Tender For special Repair For Conversion Of Oh Lt Acsr Line To Lt Ug Cable Alongwith Misc Connected Items At Yogender Vihar Under Ge Gwalior
Tender Value
66.99 Lakhs
Estimated cost
Bid Submission
02 Dec 2026
10 days left
EMD
1.26 Lakhs
Bank guarantee accepted
Document Fee
1000
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Gwalior → Madhya Pradesh
EMD Exemption
Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender for special Repair For Conversion Of Oh Lt Acsr Line To Lt Ug Cable Alongwith Misc Connected Items At Yogender Vihar Under Ge Gwalior
BOQ
| Sl. No. | Item Description |
| 1 | Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following sizes:- |
| 2 | 10 Sqmm 4 core |
| 3 | 16 Sqmm 4 core |
| 4 | 25 Sqmm 4 core |
| 5 | 35 Sqmm 3.5 core |
| 6 | 50 Sqmm 3.5 core |
| 7 | 70 Sqmm 3.5 core |
| 8 | 95 Sqmm 3.5 core |
| 9 | 120 Sqmm 3.5 core |
| 10 | 150 Sqmm 3.5 core |
| 11 | 240 Sqmm 3.5 core |
| 12 | Supply and fix , test , commissioning of CPRI approved LT weather proof panel board powder coated outdoor type double door shutter, made out of CRCA 3.15 mm thick outer and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outoor, floor mounting type with closed bus bar, chamber and with Aluminium bus bar with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digital ammeter 0-500A, digital voltmeter 0-500 Volts, CT's of suitable ratio, indicator lamps R-Y-B, selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc. The bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron )(Main Panel Near KV school from Transformer & Main Panel Near P-140 block from Transformer) a) Aluminium bus bar capacity 800 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b)MCCB FP 500 Amps 36 kA -01 No (I/C)c) MCCB FP 250 Amps 36 kA - 04 Nos (O/G to FP) f) MCB SPN 16 Amps 10 kA - 01 No g) Timer with synchronous timer 0-24 Hrs suitable for street light control and with suitable contactor single phase 20 Amps capacity - 01 Set |
| 13 | Supply and fix , test , commissioning of CPRI approved LT weather proof panel board powder coated outdoor type double door shutter, made out of CRCA 3.15 mm thick outer and 1.6 mm thick for inner door confirming to IS 8623 with angle iron 50x50x6 mm outoor, floor mounting type with closed bus bar, chamber and with Aluminium bus bar with necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supply as per CPRI approved including provn of digital ammeter 0-500A, digital voltmeter 0-500 Volts, CT's of suitable ratio, indicator lamps R-Y-B, selector switches and internal wiring including making PCC block type 0.6 Mtr above ground level grouting etc all as specified and directed with the following Work also includes provision of suitable size of cable glands, cable lugs, nut, bolts, washers etc. The bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron )(Main Panel {Near P-106 (Pool A)) from TFR} a) Aluminium bus bar capacity 600 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b)MCCB FP 400 Amps 36 kA -01 No (I/C)c) MCCB FP 250 Amps 36 kA - 01 Nos (O/G to FP)d) MCCB FP 200 Amps 36 kA - 01 Nos (O/G to FP) e) MCCB FP 125 Amps 16 kA - 01 Nos (O/G to FP)f) MCB SPN 16 Amps 10 kA - 01 No g) Timer with synchronous timer 0-24 Hrs suitable for street light control and with suitable contactor single phase 20 Amps capacity - 01 Set |
| 14 | ditto as per item No 2 above but comprising of following items(Feeder Panel - No 01 {For near Block No P-156, P-153 & P-168 (Pool B) from MP & Busbar Panel} a) Aluminium bus bar capacity 300 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 200 Amps 36 kA - 01 No (I/C)c) MCCB FP 40 Amps 16 kA - 08 Nos d) MCCB FP 63 Amps 16 kA - 01 No |
| 15 | ditto as per item No 2 above but comprising of following itemsFeeder Panel - No 03 (For near Block No P-171 and P-138) from Bus Bar panel and Hathikhana offrs messa) Aluminium bus bar capacity 400 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 250 Amp 36 kA -01 No (I/C)c) MCCB FP 100 Amps 16 kA - 01 Nos (O/G )d) MCCB FP 40 Amps 16 kA -09 Nos (O/G) |
| 16 | ditto as per item No 2 above but comprising of following itemsFeeder Panel - No 02 {For near Block No P-94, P-106, P-99 & P-92) from MP and Busbar panel} a) Aluminium bus bar capacity 200 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 125 Amps 16 kA - 01 Nos (I/C) c) MCCB FP 40 Amps 16 kA - 07 No |
| 17 | ditto as per item No 2 above but comprising of following itemsFeeder Panel - No 04{(For near Block No P-95 & P-132) from MP (Pool A) } a) Aluminium bus bar capacity 150 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 100 Amps 16 kA - 01 Nos (I/C) c) MCCB FP 40 Amps 16 kA - 04 No |
| 18 | Ditto as per item No 2 above but comprising of following itemsBus Bar Panel a) Aluminium bus bar capacity 800 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 500 Amps 36 kA - 01 Nos (I/C) |
| 19 | Ditto as per item No 2 above but comprising of following itemsBus Bar Panel a) Aluminium bus bar capacity 600 Amps for Phase-R-Y-B-3 Nos & one for neutral -1 No b) MCCB FP 350 Amps 36 kA - 01 Nos (I/C) |
| 20 | M&L Cable route indicator of size 100mm dia embossed as LT round shaped 10mm thick with marking of 1.1 KV, LT welded bolted on angle iron of 25x25 of 60cm length grouted in PCC (1:3:6) type C-2 using block size of 150x150x150mm embedded in ground including not exceeding earth work complete all as specified and directed. |
| 21 | Supply & fix Junction box of size 280 X 170 X 130 mm Hinged (L) wiith 2 way connector mounted on epoxy insulators for looping of cable for 1 Phase and 1neutral fixed on pole with the help of MS nuts bolts and MS clamps-2 Nos of size 40 mm X 4 mm thick with one No MCB SP 6 Amp capacity mounted on din rail inside box. work also includes making suitable hole in pole to make connections to fitting if required at site and provisioning of 1.0 sqmm 3.0 core flexible PVC insulated copper cable from junction box to connector of street light. |
| 22 | M&L for earthing complete with galvanized steel earth plate electrode 60cmX60cmX6mm thick buried directly in ground, earth pit not less than 2.25m deep below normal GL with top edge of the earth plate not less than 1.25m below GL connected with earth strip 32 x 6 by means of check nuts, bolts, nuts, washers of GI or steel all as shown in plate no. 3 of MES sch. Pt 0I, connected to main switch board all as specified and testing on completion including provision of earth strip protected by galvanized iron 15 mm dia light grade including all excavation, earth work, PCC, RCC cover, watering by funnel etc. complete including testing on completion complete all as specified directed |
| 23 | All as per item No 12 above but using 4 mm GI wire complete all as specifed directed. |
| 24 | Supply and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed by GE. (Note: Excavation and concrete shall be measured and paid separately). |
| 25 | M&L Cable joining kit for LT cable for outdoor termination in repair heat shrink type joint complete with joining material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 sqmm to 70 sqmm. |
| 26 | M&L Cable joining kit for LT cable for outdoor termination in repair heat shrink type joint complete with joining material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm. |
| 27 | M&L Cable joining kit for LT cable for outdoor termination in repair heat shrink type joint complete with joining material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 150 sqmm to 240 sqmm. |
| 28 | Supply and fixing LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. |
| 29 | M&L for Gl Brackets bending & shaping of size 40 mm dia galvanised iron pipe light grade over all length 0.60 mtr including necessary clamps, brackets and bolts etc to fixing on pole complete. |
| 30 | Material and labour for cutting the existing bituminous road/ hard standing to size not exceeding 45 cm wide and depth not less than 45 cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200 mm depth with plain cement concreet 1:2:4 type C1 using 20mm grade aggregate all as specified and directed. |
| 31 | S&F GI pipe light grade of dia 50, mm laying in road and along with poles for cable protection complete with all fitting laid in tranches directed. |
| 32 | S&F GI pipe light grade of dia 80, mm laying in road and along with poles for cable protection complete with all fitting laid in tranches directed. |
| 33 | S&F GI pipe light grade of dia 100, mm laying in road and along with poles for cable protection complete with all fitting laid in tranches directed. |
| 34 | Dismantling & taking down ACSR conductor of any size after taking necessary shut down for 11KV OH line by loosening the binding wires jumpers ect complete all as specified and as directed. |
| 35 | Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside all as specified & directed. |
| 36 | Dismantling GI wire of size 4 sqmm etc. complete and setting aside all as specified & directed. |
| 37 | Dismantling insulators any type, any size setting aside all as specified & directed. |
| 38 | Dismantling & taking down Main Panel any size setting aside all as specified & directed. |
| 39 | Dismantling and Taking down Old cable of all sizes XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of all sizes. |
| 40 | Fixing of LED street light any types complete fittings including connecting wire. all as specified. |
| 41 | Fixing of street light brackets ifixed on LT poles including MS clamps nuts bolts etc complete all as specified. |
| 42 | Excavation in tenches not exceeding 1.5m wide and not exc 1.5m depth and getting out in soft/loose soil complete all as specified and as directed. |
| 43 | Excavation in tenches not exceeding 1.5m wide and exc 1.5m and not exceeding 3 m depth and getting out in soft/loose soil complete all as specified and as directed. |
| 44 | Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed. |
| 45 | M&L for sand filling/cushioning in trenches for cable protection including consolidation complete all as directed. |
| 46 | Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as directed. |
| 47 | Supplying and laying un reinforced precast concrete cable cover, Class LV, Type I, flat, size 250mm x 150mm x 40mm complete all as specified and directed |
| 48 | M&L for PCC 1:3:6, type C2 (using 40mm graded stone aggregate) as in foundation, filling and mass concrete all as specified and directed. |
| 49 | M&L for PCC 1:2:4 type B-0 using 12.5 mm graded BT stone aggregate as in bed block for hold fast or coping including necessary form work complete all as specified and directed. Please Enable Macros to View BoQ information |
AI Tender Summary
Tender Timeline
Oct 31, 2026
11:30 IST
Tender Published
Tender notice published.
CompletedDec 02, 2026
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
Upcoming · 10 daysDec 07, 2026
Bid Opening Date
Technical bids will be opened and evaluated.
Upcoming · 15 daysTender Documents
Download All (ZIP) ↓
Disclaimer