi Com P111 Numerical Relays at ESS-1 including secondary-injection testing of Overload (51), Instantaneous Short-Circuit (50) and Earth Fault (51N/50N) relay elements, verification of pick-up & operating time against the approved settings, and co-ordination with TCS relay with re-calibration where required, subject to on-site approval from the Engineer-in-Charge. Relay parameters must be conducted/verified through an authorised testing agency and a signed test certificate submitted. |
| 3 | Thermostat rod type 50-800c with Pair of Heater 80 Watt Strip Type |
| 4 | Double Bit Key Lock Bar Assembly(as per attached Photo) |
| 5 | Door Interlock \\"L\\" Assembly for 11 kv(as per attached Photo) |
| 6 | TNC Switch Kaycee / Recom Make 40Amp (as per attached Photo) |
| 7 | Castle Lock \\"A\\" Mark(as per attached Photo) |
| 8 | Rack In/Out Drive Spindle/Shaft Type 3AH0104IZ 800 Amps 26.3 KA |
| 9 | Trip Coil 24V DC. INSPROS,2.65Ω |
| 10 | Closing Coil 24V DC. INSPROS,2.65Ω |
| 11 | 11KV , 3.15Amp, HRC PT Fuse , Bussman-Eaton Power / Phonex Make, 12ABCNA3-15/B1 |
| 12 | Indication Lamp ON/OFF/PT/Auto Trip ( R , Y, B, A and G ) |
| 13 | Nut & Bolt 8/15 Full Thread |
| 14 | Bolt 8/55 Half Thread with washer |
| 15 | O/C & E/F Relay 7SR1206-2JA, ARGUS, 1/5AMP Siemens make |
| 16 | O/C & E/F Relay 7SR1002-2JA, ARGUS, 1/5AMP Siemens make |
| 17 | Spring charge motor for 11 KV 1250 Amp HT VCB for existing 11 kv HT Switchboard at ESS-IHT VCB Model No:-8BK88-3AHO 104-IZUr -12KV,fr-50Hz,Ir-800A,Isc-26.3 kA, DC Comp-32%, |
| 18 | SMPS Power pack 220v AC/24 v DC 1 kvA Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
Upcoming · 1 dayBid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 1 dayBid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 3 daysTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender