Tender For Rate Contract For Various Electrical Work Including Repair And Maintenance Etc. Under The Jurisdiction Of Pwd Electrical Sub Division-V, Jaipur And Other Area, Jaipur.
Tender Value
50 Lakhs
Estimated cost
Bid Submission
12 Nov 2026
7 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Jaipur → Rajasthan
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for Rate Contract For Various Electrical Work Including Repair And Maintenance Etc. Under The Jurisdiction Of Pwd Electrical Sub Division-V, Jaipur And Other Area, Jaipur.
BOQ
| Sl. No. | Item Description |
| 1 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminum round tiles, 1.2 mm thick Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose / Holder /3 way connector, screws, making connections, testing etc. as required. |
| 2 | Short point (up to 3 mtr.) |
| 3 | Medium point (up to 6 mtr.) |
| 4 | Long point (up to 10 mtr.) |
| 5 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 2 Nos Hot Dipped Galvanized M.S Modular box of 1.2 mm thick with earth terminal,2 Nos 6 A two way Modular switch, 3 pin ceiling rose / holder / 3 way connector ,Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 6 | Short point (up to 3 mtr.) |
| 7 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988)accessories, Hot Dipped Galvanized Modular box of 1.2 mm thick with earth terminal, 6 A modular switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required. |
| 8 | On board |
| 9 | Short point (up to 3 mtr.) |
| 10 | Medium point (up to 6 mtr.) |
| 11 | Long point (up to 10 mtr..) |
| 12 | S&F following sizes (dia.) of ISI marked MMS ( IS:9537 P - III ) PVC conduit along with ISI marked (IS:3419-1988) accessories as required in recess including making jhiri in the wall,clamps at suitable spacing, covering conduit and making good the same as required. |
| 13 | 20 mm |
| 14 | 25 mm |
| 15 | 32 mm |
| 16 | 40 mm |
| 17 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal, 6 A switch, 3 pin ceiling rose/holder / 3 way connector , 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 18 | Short point (up to 3 mtr.) |
| 19 | Medium point (up to 6 mtr.) |
| 20 | Long point (up to 10 mtr.) |
| 21 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, Aluminium round tiles, 2 Nos 1.2 mm thick Hot dipped Galavanized MS box with earth terminal, 2 Nos 6 A two way switch,3 pin ceiling rose / holder/ 3 way connector, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 22 | Short point (up to 3 mtr.) |
| 23 | Medium point (up to 6 mtr.) |
| 24 | Long point (up to 10 mtr..) |
| 25 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) in recessed ISI marked MMS ( IS:9537 P - III ) PVC conduit & it's ISI marked (IS:3419-1988) accessories, 1.2 mm thick Hot dipped Galavanized MS box with earth terminal of required size, 6 A switch, 3/5 pin 6 A socket, 3.0 mm thick ISI marked (IS:2036-1995) phenolic laminated sheet, Al.alloy / Cadmium plated iron/ brass screws, cup washers, making connections, testing etc. as required. |
| 26 | On board |
| 27 | Short point (up to 3 mtr.) |
| 28 | Medium point (up to 6 mtr.) |
| 29 | Long point (up to 10 mtr..) |
| 30 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) on surface ISI marked ( IS:14927 P - II ) uPVC trunking & it's accessories, Hot Dipped Galvanized Modular box 1.2 mm thick with earth terminal/ Surface mounted UPVC molded modular box, 6 A Modular switch, Modular face plate with grid plate, 3 pin ceiling rose/holder /3 way Connector, screws, making connections, testing etc. as required. |
| 31 | Short point (up to 3 mtr.) |
| 32 | Medium point (up to 6 mtr.) |
| 33 | Long point (up to 10 mtr.) |
| 34 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade (IS:694) of approved make on surface ISI marked ( IS:14927 P - II ) uPVC trunking & it's accessories, 2 No. Hot Dipped Galvanized Modular box 1.2 mm thick with earth terminal/ 2 No. Surface mounted UPVC molded modular box, 2 Nos 6 A two way Modular switch, 3 pin ceiling rose / holder/3 way Connector , Modular face plate with grid plate, screws, making connections, testing etc. as required |
| 35 | Short point (up to 3 mtr.) |
| 36 | Medium point (up to 6 mtr.) |
| 37 | Long point (up to 10 mtr..) |
| 38 | Wiring of 3/5 pin 6 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible class 2 copper earth conductor 1.1 kV grade(IS:694) on surface ISI marked ( IS:14927 P - II ) uPVC trunking & it's accessories, Hot Dipped Galvanized Modular box 1.2 mm thick with earth terminal/Surface mounted UPVC molded modular box, modular 6 A switch, 3/5 pin 6 A modular socket, Modular face plate with grid plate, screws, making connections, testing etc. as required |
| 39 | On board |
| 40 | Short point (up to 3 mtr.) |
| 41 | Medium point (up to 6 mtr.) |
| 42 | Long point (up to 10 mtr..) |
| 43 | S&F following sizes of ISI marked ( IS:14927 P - II ) uPVC trunking along with accessories like coupler, inner, outer, elbow, square box, tee, end cap etc. on surface with screws, expansion fasteners etc. as required. |
| 44 | 20 mm x 12 mm |
| 45 | 25 mm x 12 mm |
| 46 | 32 mm x 12 mm |
| 47 | 25 mm x 16 mm |
| 48 | 38 mm x 16 mm |
| 49 | 38 mm x 25 mm |
| 50 | 38 mm x 38 mm |
| 51 | 50 mm x 16 mm |
| 52 | 50 mm x 50 mm |
| 53 | 75 mm x 50 mm |
| 54 | 75 mm x 75 mm |
| 55 | 100 mm x 50 mm |
| 56 | 100 mm x 100 mm |
| 57 | Supplying and laying FR PVC insulated & unsheathed flexible copper conductor of following nominal sizes with ISI marked (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing surface or recessed PVC/ MS conduit/casing capping making connections with Copper Lugs of suitable size, Ferrules,testing etc. as required. |
| 58 | 1 x 1.5 sq.mm |
| 59 | 2 x 1.5 sq.mm |
| 60 | 3x 1.5 sq.mm |
| 61 | 4 x 1.5 sq.mm |
| 62 | 1 x 2.5 sq.mm |
| 63 | 2 x 2.5 sq.mm |
| 64 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 65 | 3 x 2.5 sq.mm |
| 66 | 4 x 2.5 sq.mm |
| 67 | 1 x 4.0 sq.mm |
| 68 | 2 x 4.0 sq.mm |
| 69 | 3 x 4 sq. mm. |
| 70 | 4 x 4.0 sq.mm |
| 71 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. |
| 72 | 1 x 6.0 sq.mm |
| 73 | 2 x 6.0 sq.mm |
| 74 | 3 x 6.0 sq. mm. |
| 75 | 4 x 6.0 sq.mm |
| 76 | 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. |
| 77 | 2 x 6.0 sq. mm. + 1 x 4.0 sq. mm. |
| 78 | 1 x 10.0 sq.mm |
| 79 | 2 x 10.0 sq.mm |
| 80 | 4 x 10.0 sq.mm |
| 81 | 1 x 16.0 sq.mm |
| 82 | 2 x 16.0 sq.mm |
| 83 | Supplying and Laying coaxial cable 75 ohm impedance with foam PE insulated solid bare copper inner conductor, and Ist outer conductor of bonded alum. tape and second outer conductor of alum. alloy braid in existing surface or recessed conduit/casing capping including making connections as required. |
| 84 | RG - 6 |
| 85 | RG -11 |
| 86 | Supplying and Laying PE Insulated & PVC Sheathed unarmoured telephone cable with 0.5 mm dia. Solid Annealed electrolytic grade bare Copper Conductor as per IS: 8130/84 & confirming to TEC specification GR / WIR/06-03 March 2002 in existing surface or recessed conduit/casing capping. including ferruling on each pair for Identification etc. as required. |
| 87 | 2 pair |
| 88 | 4 pair |
| 89 | 5 pair |
| 90 | 10 pair |
| 91 | 20 pair |
| 92 | 50 pair |
| 93 | 100 pair |
| 94 | 200 pair |
| 95 | 100 pair |
| 96 | 200 pair |
| 97 | Supply and Laying of PE Insulated, PVC Inner Sheathed, armoured & PVC Sheathed Telephone Cable. with 0.5 mm thick Solid Annealed Bare Copper Conductor as per IS: 8130/84 telephone cable confirming to TEC specifications GR/WIR 06/03, Mar.-2002 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. |
| 98 | 5 pair |
| 99 | 10 pair |
| 100 | 20 pair |
| 101 | 50 pair |
| 102 | 100 pair |
| 103 | 200 pair |
| 104 | Supply and Laying of PE Insulated jelly filled Armoured Telephone Cable. with 0.6 mm thick Solid Annealed Bare Copper Conductor and confirming to TEC specifications confirming. to DOT GR/CUG-01/Aug.2003 in existing pipe / open trench / Cable tray / on surface including making necessary connection, testing etc. as required of size. |
| 105 | 5 pair |
| 106 | 10 pair |
| 107 | 20 pair |
| 108 | 50 pair |
| 109 | 100 pair |
| 110 | 200 pair |
| 111 | Supply & laying service connection with ISI marked (IS:694) 1100 Volts grade PVC insulated flat twin core sheathed solid aluminium conductor with 10 SWG G.I. Support wire duly clipped etc. as required. |
| 112 | 2.5sq.mm |
| 113 | 4.0 sq.mm |
| 114 | 6.0 sq.mm |
| 115 | 10.0 sq.mm |
| 116 | Supply and Laying ISI marked P.V.C. insulated submersible cable confirming to(IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 117 | 1.5 Sq.mm 3 core flat / Round |
| 118 | 2.5 Sq.mm 3 core flat / Round |
| 119 | 4.0 Sq.mm 3 core flat / Round |
| 120 | Supply and laying following size twin parallel type Speaker cables made with multi wire, bright annealed flexible bare electrolytic grade copper conductor, insulated with specially formulated transparent grade PVC compound, red strip for identification in existing conduit etc. as required. |
| 121 | 0.75 sq.mm |
| 122 | 1.0 Sq. mm |
| 123 | 1.5 Sq.mm |
| 124 | 2.5 Sq.mm |
| 125 | Supply and laying speaker cable of following size 2 core twin twisted multi stranded electrolytic grade copper conductor, overall PVC insulated and armoured cable (Blue colour) on surface/ above false ceiling including cost of GI spacers, saddles etc. as required. |
| 126 | 0.75 sq.mm |
| 127 | 1.0 Sq. mm |
| 128 | 1.5 Sq.mm |
| 129 | 2.5 Sq.mm |
| 130 | Supply and laying PVC Insulated and PVC Round Sheathed Multi Core copper conductor (IS:694) and as per IS 8130 : 2013 of 1.1 kV grade . Wire should be made from copper, stranding in acc. to IS:8130/IEC 60228 for lower watt loss , oxygen free for less chances of oxidization, insulation PVC type A/C/D , flame retardant as per IS 10810-53, better amperage rating as per IS:3961 part 5, in existing pipe / open trench / Cable tray / on surface including making connection etc. as required. |
| 131 | 1.5 sq.mm x 3 core |
| 132 | 1.5 sq.mm x 4 core |
| 133 | 1.5 sq.mm x 6 core |
| 134 | Providing & Fixing of 240/415 V AC MCB with positive isolation of 10 kA breaking capacity (B/ C/D tripping characteristic as per type of load and site requirement) 4 KV impulse withstand voltage, ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, low watt losses, trip free mechanism , energy limiting of class 3 as per IEC, minimum phase termination capacity of 25 sq.mm., conductor line load reversibility , IP 20 contact protection and fitted in existing distribution board/sheets, minimum electrical operation 20,000 upto 20 A rating, 10,000 upto 63 A, 5000 for 80 A & above rating including making connections, testing etc. as required. |
| 135 | Single pole MCB (With B / C curve tripping characteristics) |
| 136 | 0.5 A to 5 A rating |
| 137 | 6 A to 32 A rating |
| 138 | 40 A rating |
| 139 | 50/63 A rating |
| 140 | 80 A rating |
| 141 | 100 A rating |
| 142 | 125 A rating |
| 143 | Double pole MCB (With B / C curve tripping characteristics) |
| 144 | 0.5 A to 5 A rating |
| 145 | 6 A to 32 A rating |
| 146 | 40 A rating |
| 147 | 50/63 A rating |
| 148 | 80 A rating |
| 149 | 100 A rating |
| 150 | 125 A rating |
| 151 | Triple pole MCB (With B / C curve tripping characteristics) |
| 152 | 0.5A to 5 A rating |
| 153 | 6 A to 32 A rating |
| 154 | 40 A rating |
| 155 | 50/63 A rating |
| 156 | Four pole MCB (With B / C curve tripping characteristics) |
| 157 | 0.5A to 5 A rating |
| 158 | 6 A to 32 A rating |
| 159 | 40 A rating |
| 160 | 50/63 A rating |
| 161 | Triple pole MCB (With D curve tripping Characteristics) |
| 162 | 0.5 A to 5 A rating |
| 163 | 6 A to 32 A rating |
| 164 | 40 A rating |
| 165 | 50/63 A rating |
| 166 | Providing & Fixing of Recessed/surface mounting heavy duty horizontal type Double Door (Metal / Glazed / Acrylic) Distribution board with Metal end box made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3, complete with 100 amp. insulated copper bus bar/shorting link , brass neutral link with shrouds, brass earth link , door earthing arrangement, color coded interconnecting wire set of minimum 10.0 sqmm size and din bar,masking sheet, making internal DB terminations with copper lugs, Ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 167 | Metal door (single phase) IK-09 and IP-43 with Metal end box |
| 168 | 4 Way |
| 169 | 6 Way |
| 170 | 8 Way |
| 171 | 12 Way |
| 172 | 16 Way |
| 173 | Glazed / Acrylic door (single phase) IK-09 and IP-43 with Metal end box |
| 174 | 4 Way |
| 175 | 6 Way |
| 176 | 8 Way |
| 177 | 12 Way |
| 178 | 16 Way |
| 179 | Metal door (Three phase) IK-09 and IP-43 with Metal end box |
| 180 | 4 Way (8 incomer + 12 Outgoing) |
| 181 | 6 Way (8 incomer + 18 Outgoing) |
| 182 | 8 Way (8 incomer + 24 Outgoing) |
| 183 | 12 Way (8 incomer + 36 Outgoing) |
| 184 | Glazed / Acrylic door (Three phase) IK-09 and IP-43 with Metal end box |
| 185 | 4 Way (8 incomer + 12 Outgoing) |
| 186 | 6 Way (8 incomer + 18 Outgoing) |
| 187 | 8 Way (8 incomer + 24 Outgoing) |
| 188 | 12 Way (8 incomer + 36 Outgoing) |
| 189 | Providing & Fixing of Recessed/surface mounting heavy duty Flexi / Row type Distribution board with Metal end box made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with 100 Amp. copper shorting link , brass neutral link with shrouds, brass earth link , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules detachable gland plate, including making connections, testing etc. as required. |
| 190 | Double door IK-09 & IP-43 with metal End box |
| 191 | 4 Row 32 Module(8 module per row) |
| 192 | 4 Row 40 Module(10 module per row) |
| 193 | 4 Row 56 Module(14 module per row) |
| 194 | 3 Row 42 Module(14 module per row) with provision of 160 Amp. MCCB |
| 195 | Providing & Fixing of Recessed/surface mounting heavy duty Flexi / Row type Distribution board with Metal end box made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with 100 Amp. copper shorting link , brass neutral link with shrouds, brass earth link , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules detachable gland plate, including making connections, testing etc. as required. |
| 196 | Double door IK-09 & IP-43 with metal End box |
| 197 | 4 Row 32 Module(8 module per row) |
| 198 | 4 Row 40 Module(10 module per row) |
| 199 | 4 Row 56 Module(14 module per row) |
| 200 | 3 Row 42 Module(14 module per row) with provision of 160 Amp. MCCB |
| 201 | Glazed / Acrylic door IK-09 & IP-43 with Metal End Box |
| 202 | 4 Row 32 Module(8 module per row) |
| 203 | 4 Row 40 Module(10 module per row) |
| 204 | 4 Row 56 Module(14 module per row) |
| 205 | P&F metal clad / Polyamide industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in Recessed/surface mounting heavy duty Enclosure made out from Galvanized steel / CRCA sheet , powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3. (without MCB) including making connections, testing etc.as required. |
| 206 | 20 amp, (2P + E), 1 Module |
| 207 | 20 amp, (2P + E), 2 Module |
| 208 | 20 amp, (2P + E), 3 Module |
| 209 | 32 amp, (3P + E), 3 Module |
| 210 | 32 amp, (3P + N + E) 8 Module (with Polyamide Plug & Socket) |
| 211 | 63 amp, (3P + N+ E), 8 Module (with Polyamide Plug & Socket) |
| 212 | P & F of Industrial plug and socket conforming to IEC 60309-1/2 made out of self extinguishing engineering polymer / polyamide, nickel plated brass sleeve and pins, socket with shutter including making connection etc as reqd. |
| 213 | IP -67, IK - 09 Panel mounted socket |
| 214 | 16 A (2P+E) |
| 215 | 32 A (2P+E) |
| 216 | 32 A (3P+N+E) |
| 217 | 63 A (3P+N+E) |
| 218 | IP -67, IK-09 Surface/Wall mounted socket |
| 219 | 16 A (2P+E) |
| 220 | 32 A (2P+E) |
| 221 | 32 A (3P+N+E) |
| 222 | 63 A (3P+N+E) |
| 223 | IP -66, Surface/Wall mounted Interlocked switched socket Outlet with Provision of MCB |
| 224 | 16 A (2P+E) 250 V |
| 225 | 32 A (2P+E), 250 V |
| 226 | 32 A (3P+E), 415 V |
| 227 | IP - 67 Plug top |
| 228 | 16 A (2P+E) |
| 229 | 32 A (2P+E) |
| 230 | 32 A (3P+E) |
| 231 | 32 A (3P+N+E) |
| 232 | Providing & Fixing of Recessed/surface mounting heavy duty Vertical TPN Distribution board with Metal end box with provision of incomer suitable for MCB / RCCB/ RCBO up to 63 Amp and SP / TP MCB upto 32 Amp. as outgoing ,made out from Galvanized steel / CRCA sheet, powder coated conforming to IS-8623-1 & 3 / IEC 61439- 1 & 3 complete with insulated 100 A rating copper bus bar, brass neutral bars with shrouds, brass earth bar , color coded interconnecting wire set of suitable rating and din bar, door earthing arrangement, masking sheet, making internal DB terminations with copper lugs, ferrules, detachable gland plate, including making connections, testing etc. as required. |
| 233 | Double door IK-09 & IP-43 with Metal end box |
| 234 | 4 Way (8 Incomer +12 Outgoing) |
| 235 | 6 Way (8 Incomer +18 Outgoing) |
| 236 | 8 Way (8 Incomer +24 Outgoing) |
| 237 | 12 Way (8 Incomer + 36 Outgoing) |
| 238 | Double door IP-43 & IK-09 with Provision of Incomer MCCB up to 125 A Rating with Metal end box |
| 239 | 4 Way |
| 240 | 6 Way |
| 241 | 8 Way |
| 242 | 12 Way |
| 243 | Double door IP-43 & IK-09 with Provision of Incomer MCCB 160 A Rating with Metal End Box |
| 244 | 4 Way |
| 245 | 6 Way |
| 246 | 8 Way |
| 247 | 12 Way |
| 248 | Double door IP-43 & IK-09 with Provision of Incomer MCCB 200/250 A Rating with metal End Box |
| 249 | 4 Way |
| 250 | 6 Way |
| 251 | 8 Way |
| 252 | 12 Way |
| 253 | P & F Surface mounting IP-65, IK-09 Class-II self extinguishing insulating material weather proof cabinets confirming to EN60439-3 with IP-65 Key lock, fully reversible door and cabinet, removable chasis and face plates, of following size. |
| 254 | 3/4 module |
| 255 | 6 module |
| 256 | 8 module |
| 257 | 1 row 12 module |
| 258 | 2 row 24 module |
| 259 | 3 row 36 module |
| 260 | P & F ISI marked (IS:3854) 6 amp. flush type non modular switch with CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 261 | P & F ISI marked (IS :3854) 16 amp. flush type non modular switch CM/L no. printed and made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 262 | Providing & Fixing of 6 amp. Combined flush type non modular socket and switch set made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 263 | Providing & Fixing of 16 amp. Combined flush type non modular socket and switch set with indicator and fuse set, made out from industrial grade Polycarbonate material including cutting hole in tile and making connection testing etc. as required. |
| 264 | Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push surface type CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 265 | Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A switch surface type, CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 266 | Providing & Fixing of ISI marked (IS :3854) non modular 6A bell push flush type CM/L no. printed and made out from industrial grade Polycarbonate materialincluding cutting hole in tile and making connection testing etc. as required. |
| 267 | Providing & Fixing of ISI marked (IS :3854) twin control non modular 6A switch flush type CM/L no. printed , made out from industrial grade Polycarbonate material, including cutting hole in tile and making connection testing etc. as required. |
| 268 | Providing & Fixing of non modular 6A hanging bell push/one way switch made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 269 | Providing & Fixing of IS:1293 marked of 3 pin 6 amp. flush type non modular socket CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 270 | Providing & Fixing of IS:1293 3/6 pin 16 amp flush type non modular socket CM/L no. printed and made out from Industrial grade Polycarbonate material, brass terminal with Porcelain based back cover & captive screws including cutting hole in tile and making connection testing etc. as required. |
| 271 | Providing & Fixing of ISI marked (IS:371) 6 amp surface type 3 pin ceiling rose with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 272 | Providing & Fixing of ISI marked (IS:1258) batten/angle lamp holder with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal & captive screws including making connection testing etc. as required. |
| 273 | Providing & Fixing of ISI marked (IS:1293) 6 amp unbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal including making connection testing etc. as required. |
| 274 | Providing & Fixing of ISI marked (IS:1293) 16 amp unbreakable 3 pin plug top having lamp indicator with CM/L no. printed and made out from industrial grade Polycarbonate material, brass terminal including making connection testing etc. as required. |
| 275 | Providing & Fixing of flush type non modular 2 pin telephone socket with plug top made out from industrial grade Polycarbonate material, brass terminals including making connection testing etc. as required. |
| 276 | Providing & Fixing of flush type non modular single line telephone jack made out from industrial grade Polycarbonate material, including making connection testing etc. as required. |
| 277 | Providing & Fixing of flush type non modular double line telephone jack made out from industrial grade Polycarbonate materialincluding making connection testing etc. as required. |
| 278 | Providing & Fixing of flush type non modular coaxial T.V. socket made out from industrial grade Polycarbonate material,including making connection testing etc. as required. |
| 279 | Providing & Fixing of IS 11037 marked non modular socket size flush type 100 watt rotary minimum 5 step fan regulator with CM/L no. printed and made out from industrial grade Polycarbonate material including making connection testing etc. as required. |
| 280 | P & F ISI marked 32 A D.P. switch with fuse and indicating lamp including making connection testing etc. as required. |
| 281 | Providing & Fixing of ISI marked (IS:302) gong bell with CM/L no. printed including making connection testing etc. as required. |
| 282 | Providing & Fixing of single / multi tone electronic call bell / remote bell including making connection testing etc. as required. |
| 283 | Providing & Fixing of ISI marked (IS:302) ding dong/musical chime bell including making connection testing etc. as required. |
| 284 | Providing & Fixing of modular type switch/ bell push duly ISI marked (IS :3854) with CM/L no. printed and made out of unbreakable and fire retardant virgin UV Stabilized Polycarbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating ,minimum width of switch toggle( PUSH PART ) should not less then 20mm, including making connections, testing etc as required. |
| 285 | 10 A one way switch |
| 286 | 10 A two way switch |
| 287 | 16 A one way switch 1M |
| 288 | 20 A one way switch 1M |
| 289 | 20 A one way switch 2M |
| 290 | 16 Amp. 2 Module switch With Led Indicator |
| 291 | 32 Amp. 2 Module switch With Led Indicator |
| 292 | Providing & Fixing of IS:1293 marked modular type lockable feature socket with CM/L no. printed duly made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 293 | 6 A 3 pin shuttered socket |
| 294 | 6/16 A shuttered socket |
| 295 | 13 A flat pin international socket (Non ISI) |
| 296 | Providing & Fixing of modular type 100W Step Fan regulator duly ISI marked (IS 11037) with CM/L no. printed made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating , including making connections, testing etc as required. |
| 297 | 5 step fan regulator 2 Module |
| 298 | Providing & Fixing of following modular accessories, made out of unbreakable and fire retardant virgin poly carbonate with brass terminals and captive screws & silver alloy contact tip with IP-20 rating, including making connections, testing etc as required. |
| 299 | RJ-11 telephone jack single line |
| 300 | RJ-11 telephone jack Double line |
| 301 | USB Charger 2 A - 1 M with BIS mark |
| 302 | RJ-45, Cat 6 computer jack with shutter |
| 303 | T.V. coaxial socket |
| 304 | Blanking plate |
| 305 | 25 Amp. 2 Module Motor Starter with on / off Push button |
| 306 | LED Skirting /Foot Light 2 Module |
| 307 | Electronic Chime/Buzzer 2M |
| 308 | Modular MCB 6 A to 32 A SP |
| 309 | Modular MCB 6 A to 32 A DP |
| 310 | Providing & Fixing of following size mounting grid plates with cover plates made from fire retardent UV established high performance engineering plastic suitable for all universal metal boxes for front installation & removal direct fit type complete in all respect. |
| 311 | 1/2 Module |
| 312 | 3 Module |
| 313 | 4 Module |
| 314 | 5 Module |
| 315 | 6 Module |
| 316 | 8 Module |
| 317 | 10 Module |
| 318 | 12 Module |
| 319 | 16/18 Module |
| 320 | Providing & Fixing of Hot dipped Galvanized metal box of 1.2 mm thick with earthing terminal and adjustable floating clamp in recess/ surface suitable for modular accessories as required. |
| 321 | 1-2 Module |
| 322 | 3 Module |
| 323 | 4-5 Module |
| 324 | 6-8 Module |
| 325 | 10-12 Module |
| 326 | 16/18 Module |
| 327 | Providing & Fixing of Wiring Accessories OEM fabricated following size virgin material UPVC modular boxes on surface suitable for modular accessories as required. |
| 328 | 1-2 Module |
| 329 | 3 Module |
| 330 | 4/5 Module |
| 331 | 6 / 8 module |
| 332 | 10 / 12 module |
| 333 | Providing & Fixing of Multiple socket with surge and spikes protection cartridge not less then 5 KV with minimum four nos. universal 6 A sockets, one 6 A switch and 3 pin company fitted plug top and 3 core multistrand copper lead minimum 1.5 mtr. including making connection etc as required. |
| 334 | Providing & Fixing of DLP PVC adaptable trunking system for cable management including finishing accessories like corners, tees, adjustable angles, junction etc. as required . The trunking system shall have adaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover. OEM have to submit NABL accrediated /CPET lab test reports /EN 50085-2-1 complaince certificate. |
| 335 | 80mm x 50mm |
| 336 | 100/105mm x 50mm |
| 337 | 150/160mm x 50mm |
| 338 | 195/200mm x 50mm |
| 339 | Providing and fixing of power plug point with non modular accessories with Galvanized box of 1.2 mm thick with earth terminal with suitable size 3.0 mm thick phenolic laminated sheet (IS : 2036 - 1995) cover including cost of 16 amp. Switch (IS :3854) and 3/6 pin 16 amp. socket outlet making connection , testing , etc. as required. |
| 340 | Supplying and fixing of power plug point with Modular accessories on hot dipped galvanized modular box of 1.2 mm thick with earthing terminal/connector on surface or in recessed with suitable size of modular face place with grid plate and cover plate including cost of ISI marked modular 16 amp. Switch (IS :3854) and 6/16 amp. socket outlet (IS:1293) making connection , testing , etc. as required. |
| 341 | P & F Krone module with base frame in the recess / surface made out of 1.2 mm thick sheet steel box, front openable, having locking arrangements duly powder coated ,including dressing, ferruling and punching of telephone cable with krone tool etc. as required. |
| 342 | 10 Pairs |
| 343 | 20 Pairs |
| 344 | 50 Pairs |
| 345 | 100 Pairs |
| 346 | 200 Pairs |
| 347 | SITC of IP-42 and general construction confirming to IS:8623 : 1993, wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel as specifications and Other parameters required as per point (a) ,(b), (c),(d), (e), (f), (g), (h) as below:- |
| 348 | (a) Thickness of CRCA sheet shall not be less than 1.6 mm upto 450 mm length/ width of any compartment and be 2.0 mm above 450 mm, load bearing structure shall be 2.0 mm thick sheet supported by base M.S. channel if required, cable alley compartments having concealed hinged type doors with key type lock with / without detachable extension type structure. Removable 3 mm. thick sheet steel gland plates with appropriate size of knockouts for cables shall be provided |
| 349 | (b) complete panel shall undergo a process of degreasing, Water rinsing, Activation, derusting, pickling in acid bath, phosphatising & shall be subjected to nine tank process and then Powder coated with approved shade of minimum 70 microns on both side(Inner & Outer side) of panel. The panel having PE foam/ Neoprene rubber gasket of not less than 3mm thickness ,required hardware , concealed hinged door with key type locking arrangement for equipment/switchgear earthed with 2.5 sq.mm braided copper wire. |
| 350 | [c) Interconnection between bus bar and switchgears /cable shall be rigidly supported and made out by flexible copper wires (up to 63 amp ) and by solid bus bar (>63 amp ) . control wiring will be carried out with 1.5 Sq.mm, Earth wire with 2.5 Sq.mm and CT with 2.5 sq.mm flexible copper wire only. All joints / interconnections of copper bus bar shall be dully tinned . Clearance between main bus bar and risers / metal parts shall be at least 10 mm additional to width of bus bar Bus bar is insulated by Heat Shrinkable sleeves . Earth and Neutral bus bar shall be half of the size of phase bus bar. ( Cost of Bus bar / Flexible wire for Interconnection between Main busbar and Switchgear is to be Paid Extra ) |
| 351 | (d) Wiring between components within switchgear and Incoming / outgoing cable shall be done through the terminal block only. Direct connection shall not be permitted. Each terminal block shall be one piece moulded, barrier type, 650 volt grade, complete with washers, heads, studs with two nuts and identification strips and shall have adequate continuous current rating. For tap-offs, adjacent terminals with shorting strips shall be used. 10% Spare terminal blocks shall be provided. Wire identification on marking strip shall correspond to the designation of the wiring diagrams. All wire terminals on the equipment shall also be marked with designation corresponding to those of the wiring diagram. |
| 352 | (e) All wiring shall be enclosed in plastic channels and neatly bunched and closed in metering chamber, Wiring between terminals of various devices shall be ‘point to point’ (no wire splitting or tee connections) with wires neatly trucked along the back of the panels, adequately supported to prevent sagging. |
| 353 | (f) Floor mounted panel shall be mounted on Base frame of ISMC channel size 100 x 50 x 5 mm ( to be paid Extra ) |
| 354 | (g) Tests: The insulation resistance (with 1000 V Megger) and High voltage Power frequency test (by applying a voltage of 2.5KV for one minute) shall be measured between phases, between phase and neutral and between phase and earth. both before and after high voltage power frequency test. The insulation resistance shall not be less than three megaohm. CT Secondary current injection test shall also be carried out. |
| 355 | (h) only outer surface area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator only (CPRI type Test certificates for Temp. rise test, Short circuit test for 50 kA and IP test is to be submitted) |
| 356 | Supplying and fixing of Aluminium (IEC 60105 ISO 209-1,2) / Copper (IEC 60028) bus bar by means of SMC / DMC type insulator, with short circuit withstand capacity of 31 MVA for 1 Sec. , high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. |
| 357 | Electrolytic grade Aluminium bus bar 6010 grade |
| 358 | Electrolytic grade (Cu+ETP) Tin Coated annealed copper bus bars IACS 100% grade. |
| 359 | Providing & Fixing of IS: 13875 & IEC :61326/IEC:62053-22 confirming LED Digital type (up to 500) V range Volt meter / Direct- Ammeter / CT opertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracy of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. |
| 360 | Single Phase Ammeter |
| 361 | Single Phase Voltmeter |
| 362 | Three phase Ammeter with Inbuilt Selector Switch |
| 363 | Three phase Voltmeter with Inbuilt Selector Switch |
| 364 | Three phase KWH Meter |
| 365 | Three phase KWH Meter Dual Source |
| 366 | Frequency Meter |
| 367 | Three phase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS Meter |
| 368 | Three phase AMP + HZ + PF + KW + KVA + KVAR + KVARH+KWH+DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS Meter |
| 369 | Three phase with universal Auxiliary supply + AMP + HZ + PF + KW + KVA + KVAR + KVARH + KWH + DUAL ENERGY+ ENERGY+THD-I, THD-V & RUN HRS + MD with RS485 Meter |
| 370 | Providing & Fixing of Current Transformer confirming IS 2705-I (1992) with secondary terminal and shorting Block , with all necessary support in existing panel including connection etc. as required Current transformer Ring Type Tape Wound/Resin Cast Wound Accuracy Cl, CT ratio and burden as specified. ISF<=5, Cu cross section of secondary wire 1.5sqmm (minimum), including all necessary support in existing panel including connection etc. as required . |
| 371 | Ring type tape wound CT |
| 372 | C T Class 1, Ratio up to 150/5, Burden 5 VA |
| 373 | C T Class 1, Ratio 200/5 to 600/5, Burden 10 VA |
| 374 | C T Class 1, Ratio 800/5 to 1200/5, Burden 15 VA |
| 375 | C T Class 1, Ratio 1500/5 to 3000/5, Burden 15 VA |
| 376 | C T Class 1, Ratio 3200/5 to 5000/5, Burden 15 VA |
| 377 | Resin cast wound type CT |
| 378 | C T Class 1, Ratio up to 150/5, Burden 5 VA |
| 379 | C T Class 1, Ratio 200/5 to 600/5, Burden 15 VA |
| 380 | C T Class 1, Ratio 800/5 to 1200/5, Burden 15 VA |
| 381 | C T Class 1, Ratio 1600/5 to 3000/5, Burden 15 VA |
| 382 | C T Class 1, Ratio 4000/5 to 5000/5, Burden 15 VA |
| 383 | Providing & Fixing of selector switch of 10 A for voltmeter using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range 25 degree C to 55 degree C, frequency upto 10 KHz. Switch life under standard operating conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . |
| 384 | Voltage Between Phases with OFF ( 4 Position ) |
| 385 | Voltage Between Phases & Individual Phases to Neutral with OFF ( 7 Position ) |
| 386 | Providing & Fixing of CT linked selector switch of 10 A for Ampere meter (4 position ) using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range 25 degree C to 55 degree C, frequency upto 10 KHz. switch life under standard operating conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour , including making connection etc. as required . |
| 387 | Providing & Fixing of 10 A Cam operated rotary (Local- Remote, Auto - manual) switches on existing panel with 1 pole 2 way and off position using high grade engineering material to international standards with cam assembly insulation of glass filled polyamide with high tracking index. For reliable and stable electrical and mechanical endurance double butt contacts with silver bi-metal on copper should provided . contact assembly is of operating temp range -25 degree C to 55 degree C, frequency upto 10 KHz. switch life under std. op. conditions shall be mechanically minimum 50000 operations @300 cycles/ hour and electrically 10,000 operations at 100% rated duty for 100 cycles/ hour including making connection etc. as required . |
| 388 | All in all comprehensive maintenance of mono block / submersible motor pump set with starter panel etc. complete in all respect |
| 389 | Sub mersible Motor pump set |
| 390 | Rewinding of ceiling fan motor (starting and running winding) including all necessary material. The motor is to be wound taking no. of coils, turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. (New model ceiling fan) |
| 391 | 900/1200 mm sweep (New model ceiling fan) |
| 392 | Labour charges for removing and refixing of Ceiling fan/ Exhaust fan from site |
| 393 | Providing & Fixing of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid aberration marks and pasting the mat with synthetic rubber adhesive as required. |
| 394 | 3.3 KV, class A 2 mm thick with proof voltage 10 KV AC (rms) and Break Down Voltage 30 KV AC (rms) |
| 395 | 11 KV, Class B 2.5 mm thick with proof voltage 22 KV AC (rms) and Break Down Voltage 45 KV AC (rms) |
| 396 | Providing & Fixing of self healing IP20 MPP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 OR IEC : 60831-1& 2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz, Operating loss less than 0.30 Watt per KVAR. Min over current capacity 1.8 times rated current & peak inrush current min. 300 times of rated current, life expectancy greater than 100000hrs (temp class - 25 D) in 440 V including making connections, testing etc. as required. |
| 397 | Heavy duty Three phase 440 V, 50 Hz cylindrical type capacitor (Bank) |
| 398 | Heavy duty Three phase 525V, 50 Hz cylindrical type capacitor (Bank) |
| 399 | Providing & Fixing of 3-Phase 415/440 V , 7 % / 14 % Detuned Reactors conforming to IEC 61558-2-20 & IEC 60076-6 Aluminium wound for harmonics filter with 180% to 200 % Linearity, H - Class Insulation ( 180 degree C), high temp. Disconnection above 155 deg C., ambient temperature: +60 deg C. with thermal cut off switch in existing panel with following Capacitor ratings. including making connections, testing etc. as required. |
| 400 | 7 % (189 Hz) Aluminium wound Reactors |
| 401 | For 1 to 5 KVAR capacitor |
| 402 | 10 KVAR |
| 403 | 12.5 KVAR |
| 404 | 15 KVAR |
| 405 | 20 KVAR |
| 406 | 25 KVAR |
| 407 | 50 KVAR |
| 408 | 100 KVAR |
| 409 | 14 % (133 Hz) Aluminium wound Reactors |
| 410 | For 1 to 5 KVAR capacitor |
| 411 | 10 KVAR |
| 412 | 12.5 KVAR |
| 413 | 15 KVAR |
| 414 | 20 KVAR |
| 415 | 25 KVAR |
| 416 | 50 KVAR |
| 417 | 100 KVAR |
| 418 | Providing & Fixing of microprocessor based 3 CT’s for all 3 phase sensing compensation power factor correction relay with Approx. Size 139 mm x 139 mm, Operating Voltage 415/440 V , IEC / EN 61000-6-(2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analyzing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, High voltage, THD-I & THD-V insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi Built in MFM with PF Controller LCD Display, CT polarity auto correction % THD up to 30 harmonics level, step switching time 2 sec to 1800 sec. Lead & Lag parameters, metering facility and 3 no. Class- 0.5 Cast Resin CT for sensing the relay including making connection with 1.5 Sq.mm copper wire etc. as required. |
| 419 | 6 to 8 stage |
| 420 | 12 to 16 stage |
| 421 | Providing & Fixing of AC operated heavy duty 230 /440 Volt power contactor confirming to IS/IEC 60947-4-1 : 2000 having provision of mechanical interlocking, auxilary contacts, Din rail mounting type including making connections, testing etc. as required. |
| 422 | 4 pole Power contactors with following AC 1 Rating |
| 423 | 16 Amp. |
| 424 | 25/32 Amp. |
| 425 | 40 Amp |
| 426 | 50/55 Amp |
| 427 | 63 Amp |
| 428 | 100/105 Amp |
| 429 | 160 Amp |
| 430 | 200 Amp |
| 431 | 250 Amp |
| 432 | 325 Amp |
| 433 | Providing & Fixing of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current as per IS/IEC 60947-4-1 : 2000, insulation voltage 1000V, impulse withstand voltage 8 KV,Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank. |
| 434 | up to 6 KVAR |
| 435 | 8.5 KVAR |
| 436 | 10 KVAR |
| 437 | 12.5 KVAR |
| 438 | 15.0 KVAR |
| 439 | 20.0 KVAR |
| 440 | 25.0 KVAR |
| 441 | 30.0 KVAR |
| 442 | 40.0 KVAR |
| 443 | 50.0 KVAR |
| 444 | 60.0 KVAR |
| 445 | 75.0 KVAR |
| 446 | 85 KVAR |
| 447 | 100 KVAR |
| 448 | P & F of Control relays (Auxiliary Contactor) for AC control standard. 24 V Coil 110, 240 V, 415 V, 50 Hz conforming to IS:13947-4-1/IEC:60947-4-1 with required NO & NC combination including making connections, testing etc. as required. |
| 449 | P & F of Front / Side mounting Add on Auxiliary Contact Block with required NO & NC combination including making connections, testing etc. as required. |
| 450 | Providing & Fixing of thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required. |
| 451 | Up to 14 Amp |
| 452 | 14 to 23 Amp |
| 453 | 20 to 33 Amp |
| 454 | 24 to 40 Amp |
| 455 | P & F of 240 / 415 V Electronic ON - OFF Timer 3 -30 Sec / 12 - 120 Sec including making Connection etc. as required. |
| 456 | Providing & Fixing of Electromechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming conforming to IEC 60730-1 and 60730-2-7 etc. as required. |
| 457 | One day reserve (Electromechanical type ) |
| 458 | One day & week reserve (digital type ) |
| 459 | Providing & Fixing of 110 - 240 V, AC, 1 ph. , 2 W Astronomical time switch with surge suppressor, memory card, Sunrise / Sunset selectable, software for programming including making connection, etc. as required. |
| 460 | Providing & Fixing of IP54 direct or CT operated, 1x240 / 3x240 volts , 50 Hz static watt-hour meter (kwh) , having resolution 0.1 / 0.01 kwh , confirming to IS:13779/ IS:15959, LED indicators for tamper operation ( Reverse &/or earth connection) , pulsating LED indicator for meterology , LCD Display, cover plate for body and terminal sealing , push button for all standard parameters, including making connection ,testing etc. as required. |
| 461 | up to 30 ampere single phase meter acc. Cl 1 |
| 462 | 10 A to 60 ampere Single phase meter acc. Cl 1 |
| 463 | 3ph, 4W KWh CT Operated Base mounting 240 V-/5A acc. Cl 0.5s |
| 464 | 3ph, 4W KWh Direct Base mounting 240 V 10-60 Amp acc. Cl 1 |
| 465 | 3ph, 4W Trivector Meter,240 V(L-N) 5A acc. Cl 0.5 |
| 466 | P & F of Direct on line (DOL) / Star - Delta Starter as per IEC type-2 Co-ordination chart of OEM in Existing Panel with circuit breaker having inbuilt overload protection or separate thermal Overload relay , Short circuit, phase loss protection, suitable Contactors, including wiring between switchgears, Indicating lamps for R,Y,B,ON,OFF, Push button for ON, OFF, Volt meter, Ammeter, selector switch for local/remote, auto/manual/OFF operation. Cast resin CT's, provision for potential free contacts making connection, testing etc. as required. |
| 467 | Direct on line (DOL) Starter with following Motor rating |
| 468 | Motor rating 0.55 KW |
| 469 | Motor rating 0.75 KW |
| 470 | Motor rating 1.5 KW |
| 471 | Motor rating 2.2 KW |
| 472 | Motor rating 4.0 KW |
| 473 | Motor rating 5.5 KW |
| 474 | Motor rating 7.5 KW |
| 475 | SITC of 3 /4 pole current limiting Moulded case circuit breaker (MCCB) made of flame retardent & heat resistant material having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings , conforming to IS/IEC 60947 P -2 :2003 with front face and centralised adjustable, trip free mechanisum, true contact position indicator, designed for both horizontal & vertical mounting without any adverse effect on electrical performance, suitable for operation from 50 to 55 degree and without derating upto 40 degree, pollution degree 3, having positive isolation capability, push (test) to trip, trip time less then 10 ms under s/c condition, Breaking capacity Ics = 100% Icu. U imp =8 KV, rated insulation voltage 690V. provision for UVR , shunt trip , earth fault trip, door interlock, pad lock & rotary handle ( to be paid extra) , including making connections etc. as required. OEM shall have submit NABL / CPRI / ERDA/ Intertek accrediated lab type test certificate. |
| 476 | 3 pole MCCB With Thermal Magnetic release |
| 477 | up to 100 Amp , 10 kA, fixed O/L & fixed S/C setting |
| 478 | up to 100 Amp , 25 kA, adjustable O/L & Fixed S/C setting, |
| 479 | 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, |
| 480 | 160 Amp , 25 kA, adjustable O/L & fixed S/C setting, |
| 481 | 200 Amp , 25 kA, adjustable O/L & fixed S/C setting, |
| 482 | 250 Amp , 25 kA, adjustable O/L & adjustable S/C setting, |
| 483 | 250 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 484 | 400 Amp , 35 kA, adjustable O/L & adjustable S/C setting, |
| 485 | Providing & Laying XLPE insulated & P.V.C. sheathed Armoured Aluminium cable confirming to IS :7098 P - I of 1.1 KV with H4- Grade electrolytic aluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing commissioning etc. as required of following size. |
| 486 | 4.0 Sq. mm |
| 487 | 2 core |
| 488 | 3 core |
| 489 | 4 core |
| 490 | 6.0 Sq. mm |
| 491 | 2 core |
| 492 | 3 core |
| 493 | 4 core |
| 494 | 10.0 Sq. mm |
| 495 | 2 core |
| 496 | 3 core |
| 497 | 4 core |
| 498 | 16.0 Sq. mm |
| 499 | 2 core |
| 500 | 3 core |
| 501 | 4 core |
| 502 | 25.0 Sq. mm |
| 503 | 2 core |
| 504 | 3 core |
| 505 | 3.5 core |
| 506 | 35.0 Sq. mm |
| 507 | 2 core |
| 508 | 3 core |
| 509 | 3.5 core |
| 510 | 50.0 Sq. mm |
| 511 | 2 core |
| 512 | 3 core |
| 513 | 3.5 core |
| 514 | 70.0 Sq. mm |
| 515 | 1 core |
| 516 | 2 core |
| 517 | 3 core |
| 518 | 3.5 core |
| 519 | 95.0 Sq. mm |
| 520 | 1 core |
| 521 | 3.5 core |
| 522 | 120.0 Sq. mm |
| 523 | 3.5 core |
| 524 | 185.0 Sq. mm |
| 525 | 3.5 core |
| 526 | 240.0 Sq. mm |
| 527 | 3.5 core |
| 528 | Excavation of trench of size 75 cm (Depth) x 35 cm(Width) for laying of suitable no. of LT cables (Inter spacing between cables should not be less than 2 D) in ground with following procedure :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 100 mm on top of the cable, (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable, (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth. |
| 529 | Add Extra in Item no.11.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 530 | Excavation of trench of size additional 20 cm in width, with procedure as per following points :- (a) Make a river sand bed of height 100 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm., (c) Provide river sand bed of height 100 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 /Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically (Longest side is vertical to cable) along the cable , (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 531 | Add Extra in Item no. 11.7 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 532 | Add Extra in item no. 11.1 to 11.4 for Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
| 533 | Up to 35 Sq.mm fixed with 25 mm x 2 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps. |
| 534 | Above 35 sq. mm and upto 95 sq. mm fixed with 40 mm x 3 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps. |
| 535 | Above 95 sq. mm and upto 185 sq. mm fixed with 40 mm x 4 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps. |
| 536 | Above 185 sq. mm and upto 400 sq. mm fixed with 50 mm x 5 mm thick suitable length red oxide and enamel painted MS clamp and base, pvc rawl plug and screws of sufficient size with spacing 0.6 Mtr. Between Clamps. |
| 537 | Add extra in item no. 11.1 to 11.4 for Laying Charges for cable through Manual Boggi by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 538 | Add Extra in item no. 11.1 to 11.4 for Laying Charges for cable through Vermeer machine by making pit at regular interval and repairing the pit after laying of cable with PCC/ Bitumin as required. |
| 539 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as per IS 8337-1976 of following size of PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. |
| 540 | 2 x 4.0 sq.mm |
| 541 | 2 x 6.0 sq.mm |
| 542 | 2 x 10.0 sq.mm |
| 543 | 2 x 16.0 sq.mm |
| 544 | 2 x 25.0 sq.mm |
| 545 | 2 x 35.0 sq.mm |
| 546 | 2 x 50.0 sq.mm |
| 547 | 2 x 70.0 sq.mm |
| 548 | 3 x 4.0 sq.mm |
| 549 | 3 x 6.0 sq.mm |
| 550 | 3 x 10.0 sq.mm |
| 551 | 3 x 16.0 sq.mm |
| 552 | 3 x 25.0 sq.mm |
| 553 | 3 x 35.0 sq.mm |
| 554 | 3 x 50.0 sq.mm |
| 555 | 3 x 70.0 sq.mm |
| 556 | 3.5 x 25.0 sq.mm |
| 557 | 3.5 x 35.0 sq.mm |
| 558 | 3.5 x 50.0 sq.mm |
| 559 | 3.5 x 70.0 sq.mm |
| 560 | 3.5 x 95.0 sq.mm |
| 561 | 3.5 x 120.0 sq.mm |
| 562 | 3.5 x 150.0 sq.mm |
| 563 | 3.5 x 185.0 sq.mm |
| 564 | 3.5 x 240.0 sq.mm |
| 565 | 3.5 x 300.0 sq.mm |
| 566 | 3.5 x 400.0 sq.mm |
| 567 | Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring, Compression Nut, heavy duty Copper lugs (IS 8337- 1976) duly crimped with crimping tool, PVC tape for following size of PVC insulated & PVC sheathed/ XLPE copper conductor cable of 1100 volt grade as required. |
| 568 | 1 x 16.0 sq.mm |
| 569 | 1 x 25.0 sq.mm |
| 570 | 1 x 35.0 sq.mm |
| 571 | 1 x 50.0 sq.mm |
| 572 | 1 x 70.0 sq.mm |
| 573 | 1 x 95.0 sq.mm |
| 574 | 1 x 120.0 sq.mm |
| 575 | 2 x 4.0 sq.mm |
| 576 | 2 x 6.0 sq.mm |
| 577 | 2 x 10.0 sq.mm |
| 578 | 2 x 16.0 sq.mm |
| 579 | 2 x 25.0 sq.mm |
| 580 | 2 x 35.0 sq.mm |
| 581 | 2 x 50.0 sq.mm |
| 582 | 2 x 70.0 sq.mm |
| 583 | 2 x 95.0 sq.mm |
| 584 | 2 x 120.0 sq.mm |
| 585 | 3 x 1.5 sq.mm |
| 586 | 3 x 2.5 sq.mm |
| 587 | 3 x 4.0 sq.mm |
| 588 | 3 x 6.0 sq.mm |
| 589 | 3 x 10.0 sq.mm |
| 590 | 3 x 16.0 sq.mm |
| 591 | 3 x 25.0 sq.mm |
| 592 | 3 x 35.0 sq.mm |
| 593 | 3 x 50.0 sq.mm |
| 594 | 3 x 70.0 sq.mm |
| 595 | 3 x 95.0 sq.mm |
| 596 | 3 x 120.0 sq.mm |
| 597 | 4 x 1.5 sq.mm |
| 598 | 4 x 2.5 sq.mm |
| 599 | 4 x 4.0 sq.mm |
| 600 | 4 x 6.0 sq.mm |
| 601 | 4 x 10.0 sq.mm |
| 602 | 4 x 16.0 sq.mm |
| 603 | 4 x 25.0 sq.mm |
| 604 | 4 x 35.0 sq.mm |
| 605 | 4 x 50.0 sq.mm |
| 606 | 4 x 70.0 sq.mm |
| 607 | 4 x 95.0 sq.mm |
| 608 | 4 x 120.0 sq.mm |
| 609 | 6 x 1.5 sq.mm |
| 610 | 6 x 2.5 sq.mm |
| 611 | 8 x 1.5 sq.mm |
| 612 | 8 x 2.5 sq.mm |
| 613 | 10 x 1.5 sq.mm |
| 614 | 10 x 2.5 sq.mm |
| 615 | 12 x 1.5 sq.mm |
| 616 | 12 x 2.5 sq.mm |
| 617 | Supplying and making end termination with heavy aluminium lugs ( Pin / ring type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 618 | 1.5 Sq.mm |
| 619 | 2.5 Sq.mm |
| 620 | 4.0 Sq.mm |
| 621 | 6.0 Sq.mm |
| 622 | 10.0 Sq.mm |
| 623 | 16.0 Sq.mm |
| 624 | 25.0 Sq.mm |
| 625 | 35.0 Sq.mm |
| 626 | 50.0 Sq.mm |
| 627 | 70.0 Sq.mm |
| 628 | 95.0 Sq.mm |
| 629 | 120.0 Sq.mm |
| 630 | 150.0 Sq.mm |
| 631 | 185.0 Sq.mm |
| 632 | 240.0 Sq.mm |
| 633 | 300.0 Sq.mm |
| 634 | 400.0 Sq.mm |
| 635 | 500.0 Sq.mm |
| 636 | 630.0 Sq.mm |
| 637 | 800.0 Sq.mm |
| 638 | 1000.0 Sq.mm |
| 639 | Supplying and making end termination with heavy duty Copper lugs ( ANY type ) confirming to IS 8309 -1993 duly crimped with crimping tool, PVC tape etc of following size. |
| 640 | 1.5 Sq.mm |
| 641 | 2.5 Sq.mm |
| 642 | 4.0 Sq.mm |
| 643 | 6.0 Sq.mm |
| 644 | 10.0 Sq.mm |
| 645 | 16.0 Sq.mm |
| 646 | 25.0 Sq.mm |
| 647 | 35.0 Sq.mm |
| 648 | 50.0 Sq.mm |
| 649 | 70.0 Sq.mm |
| 650 | 95.0 Sq.mm |
| 651 | 120.0 Sq.mm |
| 652 | Supply, Fabricating & installing following sizes of perforated Hot dipped Galvanized iron cable tray ( Galvanized thickness not less then 50 microns) with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. |
| 653 | 100mm x 50mm x 1.6mm |
| 654 | 150mm x 50mm x 1.6mm |
| 655 | 225mm x 50mm x 1.6mm |
| 656 | 300mm x 50mm x 1.6mm |
| 657 | Supply, Fabricating & installing following sizes of perforated Powder coated MS cable tray with perforation not more then 17.5% in convenient section including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with GI suspenders including GI bolts & nuts , fastners, supports etc. as required. |
| 658 | 100mm x 50mm x 1.6mm |
| 659 | 150mm x 50mm x 1.6mm |
| 660 | 225mm x 50mm x 1.6mm |
| 661 | 300mm x 50mm x 1.6mm |
| 662 | 375mm x 50mm x 2.0mm |
| 663 | S & Making Heat shrinkable type Tubular sleeve version outdoor straight through joint for following size of PVC/ XLPE insulated aluminium conductor cable of 1.1 KV grade as required. |
| 664 | 1 x 25 sq.mm-50 sq.mm |
| 665 | 1 x 70 sq.mm-150 sq.mm |
| 666 | 1 x 185 sq.mm-300 sq.mm |
| 667 | 1 x 400 sq.mm |
| 668 | 1 x 500 sq.mm |
| 669 | 1 x 630 sq.mm |
| 670 | 1 x 800 sq.mm |
| 671 | 1 x 1000 sq.mm |
| 672 | 2 x 1.5 sq.mm-6 sq.mm |
| 673 | 2 x 10.0-16.0 sq.mm |
| 674 | 2 x 25.0 sq.mm-50 sq.mm |
| 675 | 2 x 70.0 sq.mm-150 sq.mm |
| 676 | 2 x 185.0 sq.mm-300 sq.mm |
| 677 | 2 x 400 sq.mm |
| 678 | 2 x500 sq.mm |
| 679 | 3/3.5/4 x 1.5 sq.mm-6 sq.mm |
| 680 | 3/3.5/4 x 10.0-16.0 sq.mm |
| 681 | 3/3.5/4 x 25.0 sq.mm-50 sq.mm |
| 682 | 3/3.5/4 x 70.0 sq.mm-150 sq.mm |
| 683 | 3/3.5/4 x 185.0 sq.mm-300 sq.mm |
| 684 | 3/3.5/4 x 400 sq.mm |
| 685 | 3/3.5/4 x500 sq.mm |
| 686 | S/F cable route marker with 10cm x 10cm x 5mm thick or 10 cm dia. G.I.plate with inscription thereon, bolted/welded to 35mm x 35mm x 5mm angle iron, 60cm long and fixing the same in ground in C C ( 1:3:6 ) as required |
| 687 | P / L of Double wall corrugated HDPE pipe confirming to IS : 16205 P-24, Stiffness Class 750 N, Externally corrugated and having smooth surface inside with HDPE Coupler, Elbow, Tee at required Depth below the ground for laying cable of following Nominal Outer dia. MFR Test report from NABL accrediated is to be submitted.(Excavation of trench, CC Haunching, Back filling of Earth with compaction is to be Paid Extra). |
| 688 | 50 mm |
| 689 | 63 mm |
| 690 | 75 mm |
| 691 | 90 mm |
| 692 | 110 mm |
| 693 | 120 mm |
| 694 | 160 mm |
| 695 | 200 mm |
| 696 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 11 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC pipe / Hume Pipe/ Stoneware Pipe/ PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 697 | 3 core 95.0 Sq.mm |
| 698 | 3 core 120.0 Sq.mm |
| 699 | 3 core 150.0 Sq.mm |
| 700 | 3 core 185.0 Sq.mm |
| 701 | 3 core 240.0 Sq.mm |
| 702 | 3 core 300.0 Sq.mm |
| 703 | Providing & Laying XLPE insulated three core Armoured Aluminium cable for working voltage 33 K.V.(E) confirming IS :7098 P - 2 with H4- Grade electrolytic aluminium conductor confirming to IS: 8130 class-2 of purity >99.6 %, Insulation Screening: Extruded Semiconducting Compound followed by helically wrapped Copper Tape, round / flat strip armouring of cables , Inner / outer sheath PVC type ST-2 confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray (with cable tie) including testing etc. as required of following size. |
| 704 | 3 core 150.0 Sq.mm |
| 705 | 3 core 185.0 Sq.mm |
| 706 | 3 core 240.0 Sq.mm |
| 707 | 3 core 300.0 Sq.mm |
| 708 | Excavation of trench of size 120 cm (Depth) x 35 cm(Width) for Laying of suitable no. of HT cable( Inter spacing between cables should not be less than 2 D) in ground with following procedure:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay the cable in the middle of the trench, (c) Provide river sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.), (e) Backfill the excavated soil leaving 300 mm from the Ground level, (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 709 | Add Extra in Item no. 13.3 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 710 | Add Extra for Laying of one number additional XLPE power cable of 11/33 KV (Earthed) voltage grade direct in ground in the same trench in one tier horizontal formation including excavation of trench of size additional 20 cm in width, with procedure as per following points:- (a) Make a river sand bed of height 125 mm along the trench, (b) Lay another cable in middle of trench in such manner that spacing between another cable is 20 cm, (c) Provide sand bed of height 125 mm on top of the cable. (d) Lay the protective Common burnt clay F.P.S. Bricks of Class designation 75 / Sand stone slabs of 50 mm thickness and 225 mm wide just above the sand bed vertically across the cable ( Approx. 9 no. Bricks per Mtr.) (e) Backfill the excavated soil leaving 300 mm from the Ground level. (f)Lay the Cable warning tape and again back-fill the remaining portion of the trench upto the ground level and compacting the earth |
| 711 | Add Extra in Item no. 13.5 if Excavation done in Hard Rock / CC road / TAR Road and making Good the same |
| 712 | Providing & making heat shrinkable type indoor/outdoor/straight through terminations/ joint kit suitable for 11 KV / 33 KV (Earthed) cable with required components, prepration of cable ends. Type test report should be as per IS13573:2011 including testing etc. as required of following sizes. |
| 713 | 11 KV End Termination Kit Indoor type |
| 714 | 3 core up to 35 Sqmm |
| 715 | 3 core 50/70/95 Sq.mm |
| 716 | 3 core 120/150/185 Sq.mm |
| 717 | 3 core 240/300 Sq.mm |
| 718 | 3 core 400 Sq.mm |
| 719 | 11 KV End Termination Kit Outdoor type |
| 720 | 3 core up to 35 Sqmm |
| 721 | 3 core 50/70/95 Sq.mm |
| 722 | 3 core 120/150/185 Sq.mm |
| 723 | 3 core 240/300 Sq.mm |
| 724 | 3 core 400 Sq.mm |
| 725 | 11 KV Straight Through Joint Kit |
| 726 | 3 core up to 35 Sq.mm |
| 727 | 3 core 50/70/95 Sq.mm |
| 728 | 3 core 120/150/185 Sq.mm |
| 729 | 3 core 240/300 Sq.mm |
| 730 | 3 core 400 Sq.mm |
| 731 | Pipe Earthing as per IS:3043- 1987 with 3.0 Mtr. Long, 40 mm dia. ' B ' class G.I. Pipe IS: 1239 (Part-1) 2004, Equivalent to BS : 1387 with perforated holes of 12 mm dia ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 732 | Plate Earthing as per IS:3043 with Hot dipped G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 733 | Plate Earthing as per IS:3043 with copper Earth plate of purity >95% of size 600mm x 600mm x 3.0mm by embodying 3 mtr. below the ground level with 20 mm dia. G.I. 'B' class watering Pipe ,including all accessories like nut, bolts, reducer, nipple, wire meshed funnel, Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. and embodying the pipe complete with alternate layers salt and coke/ charcoal, testing of earth resistance for value of 5 ohms or less as required. |
| 734 | SITC of Copper Bonded rod Earthing with high tensile strength (more than 600 N / sq.mm low carbon steel rod molecularly bonded with Copper thickness (250 microns) and confirming to UL 467 of following size and length and as per point mentioned (a), (b), [c), (d), (e) below :- |
| 735 | (a) Bore a hole of dia. 100 mm of required length, Place the rod in the centre of Hole |
| 736 | (b)Earth enhancing compound to ensure the moisture content and electrical conductivity, 25 kg for 3000 mm. The compound shall be tested form NABL accredited lab for low resistivity (less than 0.12 Ohm - meter) & high conductivity in nature with carbon as a major content in accordance with IEC 62561-7 |
| 737 | © Connect the rod with copper Strip/Conductor/Wire with suitable clamp made from tinned copper and SS 304 Bolt |
| 738 | (d) Place Heavy duty weather proof poly-propylene earth inspection chamber as per requirement of IS/IEC 62305 and tested as per IEC 62561-5 with lockable Jam free lid suitable for safe working load 60 kN of round / square size 250 mm, and Height 250 to 300 mm. |
| 739 | (e) Testing of earth resistance for value of 5 ohms or less as required. |
| 740 | (f) Test certificates for confirming above standards from OEM is mandatory. |
| 741 | 17.2 mm thick and 3 Mtr. Long |
| 742 | 25 mm thick and 3 Mtr. Long |
| 743 | Supply & Laying following size earth strip in horizontal or vertical run in surface by means of Earth strip DMC Insulator including riveting/ soldering/ welding, Jointing shall be done by overlapping double the width of strip and with 2 set of Brass (for Cu strip) / GI (for GI Strip) nut bolt & spring washer spaced at 50cm making connection etc. as required. |
| 744 | 20mm x 3mm copper strip |
| 745 | 25mm x 3mm copper strip |
| 746 | 20mm x 3mm G.I. ( Hot Dipped ) Strip |
| 747 | 25mm x 3mm G.I. ( Hot Dipped ) Strip |
| 748 | Supply & Laying following size earth wire in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection with GI/Cu purity purity >95% thimble etc. as required. |
| 749 | 6 SWG tinned copper Wire |
| 750 | 8 SWG tinned copper Wire |
| 751 | 10 SWG tinned copper. Wire |
| 752 | 6 SWG copper Wire |
| 753 | 8 SWG copper Wire |
| 754 | Supply & Laying following size' B ' class , G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with accessories like bend, socket etc. for laying earth conductor/ strip / cable in ground/ surface/ recess as required. (Earth Excavation will be Paid Extra) |
| 755 | 15 mm dia. |
| 756 | 20 mm dia. |
| 757 | 25 mm dia. |
| 758 | 32mm dia |
| 759 | Making of hole in wall (brick/stone) of required and placing NP-2 RCC pipe ring of required size for housing exhaust fan and making good the same, with cement plaster required of following size. |
| 760 | Up to 457 mm size |
| 761 | more than 457 mm & up to 610 mm |
| 762 | Supply & Fixing of phenolic laminated board of 6.0 mm thick for fresh air fan/exhaust fan up to size of 300 mm on existing window frame including cost of board, cutting of hole , Nut bolts etc. as required. |
| 763 | Providing & Fixing of BEE Star rated copper wounded with class of Insulation 'F', double ball bearing capacitor start, aluminium body & aluminium blade ceiling fan conforming to all the performance requirements laid down in IS 374:2019 with down rod up to 30 cm with secondary support safety cable ( steel rope) , cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor and making connection testing etc. as required. |
| 764 | 1200 mm Sweep BEE 1 Star rated (service value >=4.0 to < 4.5 ) |
| 765 | Providing & Fixing of shackle (iron hook) made from 2mm nominal thick CRCA sheet and bolts (2nos) of 6mm with spring washer nut, checknut & split pin as required. |
| 766 | Providing & Fixing of of M.S. J- hook of standard design made out of 16 mm dia. M.S. round bar and fixed with cement concrete mortar with required support as required. |
| 767 | P & F 1.2 mm thick M.S. Recessed fan box and top lid screwed on Box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 150 mm length extended on each side as required. |
| 768 | Providing & Fixing of of Double ball bearing, copper wounded capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible 3 core 1.5 Sq.mm copper conductor ,making connections, testing etc. as required. |
| 769 | 230 mm sweep, Minimum air delivery 750 Cum / hour |
| 770 | 300 mm sweep Minimum air delivery 1600 Cum / hour |
| 771 | Providing & Fixing of Heavy duty capacitor start, copper wound Double ball bearing 900/1400 RPM single phase Exhaust fan conforming to IS:2312 marked in existing opening including making connections testing etc. as required. |
| 772 | 300 mm sweep(900 RPM) |
| 773 | 380 mm sweep(900 RPM) |
| 774 | 450 mm sweep(1400 RPM) |
| 775 | Providing & Fixing of ventilating fans Capacitor start, copper wounded, single phase with PVC impeller, ABS body, automatic openable louver shutter in existing opening including making connection, testing etc. as required. |
| 776 | 150 mm sweep Minimum Air Delivery 150 Cum / hour |
| 777 | 200 mm sweep Minimum Air Delivery 450 Cum / hour |
| 778 | 250 mm sweep Minimum Air Delivery 750 Cum / hour |
| 779 | Providing & Fixing of Wall mounting / Pedestal type Heavy duty Air Circulator , Double ball bearing and with metal sturdy mesh guard; Aluminium alloy one piece blade and conforming to IS:2997, including fixing with anchor bolts, making connection testing etc. as required. |
| 780 | 450 mm sweep Wall mounting and three speed regulator with Minimum Air Delivery 150 Cum. / Minute |
| 781 | 600 mm sweep Wall mounting with Minimum Air Delivery 270 Cum. / Minute |
| 782 | Providing & Fixing of 450 mm Sweep Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Sintered Iron bush oil impregnated, with metal front and back 120 or more ribs guard; Three no. Aluminium blades, minimum Air delivery 100 Cum. / Minute , Minimum Service Value 1.11 Cum./min/watt, noise level should be <= 75 dB, power consumption <= 120 watts, motor protection through thermal overload protection device, including fixing with anchor bolts, making connection testing etc. as required. |
| 783 | Wall mounting type with Adjustable Vertical Angle |
| 784 | Pedestal Type with Adjustable Height |
| 785 | Providing & Fixing of extra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe including cutting, threading, drilling, fixing quarter pin etc as required. |
| 786 | Providing & Fixing of 400 mm Sweep BLDC technology Oscillating type Wall mounting / Pedestal type fans with Three speed, ON and OFF position, Double Wall bearing with front and back 120 or more ribs guard; Three no. blades, noise level should be <= 75 dB, including fixing with anchor bolts, making connection testing etc. as required. ( With Remote ) |
| 787 | Wall mounting type with Service value 2.0 CMM /W, Min. Air Delivery 71 CMM |
| 788 | P & F of Gravity Louver shutter of superior quality made out of frame of 18 swg M.S. sheet & Louvers made from 24 swg MS Sheet with enamel paint including cost of nuts, bolts, etc as required. |
| 789 | Up to 380 mm size |
| 790 | above 380 mm size |
| 791 | Providing & Fixing BLDC technology step regulator compatible ceiling fan, with aluminium body & aluminium blade, power factor not less then 0.9 , following service value (CMM/W) , with following air delivery , speed 350 RPM ( tolerance as per IS:374 2019 ) THD less then 10%, copper winding with class of Insulation 'F' complete with with secondary support safety cable ( steel rope), down rod up to 30 cm, cotter pin, shackle kit with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. |
| 792 | 1200 mm sweep with Air delivery >/= 230 CMM and Service Value 8.20 |
| 793 | S & F Extruded Aluminium Fresh Air / External Weather Louver, Small Format type with 38 mm flange width & 50 mm depth. finish - powder coated off white with aluminium mesh of required size. |
| 794 | Providing & Fixing of Vertical(BEE 5 star rated) / Horizontal( BEE 3 star rated) storage water heater with outer casing made of Engineering Plastic sheet (Upto 25 Ltr) / Metal rust proof Body (35 & 50 Ltr), Glass - line / Titanium Enamel coated Pressure Pump Compatible 8 bar pressure Inner tank, Glass Line Coated , mineral filled heating element, stem type, snap action adjustable thermostat , Dual indicating lamps Injected PUF insulation, Multi Function Valve etc. as required held in position with 2/4 no. 10/12 mm anchor Fastener, duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top , including making inlet, outlet Flexible alloy connection, testing etc. as required. |
| 795 | 6 Ltr. |
| 796 | 10 Ltr. |
| 797 | 15 Ltr. |
| 798 | 25 Ltr. |
| 799 | 35 Ltr. |
| 800 | 50 Ltr. |
| 801 | Providing & Fixing of stem type ISI marked (IS 3017 / 85) snap action adjustable thermostat for storage water heater including making connection testing etc. complete in all respect. |
| 802 | Providing & Fixing of stem type ISI marked (IS 3017 / 85) , snap action bipolar adjustable thermostat with built in auto thermal cut out for storage water heater including making connection testing etc. complete in all respect. |
| 803 | Providing & Fixing 2 / 3 KW nickle plated, mineral filled heating element including making connection testing etc complete in all respect. |
| 804 | Providing & Fixing of 2 / 3 KW Glass Line Coated , mineral filled heating element including making connection testing etc complete in all respect. |
| 805 | Providing & Fixing of Multi safety valve of 8.5 bar capacity with built in drain, NRV, Vacuum release, Pressure release etc. as required complete in all respect. |
| 806 | Providing & Fixing of Twin neon indicating lamp of superior quality for storage water heater complete in all respect. |
| 807 | Providing & Fixing of 13 mm Brass with C.P. finished ISI marked angle valve for storage water heater as required complete in all respect. |
| 808 | Providing & Fixing of heavy duty flexible alloy pipe for storage water heater for inlet and outlet of suitable length including the cost of nuts, washers etc complete in all respect. |
| 809 | 450 mm |
| 810 | 600 mm |
| 811 | Charges for descaling of storage water heater including replacement of Multi Function Valve as required. |
| 812 | Charges for Fixing of storage water heater including 10/12 mm Anchor fasteners of suitable size, testing, carrying from store to site,etc. as required. |
| 813 | Providing & Fixing of 2.0 KW twin ceremic cartridge, Withstands temperatures up to 1000 C long lasting even in hard water including making connection testing etc complete in all respect. |
| 814 | SITC of IP20 SMD Mid Power LED batten type integrated light fixture made from Powder coated Extruded aluminium housing with in built driver , System lumen efficacy ≥ 110 lm/Watt output only at CW (5700K to 6500K) , internal surge protection of 4.0 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 815 | 1170mm(+/-10%) LED batten with min. lumen output 2200 lm |
| 816 | 570mm (+/-10%) batten with min. lumen output 1000 lm |
| 817 | 1170mm(+/-10%) LED batten with min. lumen output 4400 lm |
| 818 | SITC of IP20 SMD Mid Power LED batten with integrated box (min.1200mmx40mmx60mm including reflector) with replacable driver fixture made from Powder coated Extruded aluminium housing ,Min. lumen output 4800 lm, System lumen efficacy ≥ 120 lm/Watt output nly at CW (5700K to 6500K), internal surge protection of 4.0 KV with Short & Open circuit protection,THD < 10% , P. F.≥0.95, CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 819 | SITC of IP-20 LED Recessed / Surface Mounted, Round / Square backlit & SMD Mid Power LED Downlight with power coated die-cast aluminum housing with UV Stabilized non yellowish Diffuser with BIS compliance 4.0 KV surge protected Isolated driver, with Short & Open circuit protection input 320VAC-48 hr protection, input 350VAC-2 hr protection), having efficiency > 85% . System Lumen efficacy of ≥ 110 lm / watt,at CW (5700K to 6500K) , THD < 10 % , Pf.≥0.95, CRI >80, life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 820 | Recessed Mounting |
| 821 | Minimum lumen output 600 lm (lumen efficacy ≥ 100 lm / watt) |
| 822 | Minimum lumen output 1300 lm |
| 823 | Minimum lumen output 1600 lm |
| 824 | Minimum lumen output 1950 lm |
| 825 | Minimum lumen output 2400 lm |
| 826 | Surface Mounting (with extruded alumn. Housing ) |
| 827 | Minimum lumen output 600 lm (lumen efficacy ≥ 100 lm / watt) |
| 828 | Minimum lumen output 1300 lm |
| 829 | Minimum lumen output 1600 lm |
| 830 | Minimum lumen output 1950 lm |
| 831 | Minimum lumen output 2400 lm |
| 832 | SITC of IP20, 2'x2' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmissivity UV stabilized Non -yellowish diffuser for uniform light distribution. operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V . High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection ( input 320VAC-48 hoursprotection,input 350VAC-2 hours protection) (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 833 | Recessed Mounting |
| 834 | Minimum lumen output 4320 lm |
| 835 | Minimum lumen output 4800 lm |
| 836 | Surface Mounting (Driver should be Inside the Luminaire) |
| 837 | Minimum lumen output 4320 lm |
| 838 | Minimum lumen output 4800 lm |
| 839 | SITC of IP20, 1'X1' LED Surface/ Recessed mounting backlit & SMD Mid power type LED Light fixture not less than 35 mm housing depth made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution.operating voltage range 140-285 V, HV cutoff - LV cutoff should be 300-100V High efficiency with 4 KV internal surge protection BIS certified isolated driver having efficiency > 85% , with Short & Open circuit protection (Integral with light fixture). System lumen efficacy of ≥ 120 lm/Watt ,THD < 10 % , p.f.≥0.95,CRI >80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 840 | Recessed Mounting |
| 841 | Minimum lumen output 2880 lm |
| 842 | Minimum lumen output 3600 lm |
| 843 | Surface Mounting (Driver should be Inside the Luminaire) |
| 844 | Minimum lumen output 2880 lm |
| 845 | Minimum lumen output 3600 lm |
| 846 | SITC of IP65 IK08 rated Integrated High power LED ( each LED between 3 to 5 watt power with secondary lencs on each LED) Highbay light fixture made from Pressure Die Cast Aluminium housing, UV stabilized PC Cover/ Toughened glass diffuser, potted driver, Eye bolt for mounting, system lumen efficacy ≥150 lm/Watt output , THD < 10% ,p.f.≥0.95,CRI >70 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and . surge protection 4 KV inbuilt & 10 KV external inside fixture as required. |
| 847 | Minimum lumen output 12000 lm |
| 848 | Minimum lumen output 15000 lm |
| 849 | SITC of energy efficient /energy saving IP 20 LED direct retrofit Bulb in existing holder or fixture as required with system lumen efficacy ≥100 lm/Watt output ,pf 0.95 , CRI >70, minimum life time of minimum 25000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) as required. |
| 850 | 9 Watt |
| 851 | 15 Watt |
| 852 | 18/20 Watt |
| 853 | SITC of IP 20 box made out from 1.0 mm thick CRCA sheet steel with depth of minimun 30 mm and finished with powder coating and suitable for mounting LED tube including side covers, holders , internal wiring to illuminate the single sided connection LED tube. ( Without tube). |
| 854 | Suitable for 2' LED Tube shape fixture for single rod |
| 855 | Suitable for 4' LED Tube shape fixture for single rod |
| 856 | Suitable for 4' LED Tube shape fixture for double rod |
| 857 | Supply and Fixing of Pole OEM fabricated hot dipped galvanised M.S. Overhang (48.3 X 3.25 mm) with cap ( 250x 88.9 / 114.3 x 3.25 mm) over the existing poles. |
| 858 | Single arm overhang |
| 859 | Double arm overhang |
| 860 | Supply and erection of Galvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular/ Conical cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, The base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have hinged lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 for Octagonal & P-02 for Conical with base plate and foundation bolt on the Existing cement concrete foundation. To ensure quality of product it's entire manufacturing process starting from sheet cutting to galvanization sould be done under one premises. |
| 861 | Poles with Octagonal/Conical Cross Section |
| 862 | 3 Mtr. |
| 863 | 7 Mtr. |
| 864 | Add for supply and fixing of Pole OEM fabricated Galvanized Overhang of following size over the existing poles. |
| 865 | 88.9 mm OD x 3.25 mm thickness |
| 866 | Supply installation testing & Commissioning of high mast lighting system (as per PLG 07 of ILP UK techinical report no 7 of ILE UK /IS:875 Part-1 – 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by piecewise single dipped method high mast, lantern carriage suitable for up to 18 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction light, double drum type self sustaining winch, integral power tool accessible from door with padlocking arrangement (winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, Stainless steel 6 mm dia. wire ropes (AISI 316, 7 / 19 costruction 3 no. rope for lantern carrage & 2 no. rope for winch assembly ) foundation bolt, torque limiter,EPR insulated PCP sheathed 5 core x 2.5 Sq.mm trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135.etc. as required including cost of RCC Foundation as per OEM Design & Drawings . ( See table P - 04 for specs.) To ensure quality of the product, OEM Must have Type test certificate for wind tunnel test from IIT. Entire manufacturing process starting from sheet cutting to galvanization should be done under one premises Inhouse galvanizing plant shall have bath length not less then 12.0 mtr to ensure the quality of galvanization . |
| 867 | 12.5 Mtr HM (in 2 section) suitable for 6 No. Luminaries 2 no. rope for lantern carrage & 2 no. rope for winch assembly |
| 868 | 16.0 Mtr HM (in 2 section) |
| 869 | 20.0 Mtr Hm (in 2 section) |
| 870 | Providing and Laying RCC Foundation for Octagonal / Conical Street Light poles as per Drawing attach at Table P-05 with Following Procedure |
| 871 | A) Excavation of Pit for Foundation Size upto required depth from Ground level |
| 872 | B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete. |
| 873 | C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness |
| 874 | D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete. |
| 875 | E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal |
| 876 | F) Providing & Fixing of 2 no. Required Size PLB HDPE Pipe & Foundation Bolt with template as per OEM Recommendations. |
| 877 | G) Providing and Laying Reinforce cement Concrete of M-20 grade in Footing and Pedestal including Curing the foundation for minimum 7 days. |
| 878 | H) Providing and Fixing Nosing Angle 25 mm x 25 mm x 3mm with 2 no. of 100 mm long, 6 mm dia fastener |
| 879 | Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr. |
| 880 | Pole Foundation for Octagonal pole from 7 Mtr. To 9 Mtr. |
| 881 | Providing & Fixing of IK07 IP65 protected Top/Bottom mounted LED Post top Luminarie top & bottom made of single piece construction powder coated die cast alluminium housing with UV stabalized Clear / frosted Polycarbonate diffuser and Aluminium anodised with powder quoted reflector. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED Driving output current <750mA as required. |
| 882 | Minimum lumen output 2800 lm Post top Luminarie |
| 883 | Minimum lumen output 3200 lm Post top Luminarie |
| 884 | Minimum lumen output 3600 lm Post top Luminarie |
| 885 | Providing & Fixing of IK08 IP-66 protected high power LED flood light system with single piece Pressure diecast aluminium housing, toughened glass with suitable lenses on LED / integrated lens diffuser to achieve various beam angles, of high power LED of 3 to 5 watt each . Integrated metal case potted driver as a unique BIS R number (as per IS 15885) having efficiency more than 85 % and in compliance to BIS certified and Trade mark certificate(Fitting & driver both have separate BIS R number). The System level Luminaire efficacy >=130 lm/ wt. LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety .Power Factor >0.95 , THD(I) <10% , LED driving output current <=750mA. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector , Surge Protection Min >=4KV internal and 10KV external but inside driver compartment, System life of 50000 Burning hours with 70% of Initial Lumens maintained, CRI>70 and CCT 5700K ±355K as required. |
| 886 | High Power LED Flood Light Minimum lumen outpu 3900 lm |
| 887 | High Power LED Flood Light Minimum lumen output 6500 lm |
| 888 | High Power LED Flood Light Minimum lumen output 10400 lm |
| 889 | High Power LED Flood Light Minimum lumen output 13000 lm |
| 890 | High Power LED Flood Light Minimum lumen output 15600 lm |
| 891 | High Power LED Flood Light Minimum lumen output 19500 lm |
| 892 | High Power LED Flood Light Minimum lumen output 23400 lm |
| 893 | High Power LED Flood Light Minimum lumen output 26000lm |
| 894 | High Power LED Flood Light Minimum lumen output 32500 lm |
| 895 | Providing & Fixing of IK08, IP 66 protected LED Street Light Luminaire on existing bracket/pole. Fixture made of powder coated single piece pressure die cast aluminum material with heat dissipation fins on housing with UV stabilized PC (UV stablization report submitted for UV cover ) /Toughened Glass cover and secondary lens on each LED/ integrated lens diffuser & should be High power LED of 3 to 5 watt each . The System efficacy >=125 lm/ wt and integrated metal case potted driver & has a unique BIS R number ( as per IS 15885) with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC & Low Voltage cutoff @>=90 V AC and Auto resetting Safety , Power Factor >0.95 driver Efficiency >85% ,THD(I) <10% Humidity 10% to 90% RH Working Temp -5C to 45C . LED driving output current <750mA. The luminaire shall be BIS certified (Fitting & driver both have separte BIS R number) and Trade mark certified. Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintened , CRI >70 and CCT 5700K +355K. Surge protection shall be min ≥ 4 KV internal and min 10 KV external inside driver compartment. driver should be Phase to phase protection of 440 V for 4 Hrs as required. |
| 896 | LED Street Light fixture with Minimum lumen output 2500 lm |
| 897 | LED Street Light fixture with Minimum lumen output 3750 lm |
| 898 | LED Street Light fixture with Minimum lumen output 5625 lm |
| 899 | LED Street Light fixture with Minimum lumen output 7500 lm |
| 900 | LED Street Light fixture with Minimum lumen output 8750 lm |
| 901 | LED Street Light fixture with Minimum lumen output 11250 lm |
| 902 | LED Street Light fixture with Minimum lumen output 12500 lm |
| 903 | LED Street Light fixture with Minimum lumen output 15000 lm |
| 904 | Providing & Fixing of IK08 IP65 protected 600-800 mm height LED Bollard Luminarie with base plate made of powder coated die cast aluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 80 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 90-270V AC at 50Hz. System life of 30000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. LED driving output current <750mA. as required. |
| 905 | Minimum lumen output 800 lm Bollard |
| 906 | Minimum lumen output 980 lm Bollard |
| 907 | Providing & Fixing of IK08 IP66 / IP67 protected Rectangular shape LED Step Luminarie made of powder coated die cast alluminium housing with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 60 Lumen/W. SMD LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<20% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained . driver current <750mA as required. |
| 908 | Minimum lumen output 450 lm Step light |
| 909 | Minimum lumen output 630 lm Step light |
| 910 | Minimum lumen output 800 lm Step light |
| 911 | Providing & Fixing of IK08 IP65 / IP66 protected LED Up - Down Luminarie Wall / Surface mounting made of powder coated die cast alluminium housing with with UV stabalized PC diffuser. The System level Luminous efficacy ≥ 80 Lumen/W. COB LEDs is to be used, System CRI>70, CCT: 3000/4000/6500 K. The integral electronic driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.9, THD<10% and input Voltage range of 140-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained Light output in Cool white or Warm White Colour as per engineers choice. LED driving output current <750mA. as required. |
| 912 | Minimum lumen output 800 lm Up-Down Luminary |
| 913 | Minimum lumen output 1300 lm Up-Down Luminary |
| 914 | Minimum lumen output 2150 lm Up-Down Luminary |
| 915 | Providing & Fixing of Street light bracket made out from following size of ' B ' class , Medium class G.I. Pipe confirming to IS : 1239 P - 1 ( 2004 ) with heavy duty pole clamp, Saddles suitable fastners etc. as required. |
| 916 | 20 mm Dia. |
| 917 | 25 mm Dia. |
| 918 | 32 mm Dia. |
| 919 | 40 mm Dia. |
| 920 | Providing & Fixing of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures with knock out for cable entry/out including fixing with nut, bolt, fatner etc as required complete in all respect of following sizes. |
| 921 | 180 x 180 x 91 mm |
| 922 | 250 x 200 x 115 mm |
| 923 | 300 x 450 x 132 mm |
| 924 | 320 x 440 x 179 mm |
| 925 | 320 x 640 x 179 mm |
| 926 | Supply and erection of PU coated , 6 to 7 mm thick Glass / Fibre Reinforced Pole (GRP /FRP) made by CNC filament winding machine using thermoset resin polyester/epoxy resin system) having minimum 62% glass content. designed to withstand the maximum wind speed as per IS 875, and Tested for deflection not more than 15% length of pole as per ASTM D 4923, The pole should be in one piece and tapered round in shape, pole shafts shall be provided with FRP Anchor with suitable MS cated Base with provision for fixing 4 no. foundation bolts( Including cost of Foundation Bolt), The Pole shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension on Existing cement concrete foundation . |
| 927 | 3 Mtr. Long, Top/ Bottom OD Dia 89/126mm ± 2mm approx. With Base 250X250 X 10mm |
| 928 | Providing & Fixing of IK10/ IP66 protected pole mount LED Post top Luminarie top & bottom made of single piece construction powder coated pressure die cast alluminium housing with High purity PC diffuser, downward illumination to control light pollution. The System level Luminous efficacy ≥ 120 Lumen/W. SMD LEDs is to be used, System CRI>/=70, CCT: 4000/5700 K. Driver must be potted & has a unique BIS R number constant current and Internal/external surge protection device of min. 4KV(L-N) and efficiency > 85%, PF>0.95, THD<10% and with Input Voltage AC 120 to 270 V AC with High voltage Cutoff @>=300 V AC and Auto resetting Safety, driver should be Phase to phase protection of 440 V for 4 Hrs. System life of 50000 Burning hours with 70% of Initial Lumens maintained . LED driving current <750mA. Mounting pole diameter 060mm, The Luminaire dimension min Dia 450mm x 200mm(H). including making connections etc. as required. |
| 929 | Minimum lumen output 5000 lm Post top Luminaire |
| 930 | Minimum lumen output 6000 lm Post top Luminaire |
| 931 | Labour charges for installation of submersible motor pump set including lowering/ delowering of pipes, cables, accessories etc. in tube-well/ open well complete including T&P, transportation of tripod, chain pulley block & any other material required for this purpose complete in all respect. |
| 932 | Lowering only |
| 933 | Delowering only |
| 934 | Delowering and Lowering |
| 935 | SITC of Radial / mixed flow water and anti-corrosive liquid filled submersible motor pump sets suitable for 100/150mm dia borewell. The size of adopter fixed on top of the motor should exceed the top of coupler , for safegaurd the coupler. The job includes labour part of lowering of riser pipe G.I./ H.D.P.E. with rope, cables & pump, installation of complete fitting and accessories, jointing of electrical cables up to Starter. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect. |
| 936 | 100 mm diameter Submersible pump shall have following HP Rating, phase, Head range, Discharge range respectively. |
| 937 | 1.0 HP, 1-Ø, (10 - 83)Mtr, (40- 10) LPM |
| 938 | 1.5HP, 1-Ø, (11 - 94)Mtr, (40 - 10) LPM |
| 939 | 2.0 HP, 1-Ø, (7- 95)Mtr, (55-22) LPM |
| 940 | 3.0 HP, 1-Ø, (40 -170)Mtr, (60- 20) LPM Copper Wound |
| 941 | 5.0 HP, 1-Ø, (56 - 236)Mtr, (90 - 25) LPM Copper wound |
| 942 | SITC of Monoblock closed coupled motor pump set with TEFC motor, motor should be IP55-F class and IE2 efficiency for monobloc, with carbon steel /SS-410 shaft, Mechanical seal, Single/Three phase Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively and Dynamically balanced rotating parts to ensure min. vibration etc. complete in all respect. |
| 943 | 5.0 HP, 3-Ø, (19-44)Mtr, (550-300) LPM ( Bronze impeller & CI Body) |
| 944 | SITC of Pressure boosting pump with MS Tank, pressure switch, pressure gauge, and all standard fittings fully automatic ON / OFF system, 2900 RPM with stainless steel casing, & impellor suitable for following capacity complete in all respect. |
| 945 | 0.5 HP ( 12 - 26 ) Mtr, (50 - 10 ) with 8 Ltr tank |
| 946 | 0.75 HP -0.90 HP ( 10 - 34 ) Mtr, (72 - 5 ) LPM with 24 Ltr Tank |
| 947 | 1.0 HP ( 10 - 38 ) Mtr, (76 - 8 ) LPM with 24 Ltr Tank |
| 948 | Providing & Fixing of CI foot valve complete in all respect as required. |
| 949 | 50/ 60 mm |
| 950 | 80/ 100 mm |
| 951 | Supply & fixing of GI pipes confirming to IS : 1239 P - 1 ( 2004 ) with socket,elbow,tee, flanges duly screwed & welded including rubber washer, nuts & bolts of 8mm dia complete in all respect. ( If Pipe Laid Underground Excavation and refilling cost will be paid extra) |
| 952 | 32mm dia |
| 953 | 40 mm dia. |
| 954 | 50 mm dia. |
| 955 | 65 mm dia. |
| 956 | 80 mm dia. |
| 957 | 100 mm dia. |
| 958 | SITC of IP 54 OEM Fabricated DOL/Star-Delta Starter panel with switchgear selection as per Type-2 Coordination Chart and made out from 1.6 mm thick powder coated CRCA sheet, enclosure comprising of over load protection relay, short circuit & single phasing protection(for three phase pumps), Illuminated ON / OFF push buttons, ammeter, voltmeter, indicating lamps, 2P/4P MCB etc. suitable for following rating motors complete in all respect. |
| 959 | For single phase Submersible / Monoblock pump |
| 960 | 0.5 HP to 1.5 HP (DOL starter) |
| 961 | 2.0 HP to 3.0 HP (DOL starter) |
| 962 | 5.0 HP (DOL starter) |
| 963 | For Three phase Submersible / Mono block pump |
| 964 | Upto 3.0 HP ( DOL starter ) |
| 965 | 3.0 HP to 5.0 HP ( DOL starter ) |
| 966 | 7.5 HP to 10.0 HP ( DOL starter ) |
| 967 | 3.0 HP to 5.0 HP ( Star / Delta starter ) |
| 968 | 7.5 HP to 10.0 HP ( Star / Delta starter ) |
| 969 | SITC of Interconnecting refrigerant copper pipe for split/Ductable/ Casseette AC of DHE Grade C12200- ASTM B68, B75, chemical composition of copper %- 99.0 Min and Phosphorus %- 0.015 to 0.040 . For Annealed copper tube :- Tensile strength = 210 Mpa wih elongation % = 40 Min . Ink Mark Brand Printing on Hard Tubes should be present. Piping between each set of indoor & outdoor units of different sizes as per OEM requirement & specifications including class 'O' Nitrile rubber sleeves (size as per item no. 22.43),7 mil Glass Cloth with 3 coats of anti UV paint (on area which is exposed to weather) chase cutting, supports, making good the same with sand cement plaster etc. as required. |
| 970 | Charges for oiling, overhauling of ceiling fan, table fan, pedestal fan irrespect to the size of fan including removing,refixing of fan from site and testing etc. as required. |
| 971 | Fans w/o Removing & Refixing |
| 972 | Fans with Removing & Refixing at Suitable Location |
| 973 | Providing and Replacement of ball bearing of ceiling/ exhaust fan and refixing the same at suitable location as requiredand as per OEM recommendations. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material shall be retained by the contractor. |
| 974 | Replacement of existing transformer oil confirming to IS: 335 after removing of old oil and remove from site (old oil shall be retained by the contractor) |
| 975 | Charges for Collection , Filtration and dehydration of existing transformer oil with the help of high vaccum filtration machine and cleaning of core-coil assembly by hot oil for removal of sludge / dust particles etc. as required. |
| 976 | Supplying and charging of fresh refrigerant and testing of performance of air conditioner/ fridge/ water cooler of following capacity including capallary and strainer/ filter. |
| 977 | 1.5 TR Window/ Split A.C. |
| 978 | S & F of capacitor of 230V/ 275V, 50Hz rating of plastic casing and terminals -Lugs or copper wire. |
| 979 | Running capacitor |
| 980 | 2.5/3.15 micro farad |
| 981 | Rewinding of single phase/3phase submersible motor including all necessary material and of the same characteristics as original with required size of super enamelled wire 'E' class insulation material and testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 982 | 0.5 H.P. To 1.0 H.P. |
| 983 | 2.0 H.P. |
| 984 | Above 3.0 HP to 5.0 HP |
| 985 | From7. 5 HP to 10.0 HP |
| 986 | Repairing of submersible pump of with replacement of broken impellers ,diffuser,bush/bearing set , oil seal complete with testing etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 987 | 0.5 H.P. To 1.0 H.P. |
| 988 | 2.0 H.P. |
| 989 | Above 3.0 HP to 5.0 HP |
| 990 | From7. 5 HP to 10.0 HP |
| 991 | Repairing of LT/HT bushings of Distribution Transformers including replacement of brass studs , porcelain insulators , nut bolts , oil seals , gaskets etc. complete as required complete in all respect. . |
| 992 | LT Bushing Set |
| 993 | 63 KVA |
| 994 | 100 KVA |
| 995 | 160 KVA |
| 996 | 200 KVA |
| 997 | 250 KVA |
| 998 | 315 KVA |
| 999 | 400 KVA |
| 1000 | 500 KVA |
| 1001 | 630 KVA |
| 1002 | 800 KVA |
| 1003 | 1000 KVA |
| 1004 | 1250 KVA |
| 1005 | 1600 KVA |
| 1006 | HT Bushing Set |
| 1007 | 63 KVA to 500 KVA |
| 1008 | 630 KVA to 1600 KVA |
| 1009 | Replacement of Silica gel Breather of Distribution Transformers of following capacities complete in all respect. . |
| 1010 | 63 KVA |
| 1011 | 100 KVA |
| 1012 | 160 KVA |
| 1013 | 200 KVA |
| 1014 | 250 KVA |
| 1015 | 315 KVA |
| 1016 | 400 KVA |
| 1017 | 500 KVA |
| 1018 | 630 KVA |
| 1019 | 800 KVA |
| 1020 | 1000 KVA |
| 1021 | 1250 KVA |
| 1022 | 1600 KVA |
| 1023 | Replacement of gasket of Distribution Transformers of following capacities complete in all respect. . |
| 1024 | 63 KVA to 500 KVA |
| 1025 | 630 KVA to 1600 KVA |
| 1026 | Earth work in excavation/ by mechanical means (Hydraulic Excavator) / Manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: |
| 1027 | Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with Cement Mortar 1:6 ( 1-Cement : 6-Sand). |
| 1028 | Rewinding of Heavy duty Exhaust fan motor including all necessary material,The motor is to be wound taking no. of coils,turns and pitch as it was originally wound with required size super enamelled wire with 'E' class insulation material and making connections etc. as required. Replacement of material or components shall be use as per guidelines of OEM of original product. All the scrap material should be retained by the contractor. |
| 1029 | 300/ 380 mm sweep |
| 1030 | 450 mm sweep |
| 1031 | Hire charges for Cable fault locator machine with manpower for detecting fault in underground cable of LT 1.1 KV grade or 11/33KV HT cable |
| 1032 | for 1st day |
| 1033 | All in all comprehensive maintenance of 11/0.415 KV or 33/0.415 KV Distribution sub station including 11 KV circuit Breaker , Transformer and its complete accessories , Auto transfer switch ,repairing of LT/HT cables with terminations, LT panel with complete accessories , Sub station Earthings etc with maintaining of Log Books complete in all respect but excluding of transformer oil as and when required. |
| 1034 | Substation Up to 500 KVA rating Transformer |
| 1035 | Substation Above 500 KVA Transformer |
| 1036 | Substation with 33/11 KV Transformer |
| 1037 | All in all comprehensive maintenance including servicing , replacement of fuel - filter, coolant , lubricating oil etc of Diesel Generating set including auto mains failure (AMF) panel , change over switch , earthing etc as per OEM guidelines and maintenance manual complete in all respet. (Excluding replacement of batteries as and when required.) |
| 1038 | Up to 62.5 KVA D. G. Set |
| 1039 | Above 62.5 KVA |
| 1040 | OEM approved liquid urea for BS-IV type DG Set |
| 1041 | All in all comprehensive maintenance of Automatic power factor correction panel including repair / replacement of defective componenets to maintain the power factor as per Discom's permissible limit and without any penalty or surcharge. |
| 1042 | Up to 125 KVAR APFC Panels |
| 1043 | Above 125 kvar APFC Panels |
| 1044 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level |
| 1045 | 1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) |
| 1046 | Plaster on new surface on wall in cement sand mortar 1:4 including racking of joints etc. complete fine finish : |
| 1047 | 20mm thick |
| 1048 | 12mm thick |
| 1049 | Providing and fixing welded mesh/expanded metal mesh 25 mmx 25 mm x 3mm in frame work, flat iron beading 20x3mm including top cross laps inside and out sides welding, iron bolts, crews, clips etc. including two coat of red oxide and two coat of enamel paint or more required complete with frame work with 50 X 50 X 6mm angle iron post 30 cm in ground embeded in cement concrete 1:3:6 (30X30X45cm) at corner and every three mtr including painting with one coat of primer and two coat of enamel paint work will be done as per direction of engineer incharge of size complete in all respect. . |
| 1050 | Gravelling of Transformer / RMU Yard with 100 mm Height Gravels of Size 20 to 25 mm including leveling, Dressing etc. as Required. |
| 1051 | SITC of 11kV 630 Amps 21KA for 3 Sec. SF6 insulated, outdoor duty (IP54) , Extensible / Non extensible type Ring main unit (RMU) manually operated in combination of VCB modules and Load Break switch consisting of Copper busbar in SF6 insulated stainless steel Outdoor enclosure of thickness of 2 mm and tank of stainless steel Outdoor enclosure of thickness 3mm with manometer. The HV switchgear and control gear should be confirming to IEC-62271-100, IEC-62271-200-2003 & IEC-60694-1996. The RMU should be internal arc tested for 21KA for 1Second with IAC-AFL classification for both Cable chamber and gas tank as per IEC 62271-200 and LBS to be rated for class E3 as per IEC 62271 - 103. Vacum Interrupter should be same as used during type test of RMU. Each feeder of RMU should have voltage presence indicator. and VCB feeder should consist of 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder, 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB.Load break switch feeder shall have Fault Passage indicator, Right angle boots for all the feeder Modules, Remote trip, Emergency Stop, Cable cover interlocking, Trasnformer protection tapo card etc. All the type test certificates as per IEC and CEA from Third party NABL / CPRI / ERDA accrediated lab to be submitted. (Cost of RCC Foundation / Steel Structure to be paid Extra) |
| 1052 | Extensible 3 way RMU with 1 no. VCB & 2 No. Load Break Switch |
| 1053 | Extensible 2 way RMU with 1 no. VCB & 1 No. Load Break Switch |
| 1054 | Extensible 1 way RMU with 1 No. VCB & Direct Cable Entry. |
| 1055 | Coupling Assembly to connect two different RMUs. |
| 1056 | S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11,ONAN Cooled & as per BEE star - 1 ( Correspnding level as per BIS amended upto date of receipt of tender) & BIS approved as per IS 2026- 1977 & losses as defined as per 2014 (Fourth Revision) Level-1 including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cable boxes, temperature rise in winding/oil 35-40 degree C upto 200 KVA & 40-45 degree C for above 200 KVA, ISI marked drain valve, Dial type Temperature gauge, first filling of transformer oil as per IS :335-1953, Epoxy based paint, undirectional rollers as required including carrying of pre-commission Testing & Charging of Transformer complete in all respect . Factory Tests : The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) in OEM's own lab and same shall be witnessed by Department engineer. Site Tests : Following tests shall be carried out on each transformer at site by OEM engineer in presence of department's site engineer:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. Transformer shall be tested from CTL of discom before charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor) |
| 1057 | Note :Manufacturer's testing laboratory should be certified by NABL and have an in house core cutting facility to ensure proper control & monitoring of quality. This is crutial to prevent the mixing of prime core materials with Second grade or defective materials. The core should be constructed from high grade, non ageing, PRIME GRADE CRGO steel with M4 Grade or Better, using silicon steel laminations, and should be of boltless design. The core and coil assembly should be undergo drying process using a highly efficient vacuum drying autoclave to remove moisture through heating and drying. |
| 1058 | 315 KVA with Off -LTC (+5% to - 10% @ 2.5%) with % impedance 4.5 |
| 1059 | Add: GST@18% EXTRA Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Nov 02, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 12, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysNov 13, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 8 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender