Defence Statutory Bodies & Commissions/Committees Closing in 17 days TDR #58320704

Tender For special Repairs/Replacement Of Perimeter Security Lights Network From Tcp-04 To Alpha Mess At Dipatoli Mil Stn Under Ge Dipatoli

Issued by Statutory Bodies & Commissions/Committees · Ranchi, Jharkhand
Tender Value
29.13 Lakhs
Estimated cost
Bid Submission
21 Nov 2026
17 days left
EMD
58260
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Ranchi → Jharkhand
EMD Exemption
Available
Quantity
Not Available

Project Description

Tender for special Repairs/Replacement Of Perimeter Security Lights Network From Tcp-04 To Alpha Mess At Dipatoli Mil Stn Under Ge Dipatoli

BOQ

Name of Work:- SPL REPAIRS/REPLACEMENT OF PERIMETER SECURITY LIGHTS NETWORK FROM TCP-04 TO ALPHA MESS AT DIPATOLI MIL STN UNDER GE DIPATOLI
Sl. No. Item Description
1S & F in replacement Pressure die cast aluminum alloy housing LED street light fitting 90 Watt comprises of pressure die cast Aluminium housing & having system efficiency 110 lumens/Watt i.e 6670 lumns,All LEDs should be highpower LEDs of 1W to 3W Only with moduler lens for batwin shape distribution of 30 degree & 60 degree,Input voltage working range is 140 Vac to 270 Vac,Brand name should be emoboised,Potted Driver is used with 4KV internal & external 5KV Potted surge protection,Short Circuit Protection,Open Circuit Protection,High & low voltage protection,fixture should withstand high & low voltage protection,fixture should withstand high voltage upto440 v for 8 hr,IP66 Protected,THD<10%,CRI>70CCT 5700+/-300K, PF>0.9, Driver efficiency>85%,LM79 report require from NABL Accediated lab all as directed by Engr-in-Charge.
2Supply, laying & testing of XLPE Cable of size 50 sqmm 3.5 core insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 Volts grade, in trenches/fixed on wall including taking down old/unserviceable cable all as directed by Engineer-in-Charge. Note: (i) Rate include the cost of lugs of proper size and cable gland (ii) Necessary Excavation, bricks and sand cushioning shall be measurd & paid separately.
3All as per Item No 2 here in before but XLPE cable of size 25sqmm, 4 core
4Excavation in trenches in soft/loose soil n.exc 1.5 mtr wide and n.exc 1.5 mtr depth and getting out for taking out / laying of cable complete all as specified and directed.
5Supply and providing sand cushioning with dry clean sand 8 cm below cable and 15 cm above the cable including punning to 18 cm total thickness complete all as specified and directed. Note : Punned thickness shall be measured for the purpose of payments.
6Supply and laying burnt bricks old size sub class-B laid in trenches for cable protection with length of brick perpendicular to length of cable complete all as directed.
7Removing surplus excavated material not exc 50 mtrs and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as directed.
8Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as directed.
9Supply and fix in replacement of 50 mm bore GI pipe light grade fixed on pole /trenches/wall/road crossing etc complete with clamp nut bolt etc all as specified and directed at site.
10Trenchless boring under road crossings/foot paths by manual / Boring machine complete all as specified and directed at site.
11S and F in replacement polycarbonate junction loop in / loop out box of internal size 250 x 200 x 100 mm made out of FRP (Hot moulded type) with weather proof canopy and locking screws alongwith 5/6 Amps MCB-01 No, 15 Amps rated 3 pole connector - 01 Nos, neutral link mounted and Din rail suitable size for mounting MCB/Connector complete in the box, duly fixed to steel tubular pole using 25 x 3mm FI clamp with suitable gland and lugs for connecting cable including taking down old one complete all as specified and as directed.
12S&F in replacement service bracket for street light fitting made out of 40 mm bore light grade GI pipe of length 1.5 mtr long (approx) bend to shape 115 degree and fix to pole for fixing of street light fitting on pole/wall etc fixed with 2 Nos 32x 6 mm GI clamp, Nut,bolts,washer etc complete all as specified and directed.
13Supply and fix 1.5 Sqmm, single core Two runs PVC insulated and unsheathed FR cable 1100 Volts grade with multistranded copper conductor and one run of 1.5 Sqmm cable for common earth dolly drawn through heavy duty PVC conduit for street light pole including connection from kiosk box to street light fittings with proper clamping of conduit pipe with pole at minimum 2 places complete all as specified and directed.
14Supply Install Testing & Commissioning of sensor Based Street Light Control Panel, 10 KW, IP 66, 3P+N, with an astronomical timer driving three 3-phase feeders Electrical basis• Supply: 415 V, 50 Hz, 3P+N+PE.• Connected load: 10 kW → I ≈ 14.7 A total; per feeder ~5 kW → ~7.3 A.• Fault level: assume ≤10 kA at location unless specified. complete all as specified and as directed and comprising the followings:-Incoming & Outgoing: 4P 40 A MCCB, 10 kA, adjustable TM, door-interlock, pad-lockable.• Busbar: tinned Cu, 100 A, 1.2 kV insulation sleeves, form-2b.• Outgoing feeders (3 nos): each 4P 25 A C-curve MCB, 10 kA, to 4P power contactor 25–32 A AC-1.• Control: 230 V AC control from Phase-N via 1P 6 A MCB. Coils 230 V AC.• SPD: Type-2, 3P+N, Uc 275 V (N-PE)/320–350 V (L-PE), Imax ≥40 kA per pole, with thermal disconnector and remote contact.• Smart Metering: whole-current 3P4W kWh meter, Class 1.0, 5–60 A.Control and automation• Astronomical timer: Legrand AstroRex or equivalent, 2-channel, 230 V AC, ≥16 A per chan (pilot duty), lat/long programmable, DST auto, ±120 min offset, battery backup.• Indications: R-Y-B healthy, Timer ON, Feeder-1 ON, Feeder-2 ON, SPD fault, Trip
15Enclosure and build• Outdoor double-door pedestal, CRCA 3.15 mm with rain canopy or GRP; IP66, IK10; UV-stable gasket.• Bottom gland plate 3.15 mm; polyamide glands; SS hardware.• Anti-condensation space heater 50 W with thermostat; hydrophobic breather plug.• Nameplates, circuit tags, laminated schematic inside.• Clearance for 25% future feeders.(i) Panel enclosure, IP65, pedestal-mount, 1000×800×300 mm with canopy – 1 no(ii) 4P 40 A MCCB, 10 kA – 1 no(iii) Cu busbar set 100 A with supports and shrouds – 1 lot(iv) Type-2 SPD 3P+N, Imax ≥40 kA – 1 no(v) 3P4W kWh meter, Class 1.0, 5–60 A – 1 no(vi) Voltage/phase-failure relay, 3-phase(vii) Glands, lugs, SS fasteners, drawings, testing – 1 lot (viii) Change over switch 40 Amps, 415 V - 01 NoNotes:-• Timer: set site lat/long; OFF at sunrise, ON at sunset; apply −10 to −20 min ON offset to pre-dusk.• Neutral switched on outgoing (4P) to fully isolate. Please Enable Macros to View BoQ information
16Enclosure and build• Outdoor double-door pedestal, CRCA 3.15 mm with rain canopy or GRP; IP66, IK10; UV-stable gasket.• Bottom gland plate 3.15 mm; polyamide glands; SS hardware.• Anti-condensation space heater 50 W with thermostat; hydrophobic breather plug.• Nameplates, circuit tags, laminated schematic inside.• Clearance for 25% future feeders.(i) Panel enclosure, IP65, pedestal-mount, 1000×800×300 mm with canopy – 1 no(ii) 4P 40 A MCCB, 10 kA – 1 no(iii) Cu busbar set 100 A with supports and shrouds – 1 lot(iv) Type-2 SPD 3P+N, Imax ≥40 kA – 1 no(v) 3P4W kWh meter, Class 1.0, 5–60 A – 1 no(vi) Voltage/phase-failure relay, 3-phase(vii) Glands, lugs, SS fasteners, drawings, testing – 1 lot (viii) Change over switch 40 Amps, 415 V - 01 NoNotes:-• Timer: set site lat/long; OFF at sunrise, ON at sunset; apply −10 to −20 min ON offset to pre-dusk.• Neutral switched on outgoing (4P) to fully isolate. Please Enable Macros to View BoQ information

AI Tender Summary

OUR REF NO 58320704
AUTHORITY Statutory Bodies & Commissions/Committees
TENDER VALUE 29.13 Lakhs
LAST DATE 21-11-2026
Authority
Authority Name Military Engineer Services
Work Description Tender for special Repairs/Replacement Of Perimeter Security Lights Network From Tcp-04 To Alpha Mess At Dipatoli Mil Stn Under Ge Dipatoli
Basic Detail
Tender No 8000/2248/E8
Bidding Type Tender
Location
City Ranchi
State Jharkhand
Key Dates
Publish Date 31 Oct 2026
Submission Date 21 Nov 2026
Open Date 28 Nov 2026
Finance
Tender Value 29.13 Lakhs
Tender Fee 500
EMD 58260
Exemption Available
Document List
84fed5b0-50b6-4f6d-a59c-93dfa5cf68bf.html
BOQ_893605.xls
TENDER2248.pdf
Tendernotice_1.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Oct 31, 2026
11:30 IST

Tender Published

Tender notice published.

Completed
Nov 21, 2026
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Upcoming · 17 days
Nov 28, 2026

Bid Opening Date

Technical bids will be opened and evaluated.

Upcoming · 24 days

Tender Documents

Download All (ZIP) ↓
html

84fed5b0-50b6-4f6d-a59c-93dfa5cf68bf.html

xls

BOQ_893605.xls

pdf

TENDER2248.pdf

pdf

Tendernotice_1.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender