Tender for Fire Suppression System For Hq 2 Corps Including Raina Auditorium & Yana Complex
BOQ
| Sl. No. | Item Description |
| 1 | Schedule 'A'Section-I (Building Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col. 5 siginifies this fact only. |
| 2 | Design, supply, construction, testing and commissioning of RCC Underground(UG) sump of capacity 1,00,000 litres complete all as specified and directed. |
| 3 | Design, supply, construction, testing and commissioning of RCC Underground(UG) sump of capacity 1,75,000 litres complete all as specified and directed. |
| 4 | Design, supply, construction of RCC framed pump house size 8.46 metre X 6.46 metre complete all as specified and directed. |
| 5 | Design, supply and construction of RCC framed pump house of size 10.46 metre X 6.46 metre complete all as specified and directed. |
| 6 | Design, supply, fabrication, erection and construction of mild steel structural staging for overhead water storage tank of 10,000 litres capacity ( for item mentioned at srl item no 18 here-in-after), at a height 6.00 metres above ground level, including design and provision of suitable RCC foundations /pedestals for the complete staging system; structural steel columns, beams, bracings, gusset plates, base plates, cleats, stiffeners, anchor/holding-down bolts and all other structural members and connections required for stability and safe support of the tank. The item shall also include provision of a suitably sized MS platform/walkway around the water tank for safe operation, inspection and maintenance, complete with non-slip/chequered plate flooring, guard railing with top rail, intermediate rail and toe guard/kick plate; MS staircase of suitable width and inclination with steps/treads, intermediate landing(s), wherever required, and hand railing on both sides for safe access to the tank/platform. The work shall include all necessary welding, bolting, drilling, cutting, fabrication, erection, surface preparation and approved anti-corrosive protective coating/painting to all exposed steelwork, together with all fixtures, fasteners, supports and incidental works necessary to provide a safe, stable and serviceable installation, complete all as specified and directed. The complete staging, foundation, access staircase, platform/walkway and safety railing shall be structurally designed for dead load, imposed/live load, full operating load of the water tank, wind load, seismic forces and other applicable loads as per relevant IS Codes and site conditions. Structural design and drawings shall be submitted by the contractor and got approved from the Accepting officer before execution. |
| 7 | All as per srl item no. 1.05 here in above, but overhead water tank 10000 litres capacity ( for item mentioned at srl item no 18 here-in-after) of height 15 metres. |
| 8 | All as per srl item no. 1.05 here in above,but overhead water tank 5000 litres capacity ( for item mentioned at srl item no 17 here-in-after) of height 15 metres |
| 9 | Total amount of Sch 'A' Sec II (SITE CLEARANCE, SITE DEVELOPEMENT & MISC. EARTH WORKS) Lump sum price worked out by the contractor for \\" SITE CLEARANCE & Earth Works \\" as listed in schedule 'A' Part-I |
| 10 | Total amount of Sch 'A' Sec III (INTERNAL ELECTRIFICATION ) Lump sum price worked out by the contractor for \\"INTERNAL ELECTRIFICATION \\" as listed in schedule 'A' Part-IV |
| 11 | Total amount of Sch 'A' Sec IV (LIGHTINING PROTECTION ) Lump sum price worked out by the contractor for \\" LIGHTINING PROTECTION \\" as listed in schedule 'A' Part-V |
| 12 | Total amount of Sch 'A' Sec V (FIRE ALARM AND DETETION SYSTEM ) Lump sum price worked out by the contractor for \\" FIRE ALARM AND DETETION SYSTEM \\" as listed in schedule 'A' Part-VI |
| 13 | Total amount of Sch 'A' Sec VI (External Water Supply Works) Lump sum price worked out by the contractor for \\" External Water Supply Works \\" as listed in schedule 'A' Part-VII |
| 14 | Total amount of Sch 'A' Sec VII (External Elect Supply Works) Lump sum price worked out by the contractor for \\" External Elect Supply Works \\" as listed in schedule 'A' Part-VIII |
| 15 | Total amount of Sch 'A' Sec VIII (FIRE HYDRENT & SPRINKLER WORK) Lump sum price worked out by the contractor for \\" FIRE HYDRENT & SPRINKLER WORK \\" as listed in schedule 'A' Part-IX |
| 16 | Schedule 'A'Section-IX (Misc Items of Works) (Items given here-in-after) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as \\"Rs 0.00\\" under Col. 5 siginifies this fact only. |
| 17 | FIRE SUPPRESSION SYSTEMDesign and preparation of detailed report and corresponding drawings through any specialised agency dealing with planning, designing and execution of fire hydrant system, fire suppresion system, sprinkler system, gas flooding system and automatic addressable type fire detection cum alarm system. The buildings involved for these fire safety arrangements are Raina Auditorium, Yana Complex, Adm block, Education block, P1, P2, and P3 buildings of HQ. This report shall be submitted to Accepting officer for approval after vetting by any IIT/NIT/CFEES as per Sch A Notes.Note : (a) For all fire suppression system works such as fire alarm & detection system, fire hydrant & sprinkler system, wet riser & down comer stem, gas flooring system and panel system, contractor shall appoint a TAC agent company at the start of projects. All works shall be executed after approval of nominated TAC agency. (b) Qualifications of TAC : As per Sch A Notes.(c) All technical submissions to MES would be routed through nominated TAC agency. TAC agency shall be involved right from designing to vetting to approval to execution to assessment and review to testing and comissioning of the project. |
| 18 | FIRE ALARM & DETECTION SYSTEMSupply, Installation, testing & commissioning of optical thermal (Multi) detector (heat & smoke) radio-linked optical thermal detector operates both with an optical sensing chamber based on the principle of scattered light as well as with a rate of rise thermal sensor. The detector communicates with a fire detection control panel in loop technology via the loop RF interface. Two lithium batteries are accommodated in the detector base one as backup. The two coloured LED indicator with 360 visibility. Mechanical theft protection in the base. Radio transmission of 150 m (in free air), operating at de-licensed frequency range of 865MHz all as specified and directed. |
| 19 | Supply, Installation, Testing & Commissioning of analouge addressable wall sounder weather proof as standard and is equipped with 3 levels of volume adjustment and 32 recognised tones which can be set locally at the sounder. When configured onto a translator, the wireless sounder is fully addressable and benefits from intelligent control, test and monitoring, complete all as specified and as directed. |
| 20 | Supply, installation, testing & commissioning of RF translator wireless device which can control upto 32 detectors modules or signalling devices, configuration through manual or PC software, up to 32 fully intelligent wireless field devices. Operating at frequency of 865-867 MHz. status indication via 3 LEDs, IT communicates with the control panel via the loop, radio transmission range 150m in free air, operating frequency channels 7, all as specified and directed. |
| 21 | Supply, installation, testing & Commissioning of Analouge addressable Wireless Resettable Manual Call Point, Bi Directional wireless communication Fully intelligent Utilises standard low cost lithiumbattery technology, Long battery life, Resettable Element, Clear ‘device activated’ warning flag, High reliability, automatic channel hopping self optimising wireless amplitude and frequency and fixing with suitable size of MS conduit pipe alongwith the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required. Communication range with the Translator Module is up to 150 metre in open area complete all as specified and as directed . |
| 22 | Supply, installation, testing & commissioning of active full function repeater panel complies with EN54-2, Network up to 64 panels/repeaters,Programmable one touch test mode,Powerful and versatile cause & effect programming,Cause & effect wizard including:Cause & effect action,Disablement configuration,Test mode configuration 5.25 amp power supply to EN54 part 4,Large graphic display,In built help and alarm information screens,Real time clock,Stylish enclosure design,Soft-touch tactile buttons,2 programmable function buttons,3 programmable front panel mounted LED’s,Improved Front loading Printer (optional)Up to 512 programmable inputs/outputs perpanel via 2 wire RS485 serial link (optional) Simple Windows graphical configuration utility.It shall have IP rating IP30 complete all as specified and as directed . |
| 23 | Supply, installation, testing and commissioning of UL listed Microprocesssor based 2 Loop analogue addressable type fire alarm control panel with 80 character LCD display four access levels 500 event historical logging upto 200 detectors all as specified. The panel will have its battery charges and 2 batteries of 7 AH. Cost of batteries and battery charger is deemed to be included in quoted cost of panel complete all as specified and directed . |
| 24 | Supply and laying of PVC insulated PVC sheathed cable galvanized steel strip or wire armoured,electric control cables (Heavy duty) with stranded Copper conductor of size 1.5 sq mm 2 core 1100 Volts grade suitable for fire survival all as specified complete all as specified and directed. Note: cost of MS clamp/Saddles placed alongwith wall/ceiling for fixing of cable shall deemed to be inclusive in quoted item rate |
| 25 | Material and labour for concealed / surface point wiring complete with 1.5 Sqmm single core multistranded copper conductor FRLS PVC insulated and unsheathed cable 1100 volts grade drawn through and including medium grade, ISI marked, PVC conduit,medium grade ISI marked not less than 20 mm dia with accessories fixed concealed/surface type on wall/ roof/ ceiling / trusses/ channel and including provision of 1.5 sqmm single core PVC insulated, unsheathed cable FRLS-H, 1100 volt grade ISI marked with multi stranded copper conductor green colour as earth conitnuity conductor and connected to common earth dolly with suitable size lugs, including mild steel sunken box or pressed steel terminal box or pressed steel terminal boxes conforming to IS:14772:2000 with earth dolly and coated with two coat of anti corrosive paint over a coat of red oxide primer both internally and externally with and including (provision of new) modular covered plate over sunken box for housing the modular switches, socket outlets., fan regulators etc with brass screws and brass washers and making good the disturbed surfaces as per existing for :-Note:-1 Modular metal flush / sunken box, and for modular switch/ socket cover plate & sheet are inclusive in the item rate quoted.2. Only switch, socket to be measured and paid separately. |
| 26 | Switch Modular type 6 Amps, one way, 1 module, 230 Volts, complete all as specified and directed. |
| 27 | Socket modular 2/3 pin, 6 Amps,one way,2 module,230 Volts , complete all as specified and directed. |
| 28 | Supplying, installing, testing & commissioning of UL listed Intelligent addressable Manual Call Points resettable type/ pull station complete all as specified and directed . |
| 29 | S & F Exit Sign of dimension 300 mm x130 mm x 8 mm made up of aluminium, acrylic LED edge light 2 Watt 230 Volt green colour with rechargable battery backup of minimum 3 Hrs alongwith necessary fixing arrangement fixed on wall/ ceiling ,complete all as specified and directed. |
| 30 | S & F powder coated GI Race Way Cable Tray of size 100 mm x 50mm x 2mm (1 Compartments) including suitable bracket ,nut, bolt washers, fixed to wall roof etc, complete all as directed |
| 31 | LIGHTINING PROTECTION WORKSSupply & fixed aluminium strip of size 25x3 mm complete with saddles and base insulators (made out of porcelene/PVC) and fixing screws on roof and down side conductors complete all as per specified and directed. |
| 32 | M&L for PCC 1:3:6 type C-2 using 40mm graded stone aggregate as in bocks to hold GI extension pipe for Air termination rod complete including necessary use and waste of form work required, all as directed. |
| 33 | Supply and fixing Air termination, single pointed aluminium rod 12 mm dia and 300 mm long including fixing base plate with insulator complete fixing on the top roof of the hanger complete all as specified and directed. |
| 34 | FIRE EXTINGUISHERSProviding & fixing of ISI marked (IS: 2878) portable Co2 fire extinguisher of capacity 4.5 kg flat base including valve discharge hose of not less than 10mm dia. meter complete in all respect including initial fill with CO2 gas confirming to IS 307-1966 and filled to filling ratio of not more than 0.367 complete all as specified and directed. |
| 35 | Providing & fixing of ISI marked (IS: 15683) portable ABC multipurpose mono monioum phosphate powder , nitrogen pressurised type fire extinguisher, Capacity 6 kg complete all as specified and directed. |
| 36 | Providing & fixing of ISI marked (IS: 13886) trolley mounted fire extinguisher, AFFF Mechnical foam type (gas pressurized) Capacity 50 litres omplete all as specified and directed. |
| 37 | Providing & fixing of ISI marked (IS: 2878) portable Co2 fire extinguisher of capacity 22.5 kg flat base including valve discharge hose of not less than 10mm dia. meter complete in all respect including initial fill with Co2 gas confirming to IS 307-1966 and filled to filling ratio of not more than 0.367 complete all as specified and directed. |
| 38 | Providing & fixing of ISI marked High pressure water mist CAF fire extinguisher Back- packtype, ultra-light, Carbon composite with Pet liner pressure vessel 9 litres and air cylinder complete all as specified and directed. |
| 39 | Providing & fixing of ISI marked High pressure water mist CAF fire extinguisher Trolley Mounted, ultra-light, Carbon composite with Pet liner pressure vessel 50 litres and air cylinder complete all as specified and directed. |
| 40 | Providing & fixing of ISI marked (IS: 15683) portable ABC multipurpose mono monioum phosphate powder , nitrogen pressurised type fire extinguisher, Capacity 9 kg complete all as specified and directed. |
| 41 | Providing & fixing of ISI marked (IS: 13886) trolley mounted fire extinguisher, AFFF Mechnical foam type (gas pressurized) Capacity 9 litres , complete all as specified and directed. |
| 42 | Providing & fixing of ISI marked (IS: 15683) portable Low/ High Pressure Water Mist CAF type fire extinguisher, Capacity 9 litres , complete all as specified and directed. |
| 43 | Providing & fixing of ISI marked (IS: 15683) Trolley Low/ High Pressure Water Mist CAF type fire extinguisher, Capacity 50 litres , complete all as specified and directed. |
| 44 | GAS FLOODING SYSTEM FOR YANA COMPLEXDesign ,Supply, installation, testing and commissioning of CCOE, Nagpur approved, UL listed seamless storage cylinder (Designd as per IS 7285 part 2, Origin - India) with PESO approved valve meant for use in FK 5-1-12 gas suppression system (Filled at PESO approved & UL Listed OEM Filling Station) Based Fire Suppression System (UL/FM Approved) pressurized to 25/42/70 bar .The OEM shall give a Certificate stating that their system is approved by UL/FM for use with Seamless Steel Cylinders.The OEM shall also provide a Letter that the OEM has Flow Calculation software suitable for Seamless Steel cylinder bidded for as per the Bill of materials, and that such Software shall be type approved by UL/FM. Cylinder valve and seamless storage cylinder shall be approved by PESO, Nagpur and the approval copies of cylinder valves and seamless cylinder shall be submitted along with the technical offer. Capacity of cylinder shall be 120 litres. |
| 45 | Design , Supply & filling of FK 5-1-12 gas in the existing seamless storage cylinder complete all as specified. OEM Factory Filled per Kgs. (UL & FM) .Note:- The FK 5-1-12 gas shall:Comply with NFPA 2001 standard ,Must have Zero Ozone Depletion Potential (ODP ) Have a short life span in the atmosphere, with atmospheric life time of less than 5 days . Agent shall not contain any Hydrofluorocarbons (HFC), complete all as specified and directed. |
| 46 | Supply, installation, Testing & commissioning of Supervisory presure switch - standard (open on fall) ,UL & FM listed, complete all as specified and directed. |
| 47 | Supply, installation, Testing & commissioning of electrical actuator with placement indicator switch suitable for operating electrically from fire detection and control panel with other master adapter kit accessories complete as per technical specifications ,UL & FM listed, complete all as specified and directed. |
| 48 | Supply, installation, Testing & commissioning of manually operated actuator/lever to operate the gas manually from the cylinder with all accessories complete as required as per technical specifications,UL & FM listed, complete all as specified and directed. |
| 49 | Supply & fixing of high pressure flexible rubber discharge hose of 50 mm dia with braided reinforcement to route the Clean agent from storage cylinders to the discharge piping complete as required as per technical specifications UL & FM listed, complete all as specified and directed. |
| 50 | Supply, installation, Testing & commissioning of DN1/4\\" PTFE flexible actuation hose x 710mm length ,UL & FM listed, complete all as specified and directed. |
| 51 | Supply, installation, Testing & commissioning of Male adaptor (1/4\\" BSPT x 1/4\\" BSPP) , complete all as specified and directed. |
| 52 | Supply, installation, Testing & commissioning of Male elbow (1/4\\" NPT x 1/4\\" BSPP) , complete all as specified and directed. |
| 53 | Supply, installation, Testing & commissioning of Male Tee (1/4\\" BSPP x 1/4\\" BSPP x 1/4\\" NPT), complete all as specified and directed. |
| 54 | Supply, installation, Testing & commissioning of gas discharge pressure switch to trip A.C/ electrical equipment etc. complete as required as per technical specifications,UL & FM listed, complete all as specified and directed. |
| 55 | Supply, installation, testing and commissioning of 25 mm, 360 degree NPT brass discharge nozzles to provide proper flow and distribution of gas to flood the hazard area, complete as per approved flow calculations, UL and FM listed, all as specified and directed. |
| 56 | Supply, installation, testing & commissioning of tank bracket assembly complete with C- Channel Stand and Supports for above Cylinder. The Price Shall include MS Fabricated Floor Supported Cylinder Support Stand (wherever required), complete with one coat of Primer and two coats of black enamel paint , complete all as specified and directed. |
| 57 | Supply, installation, testing & commissioning of warning sign board with marking \\"GAS DISCHARGE. DO NOT ENTER\\" with inbuilt hooter. Shall Operate on 24 V DC, driven through gas release panel. (for use outside room) |
| 58 | Supply installation testing & commissioning of warning sign board with marking \\"GAS DISCHARGE. GAS RELEASE EXIT\\" with inbuilt hooter, shall operate on 24 V DC, driven through gas release panel. (for use inside room) |
| 59 | Supply, installation, testing & commissioning of following size MS seamless pipe, ASTM A-106(Sch 40), Grade B complete with all fittings and painting with one coat of redoxide and 2 coats of red enamel paint; fixing on ceiling with suspended supports, clamps anchor fastners, cutting chases / holes in valve ceiling and making good the same etc complete as required as as per approved flow calculations for the specific hazard volume. All nut-bolts and fittings to be used shall be heavy duty GI only .Note:- Laying of piping shall be seismic qualified with seismic brazing. Detailed calculations for Seismic supports to be submitted to GE for approval before execution of works. These design details need to be verfied by appointed TAC before submitted to GE. |
| 60 | All as per srl item no 14.15 above, but 50 mm dia , complete all as specified and directed. |
| 61 | All as per srl item no 14.15 above, but 40 mm dia , complete all as specified and directed. |
| 62 | All as per srl item no 14.15 above, but 32 mm dia , complete all as specified and directed. |
| 63 | All as per srl item no 14.15 above, but 25 mm dia , complete all as specified and directed. |
| 64 | All as per srl item no 14.15 above, but 20 mm dia , complete all as specified and directed. |
| 65 | Supply, installation, testing & commissioning of Check Valves for discharge hose pipe complete all as specified and directed . |
| 66 | Supply installation testing & commissioning of UL Listed Manual Abort Stations with DPDT Relay, The Abort will be monitored simultaneously by Fire Alarm and BMS System. |
| 67 | Supply installation testing & commissioning of UL Listed Manual Release Stations with DPDT Relay, The Release switch will be monitored simultaneously by Fire Alarm and BMS System , complete all as specified and directed. |
| 68 | Design, supply, installation,testing & commissioning of addressable Hooter cum Strobe , complete all as specified and directed. |
| 69 | Supply installation Testing & commissioning of dome polycarbonate transparent covers for the manual release stations (Color:Green): complete with built-in battery such the alarm is locally sounded whenever the cover is lifted. With Horn Flush mount, UL/cUL Listed polycarbonate transparent cover for manual release station, LPCB (To prevent accidental operation of the release switch) , complete all as specified and directed. |
| 70 | Supply installation testing & commissioning of UL Listed Single zone Gas Release Panel facility to connect Manual Abort/Release switches. The Panel shall provide Potential free contacts for monuitoring on BMS/FAS for Alarm /Trouble / Fault Status. The Panel shall be complete with red colour housing, monitored power supply unit, battery charger & batteries for 30 minutes backup.Note- Testing shall be shown by triggering the detectors in the protected rooms & activation of electrical actuator shall be shown. |
| 71 | Supply installation testing & commissioning of UL Listed Suppression system service Disconnect Switch, flush mount; indicator lamps 24 VDC. The Service Disconnect switches shall be controlled by keyswitch and should initiate a supervisory condition to fire panel when in disconnect/disable position. (should be with Aux P F Contact) |
| 72 | Towards Conducting Room Integrity Test : Door Fan test to meet the Requirements of the NFPA 2001, and predicting the efficacy of the Protected Area Enclosure from the perspective of Fire Suppression.Note: Tests to consider room integrity for all doors separately since it is a combined flooding for both rooms. This testing need to be verified by TAC and signed reports to be submitted. Reports shall be submitted through TAC to GE for approval. |
| 73 | Supply, installation, testing and commissioning of ISI Marked 2 core x 1.5 mm2, Multistrand Copper, FRLS Armoured cable, RED in Colour, laid on surface with GI saddle-spacers every 0.3 meters complete with GI Junction Box, lugs, cable compression glands, cable tags and ferruling, complete all as specified and directed. |
| 74 | Supply, installation, testing & commissioning of VDS Approved signal processor unit. It should have LED & LC display both as well as a 16 Relay. It shall be able to support 350 RMs sensor cable length with 1 to 100 maximum sensor. The alarm triggering via differential and maximum temperature evaluation, high temperature resolution of 0.1 °C with a repeatability of ±0.1 K along the entire sensor cable length. Panel shall be Free from false alarms, caused by natural ambient temperature fluctuations, due to intelligent evaluation algorithms. Highly durable via utilisation of maintenance-free components in a modular configuration, RoHS compliant. Individual password-protected access levels for operators, maintenance and service personnel, as well as for commissioning.Operating temperature: -25 °C to +70 °C , complete all as specified and directed. |
| 75 | Supply, installation, testing & commissioning of VDS approved ,Heat Sensing Cable onto which the sensors are mounted in an encapsulation at every 4 RM interval. Complete encapsulation to protect sensors from environmental influences, Pinpoint sensor location via individual addresses, Constant sensor monitoring via control and evaluation unit Branching of cable routes via connection boxes. Cable should detect freely adjustable absolute alarm thershold & freely adjustable differential alarm thershold i.e. fixed temperature as well as rate of rise of temperature.measuring range -40°to +120° . |
| 76 | Supply, installation, testing & commissioning of connection cable 2-wire, 0.8 mm core diameter, with functional integrity E30 - E90 according to DIN 4102-12; outer sheath in HM2 compound, red, loop resistance: maximum 77 Ohm connecting cable between sensor cable & controller. |
| 77 | Supply, installation, testing & commissioning of Clamps One-piece, self-locking polyamide cable clamp for indoor and outdoor use toolless locking mechanism Halogen-free according to IEC 754-2, UV resistance according to ISO 4892-2 Temperature range -30 to +110 °C (100 pcs). |
| 78 | Supply, installation, testing & commissioning of connection module in the housing for a sensor cable, up to four external sensors and corresponding connection lines to the control and evaluation unit; Housing material: glass-fibre reinforced polycarbonate, halogen-free, UV and weather-resistant, free of heavy metals, Protection class: IP 66 according to EN. |
| 79 | Supply, installation, testing & commissioning of configuration software specially developed for the operation and programming of the sensor control unit.Setting pre-alarms and alarm thresholds (different thresholds for different sensors possible, even within a group),Two-sensor dependency to prevent false alarms and for live temperature monitoring. |
| 80 | PANEL PROTECTION SYSTEMDesign, supply testing and commissioning of Automatic High Pressure Fire Suppression Cylinder and DLP Valve clean agent Based,Cylinder CCOE/PESO approved, Valve: Brass; Approval: π0029; integrated pressure reducing valve, rupture disk safety for the high-pressure side Busting Disc: 250 Bars, spring-loaded safety valve for the low-pressure side; Integrated position control for ball valve : Open / Close. The required clean agent quantity is arrived as per the volume of the respective panels to be protected. In addition, the following standards and rules and regulations shall be applicable: |
| 81 | All asper Srl item no 15 above, Supply of 4 kg capacity HFC 227ea , DLP Assembly with automatic valve CE & pie approved, push in connector for tube, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation ,complete all as specified and directed. |
| 82 | All asper Srl item no 15 above, Supply of 6 kg capacity HFC 227ea , DLP Assembly with automatic valve CE & pie approved, push in connector for tube, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation ,complete all as specified and directed. |
| 83 | All asper Srl item no 15 above, Supply of Control Unit for controlling each system, to get a signal continually indicating the CO2 quantity inside the cylinder (for monitoring and maintenance, complete with buzzers and electronic hooters, including all necessary accessories + electrical wiring to make each entire system functional ,complete all as specified and directed. |
| 84 | All asper Srl item no 15 above, Supply of Linear pneumatic heat detection tube for automatic fire detection and suppression system made by special modified Polyamide (PA), Color Red RAL300/ Black, High grade quality, Inner diameter 4mm, Outer Diameter 6 MM, Melting Point approx. 222°C , Burst Pressure 100 bar at 20°C. Temperature range : minus 40°C to +80°C. Working Pressure 20Bar at 20°C. Burst Temperature : when Pressurised with dry nitrogen at 16 bar pressure approx 100°C to 110°C ,complete all as specified and directed. |
| 85 | All asper Srl item no 15 above, Supply of pressure Switch to monitor Pressure drop in the tube, switch point 5 Bars. Switch Type SPST, Normally Open, Electric Rating : 120/240 VAC-375 VA, 24 VAC-125 VA, Open 160 psi y-7, Close 185 psi y-5,Pressure switch + adaptor / 5bar / M10x1 / SPST complete as required ,complete all as specified and directed. |
| 86 | All asper Srl item no 15 above, Supply of End of Line Plug for Automatic fire suppression tube used for fitting at the tube end to terminate the point. Tube connection 6mm, Length 1.13``/29mm, Fitting made by brass nickel plated material with Elastomeric sealings, Temperature range TS -20 Deg C till+ 60 Deg C, Maximum working pressure 25 Bars, made as per PED pressure equipment Directives ,complete all as specified and directed. |
| 87 | All asper Srl item no 15 above, Supply of End of Line adapter with Pressure gauge for Automatic fire suppression tube used for fitting at the end of the tube for pressurizing and re pressurizing the tube includes check Valve, Pressure Gauge and fitting to connect to sensor tubing. Tube connection 6mm, length 2.77``/71mm, Gauge scale :0-20 bar. Fitting made by brass (plated /unplated), Stainless steel, Elastomeric Sealings, Copper Nickle plated, Temperature range TS -20 Deg C till + 60 Deg C, made as per PED Pressure Equipment Directives complete as required ,complete all as specified and directed. |
| 88 | All asper Srl item no 15 above, Supply of T Connection, Brass, Nickle plated, for 4x6 mm Sensor Tube, quick and easydisassembly using special tool, working pressure 15 bars at 15 Deg Temperature, temperature range-40 Deg C till + 80 Deg C, Elastometric Sealings, External Diameter tube 6mm ,complete all as specified and directed. |
| 89 | FIRE HYDRANT AND SPRINKLER SYSTEMSupplying, installing, testing and commissioning of Electrical driven fire pump having Discharge : 2850 LPM and App. Head : 70 M suitable for automatic/ manual operation consisting of the following: i) Horizontal mounted End Suction type fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 2850 LPM against a total head of 70 M while running at 2900 RPM complete in all respect. ii) Squirrel cage, induction motor TEFC type suitable for 415 + 10%V, 3 phase, 50 Hz, AC supply, of suitable HP rating for the above pump with synchronous speed of 2900 RPM with flexible coupling and coupling guard. iii) Common bed plate for mounting pump and motor fabricated of mild steel channel as per manufacturer's recommendation with heavy duty Anti Vibration pads (4 Nos., heavy duty). Including PCC foundation 0 V , 3 Phase. 50 Hz 70m Head, 2850 LPM discharge Including foundation channel and PCC foundation (1:2:4) Type B-2 made upto suitable level all as per manufacturer's recommendation complete all specified and directed. iv) Coupling and coupling guard for direct coupling of pump and motor. |
| 90 | All as per item no 16 above, but discharge 1620 LPM and 70 metre head complete all as specified and directed. |
| 91 | Supplying, installing, testing & commissioning of Diesel Engine driven fire pump having Discharge -2850 LPM and Head 70 metres suitable for automatic/manual operations consisting of the following : i) Horizontal mounted end suction type fire pump having cast iron body, bronze impeller, stainless steel shaft & capable of delivering 2850 LPM against a total head of 70 M while running at 1800/2300 RPM complete in all respect. ii) Radiator cooled diesel engine of suitable BHP at 1800/2300 RPM for the above pump complete with standard accessories & suitable cooling system as described in specifications. iii) Common base plate for mounting pump & engine of requisite strength manufactured out of M.S. channels and PCC foundation (1:2:4) Type B-2 made upto suitable level as per manufacture's recommendation with heavy duty Anti Vibration pads. (Cushy foot) (6 nos., heavy duty) . iv) Coupling & coupling guard for direct coupling of engine & pump. v) 200 liters capacity day oil storage tank fabricated from 16 SWG thick M.S. plates. Tank shall be provided with inlet, outlet, overflow, vent, drain connections, filling connection & level indicator. Tank shall be mounted on a suitable steel structure (Painted with 2 coats of red oxide paint). Tank shall be provided with epoxy coat from inside & two or more coats of synthetic enamel paint outside over two coats of red oxide primer. vi) 24 volts 180 AH lead acid battery (12 volts - 2 Nos) with boost/Trickle charger for starting the engine automatically complete as required. vii) Provision for starting of Engine automatically in case of power failure at the time of fire |
| 92 | All as per item no 16.02 above but discharge 1620 LPM and 70 metre head complete all as specified and directed |
| 93 | Supplying, installing, testing & commissioning of electrically driven jockey pump having discharge : 180 LPM (3 LPS) and App Head : 70 metre suitable for automatic/manual operation consisting of the following including PCC foundation all as specified and directed : i) Horizontal mounted end suction jockey pump having cast iron body, volute bronze impeller, stainless shaft capable of delivering 180 LPM against total head of 70 M while running at 2900 RPM complete in all respect for testing of working of the pumping set as required. ii) Squirrel cage induction motor suitable for 415 + 10%V, 3 phase, 50 Hz, AC supply of suitable HP rating for the above pump with synchronous speed of 2900 RPM T.E.F.C type connected to pump with flexible coupling and coupling guard . iii) Common bed plate for mounting pump and motor fabricated of mild steel channel and PCC foundation (1:2:4) Type B-2 made upto suitable level as per manufacturer's recommendation with heavy duty 4 Nos. Anti Vibration pads.(Cushy foot) |
| 94 | Supply, installation, testing and commissioning of Terrace pump of 450 LPM capacity at 36 metre head pressure not less than 3.5 kg/sq cm at the top most hydrant suitable for fire fighting and conformiong to IS- 12469-1988 complete with totally enclosed drip proof squirrel cage induction motor with bronz impellers, pressure guage, pressure switch complete to operate on 3 phase, 415 volts, 50 Hz complete including fixing arrangments complete with canopy of suitable size for terrace pump on MS structure near terrace tank and making connection with tail / tapper pieces to connect supply and delivery pipes, including pipes and also including fabricated MS common base plate of suitable size coupling guard air vent for casting pessure guages on delivery side and pipe etc(Including electrical connection to starter panel ) (Location- Raina Auditorium , Yana complex , Adm bldg and Education bldg ) . |
| 95 | Supply, installation, testing and commissioning Terrace pump of 900 LPM capacity at 36 metre head pressure not less than 3.5 kg/sq cm at the top most hydrant suitable for fire fighting and conformiong to IS- 12469-1988 complete with totally enclosed drip proof squirrel cage induction motor with bronz impellers, pressure guage, pressure switch complete to operate on 3 phase, 415 volts, 50 Hz complete including fixing arrangments complete with canopy of suitable sizefor terrace pump on MS structure near terrace tank and making connection with tail / tapper pieces to connect supply and delivery pipes, including pipes and also including fabricated MS common base plate of suitable size coupling guard air vent for casting pessure guages on delivery side and pipe etc. (for bldg P1,P2 and P3 ) . |
| 96 | Supply, installation, testing and commissioning of pressure switch of approved make for Hydrant pump, jockey pump and diesel engine driven pump and terrace pump including necessary wiring and cut off valve up to central panel & other material as described in specifications. |
| 97 | Suppy and fixing air cushioning tank (air vessel ) 250mm dia x 1000mm high with dished top, made of minimum 6mm thick MS Pipe /Plate complete with 20mm dia brass air valve (ball type) , 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete.(One for pump room and one for terrace) |
| 98 | Suppy and fix Air cushioning tank (Air vessel ) 200mm dia x 1000mm high with dished top, made of minimum 6mm thick MS Pipe /Plate complete with 20mm dia. Brass air valve (Ball type) , 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete.(One for pump room and one for terrace) |
| 99 | Providing, fixing, testing & commissioning of 150 mm dia 6.35 mm thick flanged end basket 300mm height of Y-type strainer made from MS body with bottom and top removable flanges with nuts, bolts etc having filteration area at least 6 times the cross sectional area of the pipe. |
| 100 | Providing, fixing, testing & commissioning of 100 mm dia 6.35 mm thick flanged end basket 300mm height of Y-type strainer made from MS body with bottom and top removable flanges with nuts, bolts etc having filteration area at least 6 times the cross sectional area of the pipe. |
| 101 | Providing, fixing, testing & commissioning of 100 mm dia Bourden type, Stainless Steel dial type pressure gauge (in Pump Room) including brass isolation valve and pipe having caliberation of 0-21 Kg/cm2 complete all as specified and directed. |
| 102 | M&L exhaust, Diesel engine driven pump exhaust M. S. pipe class 'C' 150 mm dia including fitting like flanges, bends, reducers, etc. 50 mm thick fibre wool insulation aluminium cladding, 21 gauge, necessary excavation, fixing of silencer connections at engine exhaust, necessary supports, back filling, cutting and making good, bird proof and weather proof flap complete in all respect as directed. |
| 103 | Design /Layout, supply , fixing, testing & commissioning of heavy class MS ERW pipe, IS : 3589 marked with all necessary fittings like tees, elbows, flanges, reducers, gaskets, nuts and bolts etc. welded or screwed joints as required including fixing the pipe with necessary structural supports (for delivery/suction manifold relating to the pumps) including painting of two coats of synthetic enamel paint over two coats of red oxide primer including all civil breakages and making good the same.[ Location : Plant room]. Note : Pipe lines to be laid underground buried in soil shall have protection aganist corrosion by means of coating and wrapping as per Para 27.3.7.2 of SSR Part I and above ground pipes shall be coated with one coat of red oxide primer and two coats of synthetic enamel of fire red colour as per para 27.3.12.5 of SSR Part I . |
| 104 | All as per srl item no 16.14 above,200 mm dia (6.35 mm thick) with necessary supports etc. as required. (Nominal Bore) |
| 105 | All as per srl item no 16.14 above,2250 mm dia (6.35 mm thick) with necessary supports etc. as required. (Nominal Bore) |
| 106 | Supply, Installation testing & commissioning of M.S ERW PIPE pipes conforming to IS : 3589 Part-I including cutting, threading, welding & all fittings like flanges, tees, elbows, bends junctions, reducers, ball valves etc. welded or screwed joints, clamps structural steel supports (as per TAC norms) or as required/ directed at site .Note : Pipe lines to be laid underground buried in soil shall have protection aganist corrosion by means of coating and wrapping as per Para 27.3.7.2 of SSR Part I and above ground pipes shall be coated with one coat of red oxide primer and two coats of synthetic enamel of fire red colour as per para 27.3.12.5 of SSR Part I. |
| 107 | All as per srl item no 16.17 above, 25 mm dia (Nominal Bore), complete all as specified and directed. |
| 108 | All as per srl item no 16.17 above, 32 mm dia (Nominal Bore), complete all as specified and directed. |
| 109 | All as per srl item no 16.17 above, 40 mm dia (Nominal Bore), complete all as specified and directed. |
| 110 | All as per srl item no 16.17 above, 50 mm dia (Nominal Bore), complete all as specified and directed. |
| 111 | All as per srl item no 16.17 above, 65 mm dia (Nominal Bore), complete all as specified and directed. |
| 112 | All as per srl item no 16.17 above, 80 mm dia (Nominal Bore), complete all as specified and directed. |
| 113 | All as per srl item no 16.17 above, 100 mm dia (Nominal Bore), complete all as specified and directed. |
| 114 | All as per srl item no 16.17 above, 150 mm dia (Nominal Bore), complete all as specified and directed. |
| 115 | Providing & Fixing S.S. single headed ISI marked oblique pattern hydrant landing valves with 80 mm dia flanged inlet & 63 mm dia female outlet complete with gun metal cap and GI chain twist release type plugh and all accessories as per IS : 5290-1983 Type A, complete all as specified and directed. |
| 116 | Providing & Fixing of 63 mm dia 30 m long non-percolating flexible hose (RRL- type A) as per IS : 636. Type A with S.S. male & female instantaneous type coupling (IS 903) complete all as specified and directed. |
| 117 | Supply and fix 63 mm dia Gun Metal branch pipe with 12.5 mm nozzle confirming to IS 903 complete all as specified and directed. |
| 118 | Providing & Fixing of wall mounting swinging type first aid fire hose reel with drum, hanging bracket, 36.5 RM. length x 20 mm dia high pressure hose reel tubing as per IS: 444 with gun metal (GM) shut off nozzle having 5 mm dia orifice. The hose reel shall be conforming to IS : 884-1985. Rate shall include 25 mm dia M.S. pipe connection from Riser to hose reel, sockets, nipples, elbows and ball valve (25 mm dia). Drum shall be fixed on adjoining wall through anchor fasteners / cement concrete block as and when required,hose reel of 20 mm dia and 30 metre length confirming to IS 8090 . |
| 119 | Providing & Fixing of weather proof standard fire hose cabinet 800mm X 600mm X 250 mm for yard hydrants made of 18 SWG powder coated M.S. sheet having single or double opening glazed (4.0 mm thick glass) shutter including necessary locking arrangement by allan key, stove enamelled Fire red finish with \\"Fire Hose\\" marked on front, suitable for housing 2 each Hose pipe, 1 No. branch pipe & nozzle spanner. |
| 120 | Providing & Fixing of burden type Stainless Steel dial type pressure gauge with brass isolation valve and pipe. (For each internal Fire hose cabinet) Dial Diameter : 100 mmCaliberation : 0-10 Kg/cm2 |
| 121 | Design / Lay out, Supply, Installation, Testing and Commissioning of following type of Sprinkler heads UL listed and FM approved complete with fusible glass capsule of 5 mm dia suitable for horizontal / pendent type sprinkler's head of 57 degree with powder coated conforming to relevant IS ammended upto date complete etc. as required. |
| 122 | All as per srl item no 16.32 above, but Upright Type |
| 123 | All as per srl item no 16.32 above, but Pendent Type |
| 124 | Design ,fabrication ,supply, installation, testing and commissioning of following fire fighting panel suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution system. The panel shall be free standing floor mounting sheet metal enclosed dust and vermin proof conforming to IP-56, compartmentalized design, fabricated out of 14 SWG sheet steel, painting, earthing numbering, danger plate as per specifications and drawings , flush front with Aluminium busbars, separate earth bus bars to be provided throughout the length of the panel. The incoming and outgoing feeder breakers, fuses, indicating lamps etc shall be accommodated in a modular multitier arrangement. The painting shall done as per relevant IS codes/as specified in the specifications. Adequate size cable alley shall be provided all round the panel and in the back for each cable bending and termination. The panel shall be fabricated by CPRI/TAC/Fire authority approved vendor. The outgoing feeders inside the panel shall be connected through solid bus bars. Flexible cable links are not acceptable. Bus bars shall be provided with heat shrinkable sleeves and shall be colour coded. The panels shall be suitable for cable entry from top. The minimum fault rupturing of all incoming and outgoing switches/breakers shall be 35 KA. The panels shall be fabricated after the approval of fabrication drawings.(Note-The description in srl item no 16.35 to 16.37 is to be considered when quoting against this item) |
| 125 | Main Fire Pump Panel:Incoming Section:i) One (1) No. 250 A TPN MCCB (35 KA)ii) 600 Amps Aluminium bus bar shall be insulated with heat shrinkable sleeves and shall be color coded.iii) Three (4) Each current transformer (400/5A).iv) One (1) No. ammeter (0-800) Amps with selector switch.v) One (1) No. (0-500 V) voltmeter with selector switch.vi) 1 Set (4 Nos) of phase indication lamps with HRC fuses.vii) Indication for control supply 'healthy'.Outgoing:i) 2 Each 160 A TPN MCCB 35 KA.ii) 4 Each 63 A TPN MCCB 25 KA.iii) Two (2) Each Star delta Starters complete with . ON/OFF, indication lamp, contactors ammeter with suitable C.T's, sufficient Each of potential free spare contacts, etc. suitable for 50 HP and 12 HP motor. iv) Wiring from pressure switch to starter - Lot v) Three (3 No. ) DOL Starter with single phase protection feature. ON/OFF, indication lamp, contactors ammeter with suitable C.T's, sufficient Each of potential free spare contacts, etc. suitable for upto 6 HP motor.vi) Set of control system to make the system automatic as per functional requirements.vii) Wiring from pressure switch to starter – Lotix) One (1) no. pressure switch.x) Wiring from pressure switch to Diesel engine control panel. |
| 126 | Note:i) Separate neutral link to be provided wherever TP MCCB are used.ii) Following provisions to be made in the fire panel:-a) Audio visual alarm & indications having disconnect/reset facility with a range of 1/2 km. Annunciator to be provided in the Fire panel with hooter and acknowledge, test and reset PBs. The indication shall come on when electrical driven pump set fails to start on pressure drop or when there is power failure during pressure drop.b) Facility for mode selection ie auto or manual test & local/remote.c) Protection failure & control cabling. d) Panel shall be interlocked in such a way when fire pump starts on pressure drop in the header, supply to working chiller A/c panel is disconnected.e) Remote indication of ON/OFF/ TRIP shall be provided through potential free contact.f) Provision of remote starting/ stopping (manual) of the engine shall be made. |
| 127 | Design , fabrication , Supply, installation, testing and commissioning of following fire fighting panel suitable for 415 V, 3 phase, 4 wires, 50 Hz power distribution system. The panel shall be free standing floor mounting sheet metal enclosed dust and vermin proof conforming to IP-56, compartmentalized design, fabricated out of 14 SWG sheet steel, painting, earthing numbering, danger plate as per specifications and drawings , flush front with Aluminium busbars, separate earth bus bars to be provided throughout the length of the panel. The incoming and outgoing feeder breakers, fuses, indicating lamps etc shall be accommodated in a modular multitier arrangement. The painting shall done as per relevant IS codes/as specified in the specifications. Adequate size cable alley shall be provided all round the panel and in the back for each cable bending and termination. The panel shall be fabricated by CPRI/TAC/Fire authority approved vendor. The outgoing feeders inside the panel shall be connected through solid bus bars. Flexible cable links are not acceptable.Bus bars shall be provided with heat shrinkable sleeves and shall be colour coded. The panels shall be suitable for cable entry from top. The minimum fault rupturing of all incoming and outgoing switches/breakers shall be 35 KA. The panels shall be fabricated after the approval of fabrication drawings. (Note-The description in srl item no 16.38 to 16.40 is to be considered when quoting against this item) |
| 128 | Main Fire Pump Panel:Incoming Section:i) One (1) No. 315A TPN MCCB (35 KA)ii) 630 Amps Aluminium bus bar shall be insulated with heat shrinkable sleeves and shall be color coded.iii) Three (4) Each current transformer (400/5A).iv) One (1) No. ammeter (0-800) Amps with selector switch.v) One (1) No. (0-500 V) voltmeter with selector switch.vi) 1 Set (4 Nos) of phase indication lamps with HRC fuses.vii) Indication for control supply 'healthy'.Outgoing:i) 2 Each 160 A TPN MCCB 35 KA.ii) 4 Each 63 A TPN MCCB 25 KA.iii) Two(2) EachStar Delta Starters complete with . ON/OFF, indication lamp, contactors ammeter with suitable C.T's, sufficient Each of potential free spare contacts, etc. for 75 HP motor. iv) Wiring from pressure switch to starter - Lot v) Three (03) No. DOL Starter with single phase protection feature. ON/OFF, indication lamp, contactors ammeter with suitable C.T's, sufficient Each of potential free spare contacts, etc. suitable for upto 6 HP motor.vi) Set of control system to make the system automatic as per functional requirements.vii) Wiring from pressure switch to starter – Lotviii)One (1) no. pressure switch.Wiring from pressure switch to Diesel engine control panel. |
| 129 | NOTE:-i) Separate neutral link to be provided wherever TP MCCB are used.ii) Following provisions to be made in the fire panel:a) Audio visual alarm & indications having disconnect/reset facility with a range of 1/2 km. Annunciator to be provided in the Fire panel with hooter and acknowledge, test and reset PBs. The indication shall come on when electrical driven pump set fails to start on pressure drop or when there is power failure during pressure drop.b) Facility for mode selection ie auto or manual test & local/remote.c) Protection failure & control cabling. d) Panel shall be interlocked in such a way when fire pump starts on pressure drop in the header.e) Remote indication of ON/OFF/ TRIP shall be provided through potential free contact.f) Provision of remote starting/ stopping (manual) of the engine shall be made. |
| 130 | Supply, installation, testing & commissioning of following sizes of 1100 V grade PVC armoured copper cables, PVC insulated PVC sheathed, including cable trays of minimum 300 mm width /supports as per site conditions. |
| 131 | All as per srl item no 16.41 above,size 3C x 35 Sq.mm. |
| 132 | All as per srl item no 16.41 above,size 3C x 10 Sq.mm. |
| 133 | All as per srl item no 16.41 above,size Control Cable 4 C x 1.5 sq.mm. |
| 134 | Supply & making end termination with brass double compression glands for the following PVC insulated, PVC sheathed & armoured 1100 V grade copper cable including cost of crimping lugs/ferrules, compression glands, solder, cable sockets, insulation tape etc complete as required. |
| 135 | All as per srl item no 16.45 above,3C x 35 Sq.mm. |
| 136 | All as per srl item no 16.45 above,3C x 10 Sq.mm. |
| 137 | All as per srl item no 16.45 above,Control Cable 4 C x 1.5 sq.mm. |
| 138 | Design, supply and applying two coat of 4 mm thick antirust protection including primer and lap of 25 mm on M.S. pipe of 150 mm dia in trenches or complete including surface preparation coating and wrapping shall be confirm to ISI 10221 including conducting Holiday Test. |
| 139 | Supplying, Installation, Testing and Commissioning of Water flow switch i/c connection, controls wiring complete all as directed and specified. |
| 140 | M&L for fixing of CI Foot Valve of size 150 mm complete with nuts ,bolts and washers complete all as specified and direted |
| 141 | M&L for fixing of CI Foot Valve of size 100 mm complete with nuts ,bolts and washers complete all as specified and direted |
| 142 | Supply and fix Dual plates CI wafer type check valve upto 150 mm bore tested to pressure of 15Kg/ Sqcm complete all as specified and directed. |
| 143 | M & L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed .(Note- This item is to be catered in external electrification works and fire hydrant & sprinkler system works) |
| 144 | Providing & fixing air release valve of 25 mm dia and 25 mm dia gun metal gate valve with fittings etc. to be installed at risers complete all as specified and directed . |
| 145 | Supply, erection, testing and commissioning of dia 150mm Wet Automatic Alarm Control valve, internally and externally painted, pre-trimmed with bi-pass connection, test and drain connection, tested to 1.5 times the working pressure, with pressure gauge, Turbine type water motor gong,with required flanges etc . |
| 146 | Providing and laying light duty non pressure NP-3 Class RCC pipe S/S jointed with stiff mixture in the proportion 1:2, 300 mm dia R.C.C. Hume pipe for underground hydrant pipe at road crossings including collar pieces and filling inside of pipe with sand complete as required including necessary excavations and back filling. (For road crossing) |
| 147 | Supply and fix MS Cabinet ( approx 750mm x 600mm x 450 mm ) to enclose fire brigade inlet connection fabricated from 16 gauge sheet with full front glass door and locking arrangement painted and mounted on masonry platform complete all as sirected and specified. |
| 148 | Supply, erection, testing and commissioning of 4 Way fire brigade inlet connection to wet riser system which comprises of 4 No. 63 mm dia Gun metal NRV, 1 No. powder coated weather proof standard hose box suitable for accommodating the above components fabricated out of 16 SWG MS sheet with central opening, glazed front incluiding necessary fittings the word FIRE BRIGADE DRAW OFF to be painted on the box complete all as specified and directed. |
| 149 | Supply and fixing of framed brackets of angles cut to shape, drilled and countersunk for screw, including bending and welding angles as necessary, confirming to Fe.290 Grade, complete all as specified and directed. |
| 150 | Providing and making drainage provision for the wet riser with 50mm dia MS (heavy duty) pipe, ball valve, fittings etc. as required maximum length of pipe 2 RM , complete all as specified and directed. |
| 151 | Supply, erection, testing and commissioning of fire brigade draw off connection confirming to IS : 4038-1986 with 150 mm Non return valve/ strainer incluiding necessary fittings the word FIRE BRIGADE DRAW OFF to be painted on the box complete all as specified and directed. |
| 152 | Supply, erection, testing and commissioning of TWO WAY fire brigade inlet connection to wet riser system which comprises of 2 No. 63 mm dia Gun metal NRV, 1 No. powder coated weather proof standard hose box suitable for accommodating the above components fabricated out of 16 SWG MS sheet with central opening, glazed front incluiding necessary fittings the word FIRE BRIGADE DRAW OFF to be painted on the box complete all as specified and directed. |
| 153 | Supply and fixing of SS flexible Pipe 25mm dia, UL Listed / FM Approved tested up to 10-16 kg /cm2 pressure of length 1000 mm to 1500mm as required and specified. |
| 154 | OVERHEAD WATER TANKSProviding and Fixing Hot compressed molded SMC (sheet molding compound) panel tanks for 5000 litres capacity of as per BIS : 14399 Part-l & Part-ll lSl Marked SMC Panel Tanks. Roof & Base of SMC Panel tanks having panels of size 1.00 metre X 1.00 metre, 1.00 meter X 0.5 meter Side Walls of tanks shall be constructed using SMC panels of size 1.00m x 1.00m panel as per site requirement. One manhole of diameter 600mm should be provided on the roof of tank with lockable lid and FRP ladder inside the tank (if tank height is more than 1m) and aluminium ladder with wall mounting arrangement outside the tank for access. Tanks must have vertical iron posts tied firmiy with Tie rods. The panel should withstand Hydrostatic pressure of at least 4 times the working load and should be provided with HDG bolts, nuts, washers, food grade foam gasket, cleats, including PVC pipe support of 110mm dia fo.r the roof of top panels. Tank shall be erected on steel base which must be kept at RCC base foundation at site as per manufacturer's specifications & design.inlei and outlet, overflow & drain should be provided with tank. The Tank installation work will be carried out at roof of building /ground level. (Note.- The tanks panels must be printed with lSl Logo, lSl Certification Number, CML Number, Batch Number etc.)Note : (a) The tank should be provided with Aluminium body water level indicator with clear tube type and brass nozzle. |
| 155 | Providing and Fixing Hot compressed molded SMC (sheet molding compound) panel tanks for 10,000 Litres capacity as per BIS : 14399 Part-l & Part-ll lSl Marked SMC Panel Tanks of approved brands. Roof & Base of SMC Panel tanks having paneis of size 1.00 metre X 1.00 metre, 1.00 meter X 0.5 meter Side Walls of tanks shall be constructed using SMC panels of size 1.00m x 1.00m panel as per site requirement. One manhole of diameter 600mm should be provided on the roof of tank with lockable lid and FRP ladder inside the tank (if tank height is more than 1 metre) and aluminium ladder with wall mounting arrangement outside the tank for access. Tanks must have vertical iron posts tied firmiy with Tie rods. The panel should withstand Hydrostatic pressure of at least 4 times the working load and should be provided with HDG bolts, nuts, washers, food grade foam gasket, cleats, including PVC pipe support of 110mm dia for the roof of top panels. Tank shall be erected on steel base which must be kept at RCC base foundation at site as per manufacturers specification & design inlet and outlet, overflow & drain should be provided with tank. The Tank installation work will be carried out at roof of building /ground level. (Note.- The tanks panels must be printed with lSl Logo, lSl Certification Number, CML Number, Batch Number etc.)Note : (a) The tank should be provided with Aluminium body water level indicator with clear tube type and brass nozzle. SCHEDULE OF CREDIT Notes:-(a) The items and quantities given under in the respective columns are provisional; however, the rates inserted for credit are firm. The recovery for the credit shall be made for the actual quantities ordered and retrieved from the demolition/dismantling /taking down under respective items of BOQ. Contractor shall be permitted to remove the materials indicated in this credit schedule only after affecting the recovery for the same from the RAR/Final bill asapplicable and after written permission is obtained by the contractor from the Engineer-in-Charge. (b) Tenderers are advised to visit the site to ascertain the worth value, prevailing conditions of the existing materials for which credit is to be afforded. No claim whatsoever on account of above shall however be entertained at any stage whether the contractor (s) inspected the site or not. (c) The old materials obtained will not be allowed to be re-used in the work unless it is specifically mentioned in the description of relevant items of BOQ. All other serviceable/ salvage value materials obtained from the site other than those considered in this schedule shall be Govt. property and contrator’s quoted rates shall be deemed inclusive of removing such material to MES store yard of the Engineer-in-Charge, who will take such material on charge. In case of the dispute related to the interpretation of the provision with regard to the credit schedule, the decision of the Accepting Officer shall be final & binding. Sl No DESCRIPTION OF ITEM A/U QTY RATE AMOUNT REMARKS |
| 156 | Providing and Fixing Hot compressed molded SMC (sheet molding compound) panel tanks for 10,000 Litres capacity as per BIS : 14399 Part-l & Part-ll lSl Marked SMC Panel Tanks of approved brands. Roof & Base of SMC Panel tanks having paneis of size 1.00 metre X 1.00 metre, 1.00 meter X 0.5 meter Side Walls of tanks shall be constructed using SMC panels of size 1.00m x 1.00m panel as per site requirement. One manhole of diameter 600mm should be provided on the roof of tank with lockable lid and FRP ladder inside the tank (if tank height is more than 1 metre) and aluminium ladder with wall mounting arrangement outside the tank for access. Tanks must have vertical iron posts tied firmiy with Tie rods. The panel should withstand Hydrostatic pressure of at least 4 times the working load and should be provided with HDG bolts, nuts, washers, food grade foam gasket, cleats, including PVC pipe support of 110mm dia for the roof of top panels. Tank shall be erected on steel base which must be kept at RCC base foundation at site as per manufacturers specification & design inlet and outlet, overflow & drain should be provided with tank. The Tank installation work will be carried out at roof of building /ground level. (Note.- The tanks panels must be printed with lSl Logo, lSl Certification Number, CML Number, Batch Number etc.)Note : (a) The tank should be provided with Aluminium body water level indicator with clear tube type and brass nozzle. SCHEDULE OF CREDIT Notes:-(a) The items and quantities given under in the respective columns are provisional; however, the rates inserted for credit are firm. The recovery for the credit shall be made for the actual quantities ordered and retrieved from the demolition/dismantling /taking down under respective items of BOQ. Contractor shall be permitted to remove the materials indicated in this credit schedule only after affecting the recovery for the same from the RAR/Final bill asapplicable and after written permission is obtained by the contractor from the Engineer-in-Charge. (b) Tenderers are advised to visit the site to ascertain the worth value, prevailing conditions of the existing materials for which credit is to be afforded. No claim whatsoever on account of above shall however be entertained at any stage whether the contractor (s) inspected the site or not. (c) The old materials obtained will not be allowed to be re-used in the work unless it is specifically mentioned in the description of relevant items of BOQ. All other serviceable/ salvage value materials obtained from the site other than those considered in this schedule shall be Govt. property and contrator’s quoted rates shall be deemed inclusive of removing such material to MES store yard of the Engineer-in-Charge, who will take such material on charge. In case of the dispute related to the interpretation of the provision with regard to the credit schedule, the decision of the Accepting Officer shall be final & binding. Sl No DESCRIPTION OF ITEM A/U QTY RATE AMOUNT REMARKS |
| 157 | Old ceiling/linning/panelling/boarding |
| 158 | Old WHB Mixer of any description |
| 159 | Old health faucet |
| 160 | Old WHB/EWC of any description |
| 161 | Old toilet paper holder |
| 162 | Old Bricks tiles |
| 163 | Old PVC OHT 500 litres |
| 164 | Old unserviceable point wiring 1.5/2.5/4.0 sqmm without switch socket 5/15 amps, lamp holder, fan regulator ceiling rose, etc. |
| 165 | Old Unserviceable Switch, Socket, fan regulator, lamp holder,ceiling rose etc |
| 166 | Old unserviceable light fittings (Any Size/Type) |
| 167 | Old unserviceable Security light (Any Size/Type) |
| 168 | Old U/S materials retrieved from Sub-Main 1.5/2.5/4/6/10 sqmm |
| 169 | Old U/S materials retrieved from VTPN DB /SPN DB 8 way/12 way/ single pole and neutral enclosure |
| 170 | Old U/S MCB SP/SPN of any type |
| 171 | Old U/S earthing Total = Rs 322124.0 Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedNov 21, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 7 daysNov 23, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 9 daysTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender